| Plan Review Stops For Permit 06081713 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
3 |
Status |
P |
Date |
2007-04-30 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2007-04-30 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2007-04-30 |
Time |
08:31 |
Sent To |
|
|
| Notes |
| 2007-04-30 08:33:48 | PERMIT WAS ATTACHED TO 6612 GEORGIA AVE .THE JOB | | | LOCATION IS AT THE SOUTH SIDE OF THE PROPERTY , BASED | | | ON PREVIOUS COMMENTS. | | | | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | OFFICE:822-1239 | | | FAX: 822-1249 | | | E-MAIL:[email protected] |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2006-09-25 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-09-25 |
Time |
08:11 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-09-25 |
Time |
08:11 |
Sent To |
|
|
| Notes |
| 2006-09-25 00:00:00 | FIELD VERIFICATION DONE BE FD ON SEPT 22 | | | , JOB LOCATION IS AT 6612 GEORGIA AVE, | | | THE SOUTH SIDE BLDG ON THE PCN = | | | 74434408050002770 |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2006-09-11 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-09-11 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-09-11 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2006-09-11 00:00:00 | 2 PARCELS HAVE THE SAME ADDRESS AND SAME | | | OWNER .PROJECT UNDER REVIEW. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2007-09-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-09-25 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-09-25 |
Time |
09:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2007-07-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-07-25 |
Time |
17:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-07-25 |
Time |
17:34 |
Sent To |
|
|
| Notes |
| 2007-07-25 17:45:59 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.)A SITE PLAN WAS PROVIDED IN RESPONSE TO CORRECTION | | | #7, A REQUEST FOR A SURVEY TO DETERMINE COMPLIANCE WITH | | | FBC TABLE 602.A SITE PLAN WAS PROVIDED, BUT IT SHOWS | | | A SECTION OF THE BUILDING HATCHED WHICH ENCROACHES THE | | | PROPERTY LINE.DOES THIS BUILDING ENCROACH THE | | | PROPERTY LINE?NORTH ON THE SITE PLAN DOES NOT | | | CORRELATE WITH THE NORTH ON THE FLOOR PLAN.IT APPEARS | | | THAT NORTH ON THE FLOOR PLAN IS ACTUALLY WEST.IT | | | APPEARS THAT THE WEST AND NORTH ELEVATIONS OF THE | | | BUILDING ARE ON THE PROPERTY LINE, REQUIRING A 3 HOUR | | | FIRE RATING FBC TABLE 602.NOTE THAT THE FEC EASEMENT | | | IS NOT CONSIDERED OPEN SPACE.TYPE IIIB REQUIRES 2 | | | HOUR BEARING WALLS FBC TABLE 601. | | | | | | THE SITE PLAN IS NOT LEGIBLE.PROVIDE A COPY OF THE | | | SURVEY AS REQUESTED WHICH WILL CLEARLY SHOW THE | | | BUILDING FOOTPRINT IN RELATION TO THE PROPERTY LINE. | | | | | | 2.)SEE ELECTRIC COMMENTS REGARDING THE ENERGY CALCS. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-05-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-05-08 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-05-08 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2007-05-08 09:44:27 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC RFLORIDA BUILDING CODE 2004 | | | RESIDENTIAL | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | FROM THE PREVIOUS LISTS, NUMBERING REMAINING THE SAME | | | FOR CONSISTENCY: | | | | | | 1.)ADDRESSED. | | | | | | 2.)AS AGREED, THIS IS A CHANGE OF OCCUPANCY.PLEASE | | | INCLUDE THIS INFORMATION (CHANGE OF OCCUPANCY) IN THE | | | BUILDING CODE CHECKLIST AS THE CHANGE OF OCCUPANCY | | | REQUIRES COMPLIANCE WITH ALL REQUIREMENTS OF FBC EB | | | CHAPTER 8.SOME COMMENTS ARE DUE TO THE CHAPTER 8 | | | REQUIREMENTS. | | | 7.)PROVIDE A SURVEY FOR THIS PROPERTY | | | TO DETERMINE COMPLIANCE WITH FBC TABLE | | | 602. | | | | | | 8.)1ST REVIEW COMMENT - THE NORTH WALL APPEARS TO BE | | | A | | | TENANT SEPARATION WALL; WHAT OCCUPANCY CLASSIFICATION | | | IS THAT SPACE?SHOW | | | COMPLIANCE WITH FBC TABLE 302.3.2. | | | | | | 2ND REVIEW COMMENT - THE PLAN WAS REVISED TO SHOW B | | | OCCUPANCY.NO COMPLIANCE WITH FBC TABLE 302.3.2 | | | SHOWN. | | | | | | 3RD REVIEW COMMENT - AS DISCUSSED, IF THIS IS A | | | SEPARATED USE FBC302.3.2, A 3 HOUR OCCUPANCY SEPARATION | | | IS REQUIRED BETWEEN B AND F1, FBC TABLE 302.3.2.IF | | | THIS IS A NON SEPARATED USE FBC302.3.1, YOU MUST SHOW | | | COMPLIANCE WITH THE MOST STRINGENT OCCUPANCY FBC TABLE | | | 503, FBC TABLE 601, FBC TABLE 602.IF ALLOWABLE AREA | | | INCREASES ARE USED, SHOW ALL CALCULATIONS ON THE PLAN. | | | CODE COMPLIANCE IS TO BE CLEAR AND IS TO BE | | | INCORPORATED INTO THE PLAN (CANNOT BE ADDRESSED THROUGH | | | A RESPONSE LETTER). | | | | | | WHEN SHOWING REQUIRED FIRE RESISTANCE, EITHER SPECIFY | | | AN APPROVED LISTING OR CALCULATED FIRE RESISTANCE | | | (LISTING ALL COMPONENTS AS WELL AS TIME ASSIGNED TO | | | EACH COMPONENT), FBC CHAPTER 7. | | | | | | 10.)PROVIDE OVERALL DIMENSIONS OF THE | | | SPACE ON THE LIFE SAFETY SHEET A120.1. (NOT ADDRESSED. | | | OVERALL DIMENSIONS ARE NOT SHOWN ON ANY OF THE FLOOR | | | PLANS PROVIDED.) | | | | | | 11.)SEE FBC306.2.FOOD PROCESSING IS | | | FACTORY OCCUPANCY CLASSIFICATION. | | | CLARIFY WHY YOU HAVE DECLARED BUSINESS | | | OCCUPANCY FOR THE FOOD PROCESSING AREA. | | | SEE FBC302.1, PORTIONS OF STRUCTURES ARE | | | TO BE CLASSIFIEDWITH RESPECT TO | | | OCCUPANCY. | | | | | | 3RD REVIEW - NOT ADDRESSED.PER MY CONVERSATION WITH | | | THE ARCHITECT, THE FOOD IS PREPARED AND SERVED HOT AT | | | ANOTHER LOCATION.DESPITE THIS ADDITIONAL INFORMATION | | | (THE FACT THAT THE FOOD LEAVES THE FACILITY HOT RATHER | | | THAN COLD), I THINK THAT THE CORRECT OCCUPANCY | | | CLASSIFICATION IS F1, FBC306.2.ARCHITECT IS TO EITHER | | | REVISE THE OCCUPANCY CLASSIFICATION ON THE PLAN AND | | | SHOW CODE COMPLIANCE OR SUBMIT JUSTIFICATION (IN | | | WRITING, PRIOR TO THE NEXT RESUBMITTAL) FOR THE | | | BUSINESS OCCUPANCY DECLARED TO BE REVIEWED BY ASSISTANT | | | BUILDING OFFICIAL.AS DISCUSSED IN OUR TELEPHONE | | | CONVERSATION, IT APPEARS THAT A NON SEPARATED USE | | | FBC302.3.1 MAY BE AN OPTION. | | | | | | 16.)SIGN THE OWNER/AGENT LINE OF THE | | | ENERGY CALC FBC13-103.1. | | | | | | 3RD REVIEW - THE PREPARER AND OWNER AGENT ARE TO SIGN | | | THE ENERGY CALCS. | | | | | | 17.)THE SQUARE FOOT AREA ON THE ENERGY | | | CALC DOES NOT MATCH THE PLAN.NO | | | UNCONDITIONED AREA SHOWN ON THE ENERGY | | | CALC, UNCONDITIONED AREA SHOWN ON PLAN. | | | | | | 3RD REVIEW - PLEASE DECLARE TOTAL SF AREA FOR THE | | | TENANT SPACE, BOTH CONDITIONED AND UNCONDITIONED.WHEN | | | SCALED, THE AREA IS APPROXIMATELY 1568 SQUARE FEET. | | | ENERGY CALCS STATE 1750 CONDITIONED, 1750 | | | CONDITIONED/UNCONDITIONED.OCCUPANT LOAD IS 30 AT | | | 100SF PER PERSON.CODE COMPLIANCE WITH OCCUPANT LOAD | | | AND EGRESS REQUIREMENTS CANNOT BE DETEREMINED DUE TO | | | INSUFFICIENT/INCOMPLETE/INCONSISTENT INFORMATION. | | | | | | THE ENERGY CALCS DID NOT PASS ELECTRIC REVIEW.NOTE | | | THAT ENERGY CALCS ARE REQUIRED; CORRECT, CODE COMPLIANT | | | ENERGY CALCS ARE REQUIRED FOR PERMIT ISSUANCE. | | | STATUTORY REQUIREMENTS CAN NEVER BE WAIVED OR | | | PROVISO'D. | | | | | | 18.)INTERIOR FINISHES TO COMPLY WITH TABLE 803.5. | | | | | | 3RD REVIEW - THIS WAS ADDRESSED ON SHEET A130. HOWEVER, | | | THE ARCHITECT HAS DECLARED BUSINESS OCCUPANCY BUT THE | | | INTERIOR FINISHES REQUIREMENTS DO NOT COMPLY WITH TABLE | | | 803.5 FOR BUSINESS OCCUPANCY, BUT ARE COMPLIANT FOR | | | F1. | | | | | | 19.)SEE ATTACHED FS 553.80(2)(B). | | | | | | 3RD REVIEW - DUE TO SEVERAL OF THE ABOVE COMMENTS, A 4X | | | PLAN REVIEW FEE HAS BEEN ASSESSED AS REQUIRED BY | | | FLORIDA STATUTE.A BILL IS ATTACHED AND MUST BE PAID | | | WHEN RESUBMITTING. | | | | | | 18.)PROVIDE INFORMATION IN REGARDS TO ACCESSIBLE | | | PARKING, ACCESSIBLE ROUTE.SEE FBC11-4.1.4.6(2). | | | | | | 3RD REVIEW - SEE ATTACHED DETAIL WHICH IS THE CITY OF | | | WEST PALM BEACH STANDARD PARKING DETAIL AND REVISE | | | A110.1.ALSO SHOW THE ACCESSIBLE ROUTE; FROM THE | | | PUBLIC WAY, AND FROM THE ACCESSIBLE PARKING.THIS CAN | | | BE DONE ON THE SITE PLAN. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-11-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-11-14 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-11-14 |
Time |
13:04 |
Sent To |
|
|
| Notes |
| 2006-11-14 13:15:55 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC RFLORIDA BUILDING CODE 2004 | | | RESIDENTIAL | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | FROM THE PREVIOUS LIST, COMMENTS NOT ADDRESSED | | | | | | 1.)DECLARE LEVEL OF ALTERATION FBC EB3 | | | AND INCLUDE FBC EB AS GOVERNING CODE. | | | SEE FBC EB CHAPTER 3 TO DETERMINE LEVEL | | | OF ALTERATION. | | | | | | THE ARCHITECT DECLARED A LEVEL 3 AND FBC EB3.THE | | | CORRECT CODE REFERENCE IS FBC 2004 EXISTING BUILDING. | | | LEVEL 3 IS FOR OVER 50% IMPROVEMENT.THE PLAN SHOWS | | | THAT LESS THAN 30% OF THE BUILDING IS BEING IMPROVED. | | | IF THIS IS A LEVEL 3, PLEASE SHOW COMPLIANCE WITH ALL | | | REQUIREMENTS.IF IT IS NOT,PLEASE REVISE THE NOTE. | | | ALSO THIS IS A CHANGE OF OCCUPANCY; DESIGNER IS TO | | | REVIEW REQUIREMENTS IN CHAPTER 8 FBC EB AND SHOW | | | COMPLIANCE WITH ALL REQUIREMENTS. | | | | | | 2.)THIS APPEARS TO BE A CHANGE OF | | | OCCUPANCY BASED ON OCCUPATIONAL LICENSE | | | ISSUED AND ON RECORD, SEE WWW.WPB.ORG | | | (ONE STOP SHOP, OCCUPATIONAL LICENSES). | | | THE PREVIOUS OCCUPANCY CLASSIFICATION | | | APPEARS TO BE MERCANTILE.SEE FBC306. | | | | | | 7.)PROVIDE A SURVEY FOR THIS PROPERTY | | | TO DETERMINE COMPLIANCE WITH FBC TABLE | | | 602. | | | | | | 8.)THE NORTH WALL APPEARS TO BE A | | | TENANT SEPARATION WALL; WHAT OCCUPANCY CLASSIFICATION | | | IS THAT SPACE?SHOW | | | COMPLIANCE WITH FBC TABLE 302.3.2. | | | | | | THE PLAN WAS REVISED TO SHOW B OCCUPANCY.NO | | | COMPLIANCE WITH FBC TABLE 302.3.2 SHOWN. | | | | | | 10.)PROVIDE OVERALL DIMENSIONS OF THE | | | SPACE ON THE LIFE SAFETY SHEET A120.1. | | | | | | 11.)SEE FBC306.2.FOOD PROCESSING IS | | | FACTORY OCCUPANCY CLASSIFICATION. | | | CLARIFY WHY YOU HAVE DECLARED BUSINESS | | | OCCUPANCY FOR THE FOOD PROCESSING AREA. | | | SEE FBC302.1, PORTIONS OF STRUCTURES ARE | | | TO BE CLASSIFIEDWITH RESPECT TO | | | OCCUPANCY. | | | | | | 16.)SIGN THE OWNER/AGENT LINE OF THE | | | ENERGY CALC FBC13-103.1. | | | | | | 17.)THE SQUARE FOOT AREA ON THE ENERGY | | | CALC DOES NOT MATCH THE PLAN.NO | | | UNCONDITIONED AREA SHOWN ON THE ENERGY | | | CALC, UNCONDITIONED AREA SHOWN ON PLAN. | | | | | | NEW COMMENT: | | | | | | 18.)INTERIOR FINISHES TO COMPLY WITH TABLE 803.5. | | | | | | 19.)SEE ATTACHED FS 553.80(2)(B). | | | | | | 18.)PROVIDE INFORMATION IN REGARDS TO ACCESSIBLE | | | PARKING, ACCESSIBLE ROUTE.SEE FBC11-4.1.4.6(2). |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-09-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-09-18 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-09-18 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2006-09-18 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC RFLORIDA BUILDING CODE 2004 | | | RESIDENTIAL | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)DECLARE LEVEL OF ALTERATION FBC EB3 | | | AND INCLUDE FBC EB AS GOVERNING CODE. | | | SEE FBC EB CHAPTER 3 TO DETERMINE LEVEL | | | OF ALTERATION. | | | | | | 2.)THIS APPEARS TO BE A CHANGE OF | | | OCCUPANCY BASED ON OCCUPATIONAL LICENSE | | | ISSUED AND ON RECORD, SEE WWW.WPB.ORG | | | (ONE STOP SHOP, OCCUPATIONAL LICENSES). | | | THE PREVIOUS OCCUPANCY CLASSIFICATION | | | APPEARS TO BE MERCANTILE.SEE FBC306. | | | | | | 3.)THE COMPANY RJS ARCHITECTS, INC. IS | | | REQUIRED TO HAVE AN ARCHITECT BUSINESS | | | LICENSE.I WAS UNABLE TO LOCATE THIS ON | | | WWW.MYFLORIDALICENSE.COM.PLEASE | | | PROVIDE THE LICENSE NUMBER ON THE PLAN | | | FAC61G1-16.003,004. | | | | | | 4.)SEE COMMENTS FROM ADDRESSING AND | | | ELECTRIC REGARDING THE BUILDING ADDRESS | | | ON THE PLAN.PLEASE RESOLVE AND REVISE | | | PLAN IF NECESSARY. | | | | | | 5.)A120.1 IS USED TWICE, BOTH MARKED | | | LIFE SAFETY PLAN, BUT ONE IS A DEMO | | | PLAN. | | | | | | 6.)BUILDING CODE CHECKLIST, PROVIDE | | | THE TOTAL BUILDING AREA, BUILDING | | | HEIGHT, OTHER TENANT SPACES AND | | | OCCUPANCY TO DETERMINE COMPLIANCE WITH | | | FBC TABLE 503. | | | | | | 7.)PROVIDE A SURVEY FOR THIS PROPERTY | | | TO DETERMINE COMPLIANCE WITH FBC TABLE | | | 602. | | | | | | 8.)THE NORTH WALL APPEARS TO BE A | | | TENANT SEPARATION WALL; WHAT OCCUPANCY | | | CLASSIFICATION IS THAT SPACE?SHOW | | | COMPLIANCE WITH FBC TABLE 302.3.2. | | | | | | 9.)A120.1 SHOWS 1 AND 2 HOUR | | | PENETRATION DETAILS; WHERE WILL THIS BE | | | INSTALLED?NO FIRE RATED WALLS ARE | | | SHOWN ON THE PLAN.SHOW ALL REQUIRED | | | FIRE SEPARATIONS REQUIRED ON THE PLAN. | | | | | | 10.)PROVIDE OVERALL DIMENSIONS OF THE | | | SPACE ON THE LIFE SAFETY SHEET A120.1. | | | | | | 11.)SEE FBC306.2.FOOD PROCESSING IS | | | FACTORY OCCUPANCY CLASSIFICATION. | | | CLARIFY WHY YOU HAVE DECLARED BUSINESS | | | OCCUPANCY FOR THE FOOD PROCESSING AREA. | | | SEE FBC302.1, PORTIONS OF STRUCTURES ARE | | | TO BE CLASSIFIEDWITH RESPECT TO | | | OCCUPANCY. | | | | | | 12.)SEE FBC302.1, FBC302.2.ADDRESS | | | THE MIXED USE OF THE OFFICE AREAS | | | (BUSINESS) AND THE PROCESSING AREA | | | (FACTORY).SHOW COMPLIANCE WITH | | | FBC302.2 OR SHOW REQUIRED FIRE | | | SEPARATION. | | | | | | 13.)LIFE SAFETY NOTE #5 REFERS TO | | | DINING AND SEATING AREAS.NONE SHOWN ON | | | THE PLAN AND THIS CONFLICTS WITH THE | | | NOTE ON THE COVER SHEET WHICH STATES | | | THAT ALL FOOD WILL BE CONSUMED OFF | | | PREMISES.PLEASE CLARIFY. | | | | | | 14.)NOTE 1 HAS REFERENCES TO A, E, I, | | | R OCCUPANCIES.PLEASE REMOVE AS THEY | | | ARE NOT PERTINENT TO THIS JOB AND DO NOT | | | APPEAR TO BE FBC2004 NOTES. | | | | | | 15.)RESTROOM DOOR 3 BLOCKS OVER HALF | | | THE REQUIRED EGRESS WIDTH, SEE | | | FBC1005.2. | | | | | | 16.)SIGN THE OWNER/AGENT LINE OF THE | | | ENERGY CALC FBC13-103.1. | | | | | | 17.)THE SQUARE FOOT AREA ON THE ENERGY | | | CALC DOES NOT MATCH THE PLAN.NO | | | UNCONDITIONED AREA SHOWN ON THE ENERGY | | | CALC, UNCONDITIONED AREA SHOWN ON PLAN. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2007-10-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-04 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-04 |
Time |
10:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-07-13 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-07-07 |
Time |
14:33 |
Sent To |
I |
|
| Notes |
| 2007-07-13 08:41:08 | 2007-07-13 08:41:08 | | | | | | ** UNSAT 4TH REVIEW** | | | | | | 1) NOTE:PLEASE SEE THE PREVIOUS COMMENTS REQUESTED | | | THE ENERGY CALCULATIONS WHICH WERE SUBMITTED TO | | | COORDINATE WITH THE ELECTRICAL PLANS. THERE WAS NO | | | COMMENT THAT THE VERSION OF THE CALCULATIONS NEEDED TO | | | CHANGE. | | | PLEASE SEE THE ENERGY CALCULATIONS NOW SUBMITTED IS | | | VERSION 3.0 WHICH WENT INTO EFFECT DECEMBER 8TH, 2006. | | | PLEASE KNOW HOWEVER AS THIS PROJECT WAS SUBMITTED UNDER | | | THE PREVIOUS CODE BEFORE THE CODE CHANGE OF DECEMBER | | | 8TH, 2006, THE CALCULATIONS NEED TO BE DONE UNDER THE | | | PREVIOUS 2.11 AS SUBMITTED UNDER THE PREVIOUS REVIEW. | | | PLEASE BE SURE TO TRANSFER ALL INFORMATION OVER TO THE | | | CALCULATIONS. | | | PLEASE SEE THE PREVIOUS CALCULATIONS SUBMITTED | | | INDICATED 1750 SQ FT AND NOW THE NEW ONES INDICATE 2970 | | | SQ FT? PLEASE BE SURE THE CALCULATIONS COORDINATE WITH | | | PLANS AND THE CORRECT VERSION. | | | IF THERE ARE ANY QUESTIONS ON THIS PLEASE CALL. | | | | | | | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-07-07 14:54:06 | 2007-07-07 14:54:06 | | | | | | | | | CONTRACTOR CAME IN AND CORRECTED SETS FOR REVIEW ON | | | 7/11 | | 2007-07-07 14:34:21 | 2007/07/07 14:34:21 | | | PLANS REMOVED FROM INCOMING. PLANS WILL BE RETURNED TO | | | INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW | | | IS COMPLETED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-04-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-04-25 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-04-25 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2007-04-25 13:33:06 | | | | | | | ** UNSAT3RD REVIEW** | | | | | | 1) NOTE: PLEASE SEE THEAIC RATINGS SHOW DIFFERENT | | | LENGTHS ON PLANS FROM THE ACTUAL LENGTHS SHOWN ON | | | SHEETS WHERE CONDUITS ARE RUN. | | | PLEASE SEE THE LENGTH SHOWN AS 60FT IS ACTUALLY LONGER | | | BY WHAT IS BEING SHOWN ON PLANS. | | | THE AVAILABLE FAULT CURRENT WILL ACTUALLY BE LESS. | | | 110.9, | | | FBC 106.1.2 | | | | | | 2) NOTE: PLEASE VERIFY VOLTAGE DROP FOR THESE SAME | | | SERVICE CONDUCTORS AS THE LENGTH ON PLANS IS LONGER | | | THAN FIGURES. | | | 13-413. | | | | | | 3) NOTE: PLEASE SEE THE SAME ENERGY CALCULATIONS WERE | | | SUBMITTED BACK AS SUBMITTED ON PREVIOUS SUBMITTAL. | | | PLEASE SEE THE LIGHTING ON CALCULATIONS DO NOT | | | CORRELATE WITH PLANS FOR TYPES OF FIXTURES, NUMBER OF | | | FIXTURES AND WATTAGE. ONLY ONE FIXTURE IS NOTED ON | | | CALCULATIONS. | | | PLEASE ALSO SEE THAT THE ENERGY CALCULATIONS ALSO | | | INDICATE MANUAL MEANS FOR CONTROL OF LIGHTING WHEN THE | | | PLANS INDICATE AUTOMATED MEANS. | | | PLEASE ADJUST. | | | PLEASE ALSO SEE THE SHEETS WHICH ARE REQUIRED TO BE | | | SIGNED DATED AND SEALED NEEDS TO BE THE SHEETS WHICH | | | CONTAIN THE LICENSEE INFORMATION. (2ND SHEET IN). | | | PLEASE SEE THE METHOD AS SHOWN ON PLANS IS *B*, YET | | | ENERGY CALCULATIONS ARE *A*.? | | | PLEASE COORDINATE. | | | 13-415.1.A, 13-415.1.B, 13-415.C, 13-415.2 | | | 13-103.1.1.1 | | | | | | 4) NOTE: PLEASE CLARIFY HOW MANY MAINS ARE ON THE | | | EXISTING SERVICE AND LABEL MAINS , 1OF ? , 2OF ? ETC. | | | 230.2 | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-10-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-27 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-27 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2006-10-27 16:25:55 | *** UNSAT2ND REVIEW****** | | | | | | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW AND | | | SOME NEW COMMENTS DUE TO THE PLANS SUBMITTED. | | | PLEASE SEE NOTES BELOW WHICH ARE TAKEN DIRECTLY FROM | | | PREVIOUS REVIEW. | | | | | | 1) NOTE: OK, HOWEVER PLEASE BE SURE TO CORRECT PERMIT | | | APPLICATION AS ADDRESS STILLS SHOWS 6600. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE PERMIT APPLICATION | | | DOES NOT MATCH WITH THE LEGAL OWNER OF | | | RECORD ON OUR SYSTEM, THE PALM BEACH | | | COUNTY PROPERTY APPRAISER'S WEBSITE OR | | | THE NOTICE OF COMMENCEMENT SUBMITTED. | | | PLEASE CORRECT AND REVISE. | | | | | | | | | 2) NOTE: OK. NOTE #1 | | | | | | 3) NOTE: OK. | | | | | | 4) NOTE:NO, PLEASE SEE AS SHOWN ON PLANS , THIS IS | | | "NOT" CLASSIFIED AS SEPARATE BUILDING BY RATING THE | | | WALL 4HRS. PLEASE SEE DEFINITION OF "FIRE WALL " IN THE | | | FBC. | | | ONE SERVICE OR COMING FROM THE EXISTING SERVICE OR | | | MEETING AN EXCEPTION. PLEASE KNOW, AS SHOWN IN ORDER | | | FOR THIS OFFICE TO GRANT SPECIAL PERMISSION, PLEASE | | | CALL TO GO OVER. PLEASE KNOW A PHONE MEETING WITH THE | | | ENGINEER OF RECORD WOULD BE RECOMMEND AND POSSIBLY THE | | | ARCHITECT TO RESOLVE THIS MATTER MAY BE NEEDED. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE THIS IS A TENANT | | | SPACE PART OF A LARGER BUILDING AND THE | | | NEW SERVICE AS SHOWN IS NOT GRANTED OR | | | PERMITTED. 230.2 | | | ** PLEASE SEE AERIAL MAP PROVIDED. | | | PLEASE SEE SERVICE LOCATION FOR THE | | | EXISTING SERVICE IS TO BE SHOWN. | | | PLEASE SEE SERVICE AS SHOWN IS BEING | | | SHOWN AS AN OVERHEAD SERVICE LOCATED ON | | | THE SOUTH SIDE OF BUILDING WHERE THE | | | BUILDING FROM THE ADJOINING PROPERTY IS | | | LOCATED. CLEARANCES AS REQUIRED UNDER | | | THE FPL SERVICE GUIDELINES AND NEC ARE | | | NOTMET IN EITHER CASE. | | | PLEASE KNOW, THE EXISTING SERVICE FOR | | | THE BUILDING MUST BE USED OR UPGRADED. | | | PLEASE SEE THE 1HR SEPARATION DOES NOT | | | MAKE THIS SPACE A SEPARATE BUILDING. | | | PLEASE SEE FBC DEFINITIONS OF BUILDING, | | | AND REQUIRED "FIRE WALL" IN ORDER TO | | | BECOME A SEPARATE BUILDING. PLEASE SEE | | | REQUIRED "FIRE WALL" WOULD BE A FOUR HR | | | RATED WALL WHICH WOULD PERMIT THE | | | COLLAPSE THE ADJOINING STRUCTURE WITHOUT | | | AFFECT THE STRUCTURAL INTEGRITY OF THE | | | ADJOINING REMAINING BUILDING. | | | | | | 5) NOTE: OK. | | | | | | 6) NOTE:NO, PLEASE SEE MEANS OF EGRESS INTO ANY ONE | | | AREA/ KITCHEN ETC WILL REQUIRE A MEANS FOR OVER RIDING | | | THE TIME OF DAY SCHEDULING.PLEASE SEE REDLINED AREAS | | | ON PLANS. PLEASE ALSO SEE THAT THE OVER RIDES SWITCH IF | | | TIMER TYPE IS TO BE SHOWN WITH A MAX OF 4HRS OR IF AN | | | OCC SENSOR TYPE 30MINS MAX). | | | PLEASE SEE ENERGY CALCULATIONS ARE NOT SIGNED, DATED | | | AND SEALED ON THE CORRECT SHEET. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | IF TRYING TO OBTAIN COMPLIANCE | | | WITH THE 2004 FBC CHAPTER 13,THE | | | LIGHTING CONTROLS AS NOTED ARE NOT | | | COMPLETE AT THIS TIME.PLEASE SHOW THE | | | DETAIL FOR "SYSTEM" BEING PROPOSED. | | | PLEASE ALSO INCLUDE EXISTING OFFICE | | | AREAS ARE REQUIRED TO BE CONTROLLED BY | | | THIS SYSTEM. | | | PLEASE PROVIDE SCHEDULING, OVER RIDE | | | DEVICES ALONG WITH MAX PERMITTED TIMES | | | ON OVER RIDE DEVICES. | | | (4HRS MAX FOR TIMER TYPES, 30MIN MAX ON | | | OCCUPANT SENSOR TYPES). | | | PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND | | | .1.3. | | | | | | 7) NOTE: ?? | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE COMMENTS BASED ON | | | THE PROPOSED ELECTRICAL RISER ARE MUTE | | | AT THIS TIME AS SERVICE SHOWN IS NOT | | | PERMITTED. PLEASE HOWEVER SEE SOME ITEMS | | | BELOW AS ANY SERVICE UPGRADE WILL | | | REQUIRE SOME OF THE SAME ITEMS. | | | PLEASE SEE THE FOLLOWING. | | | MISSING GAS BOND ON THE GROUNDING | | | ELECTRODE SYSTEM, MISSING THE THE | | | EQUIPMENT GROUNDING CONDUCTOR FROM MAIN | | | TO SUB PANELS. PLEASE SEE WHAT APPEARS | | | TO BE A MISPRINT AS 1/4" FOR EQUIPMENT | | | GROUND. | | | PLEASE SEE MISSING AIC RATING FOR | | | MAIN.(SHOWN FOR NEW SUB PANELS). | | | | | | | | | 8) NOTE: OK, NO PANEL "E" SHOWN . | | | | | | 9) NOTE:OK. | | | | | | | | | | | | ** PLEASE SEE POSSIBLE COMMENTS FROM | | | OTHER TRADES WHICH MAY AFFECT THE | | | ELECTRICAL DESIGN/PLANS. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-09-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-10 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-10 |
Time |
08:29 |
Sent To |
|
|
| Notes |
| 2006-09-10 00:00:00 | *** UNSAT****** | | | | | | 1) NOTE: PLEASE SEE PERMIT APPLICATION | | | DOES NOT MATCH WITH THE LEGAL OWNER OF | | | RECORD ON OUR SYSTEM, THE PALM BEACH | | | COUNTY PROPERTY APPRAISER'S WEBSITE OR | | | THE NOTICE OF COMMENCEMENT SUBMITTED. | | | PLEASE CORRECT AND REVISE. | | | | | | | | | 2) NOTE: PLEASE SEE THE ADDRESS ON PLANS | | | NEEDS TO CORRELATE WITH THE LEGAL | | | ADDRESS OF PROPERTY. PLEASE KNOW THAT | | | PERMIT APPLICATION WILL BE ROUTED TO THE ADDRESSING | | | PERSON TO OBTAIN AN ADDRESS | | | EXTENSION FOR THE TENANT SPACE. | | | (UNIT/SUITER #). | | | PLEASE BE SURE TO PLACE CORRECT ADDRESS | | | ON PLANS ALONG WITH ANY REVISED/ NEW | | | SUITE . | | | FAC 61G1-16.004, FAC 61G15-23.002 | | | | | | 3) NOTE: PLEASE SEE MISSING REQUIRED | | | LICENSE INFORMATION ON ALL TITLE BLOCKS | | | FOR ARCHITECTURAL FIRM. PLEASE SEE FAC | | | 61G1-16.004 AND FS 481.219. | | | MISSING THE REQUIRED CERTIFICATE OF | | | AUTHORIZATION NUMBER. | | | THIS IS REQUIRED ON ALL SHEETS AND FOR | | | ALL TRADES WHETHER OR NOT COMMENT IS | | | MADE BY OTHER REVIEWER(S). | | | | | | 4) NOTE: PLEASE SEE THIS IS A TENANT | | | SPACE PART OF A LARGER BUILDING AND THE | | | NEW SERVICE AS SHOWN IS NOT GRANTED OR | | | PERMITTED. 230.2 | | | ** PLEASE SEE AERIAL MAP PROVIDED. | | | PLEASE SEE SERVICE LOCATION FOR THE | | | EXISTING SERVICE IS TO BE SHOWN. | | | PLEASE SEE SERVICE AS SHOWN IS BEING | | | SHOWN AS AN OVERHEAD SERVICE LOCATED ON | | | THE SOUTH SIDE OF BUILDING WHERE THE | | | BUILDING FROM THE ADJOINING PROPERTY IS | | | LOCATED. CLEARANCES AS REQUIRED UNDER | | | THE FPL SERVICE GUIDELINES AND NEC ARE | | | NOTMET IN EITHER CASE. | | | PLEASE KNOW, THE EXISTING SERVICE FOR | | | THE BUILDING MUST BE USED OR UPGRADED. | | | PLEASE SEE THE 1HR SEPARATION DOES NOT | | | MAKE THIS SPACE A SEPARATE BUILDING. | | | PLEASE SEE FBC DEFINITIONS OF BUILDING, | | | AND REQUIRED "FIRE WALL" IN ORDER TO | | | BECOME A SEPARATE BUILDING. PLEASE SEE | | | REQUIRED "FIRE WALL" WOULD BE A FOUR HR | | | RATED WALL WHICH WOULD PERMIT THE | | | COLLAPSE THE ADJOINING STRUCTURE WITHOUT | | | AFFECT THE STRUCTURAL INTEGRITY OF THE | | | ADJOINING REMAINING BUILDING. | | | | | | 5) NOTE: PLEASE SEE THE SIGN CIRCUIT AS | | | BEING SHOWN IS LOCATEDAT THE REAR DOOR | | | WHICH BACKS UP TO THE FEC RAILROAD | | | TRACKS. PLEASE SEE 600.5 WHICH REQUIRES | | | THIS CIRCUIT TO BE LOCATED AT THE FRONT | | | ENTRANCE SUBJECT TO PEDESTRIAN TRAFFIC. | | | | | | 6) NOTE: IF TRYING TO OBTAIN COMPLIANCE | | | WITH THE 2004 FBC CHAPTER 13,THE | | | LIGHTING CONTROLS AS NOTED ARE NOT | | | COMPLETE AT THIS TIME.PLEASE SHOW THE | | | DETAIL FOR "SYSTEM" BEING PROPOSED. | | | PLEASE ALSO INCLUDE EXISTING OFFICE | | | AREAS ARE REQUIRED TO BE CONTROLLED BY | | | THIS SYSTEM. | | | PLEASE PROVIDE SCHEDULING, OVER RIDE | | | DEVICES ALONG WITH MAX PERMITTED TIMES | | | ON OVER RIDE DEVICES. | | | (4HRS MAX FOR TIMER TYPES, 30MIN MAX ON | | | OCCUPANT SENSOR TYPES). | | | PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND | | | .1.3. | | | | | | 7) NOTE: PLEASE SEE COMMENTS BASED ON | | | THE PROPOSED ELECTRICAL RISER ARE MUTE | | | AT THIS TIME AS SERVICE SHOWN IS NOT | | | PERMITTED. PLEASE HOWEVER SEE SOME ITEMS | | | BELOW AS ANY SERVICE UPGRADE WILL | | | REQUIRE SOME OF THE SAME ITEMS. | | | PLEASE SEE THE FOLLOWING. | | | MISSING GAS BOND ON THE GROUNDING | | | ELECTRODE SYSTEM, MISSING THE THE | | | EQUIPMENT GROUNDING CONDUCTOR FROM MAIN | | | TO SUB PANELS. PLEASE SEE WHAT APPEARS | | | TO BE A MISPRINT AS 1/4" FOR EQUIPMENT | | | GROUND. | | | PLEASE SEE MISSING AIC RATING FOR | | | MAIN.(SHOWN FOR NEW SUB PANELS). | | | | | | | | | 8) NOTE: PLEASE SEE MISSING THE PANEL | | | SCHEDULE FOR EXISTING PANEL "E" AND WHERE | | | LOADS ARE DERIVED. | | | 408.4,310.16,240.4, 215.5 ETC | | | FBC 106.1.2 ADMIN SECT. | | | | | | 9) NOTE: PLEASE SEE PLANS SHALL STATE | | | THE ADOPTED CODES RELEVANT TO PLANS AND | | | DESIGN. PLEASE SEE 2002 NFPA-70, 2002 | | | NFPA-72, 2003 NFPA-101 (SHOWN ON "A" | | | SHEETS) AND NFPA-96 2004 ARE ALL | | | REQUIRED AT A MINIMUM. | | | PLEASE SEE NOTES FROM OTHER TRADES FOR | | | OTHER POSSIBLE RELEVANT CODES REQUIRED. | | | | | | ** PLEASE SEE POSSIBLE COMMENTS FROM | | | OTHER TRADES WHICH MAY AFFECT THE | | | ELECTRICAL DESIGN/PLANS. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2007-10-25 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-10-25 |
Time |
12:15 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-10-25 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2007-10-25 12:15:19 | *****APPROVED***** | | | | | | | | | PLAN SHEETSA120.1 AND E-1 WERE STAMPED, INTIALED, AND | | | DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2007-07-26 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-07-26 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-07-26 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2007-07-26 15:44:00 | *****PROVISO***** | | | | | | | | | ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ADDRESSED; HOWEVER THE APPROPIATE PLAN SHEETS WILL | | | BE STAMPED WHEN ALL PLAN REVIEWS HAVE BEEN SATISFIED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-05-07 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-05-07 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-05-07 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2007-05-07 13:49:34 | *****PROVISO***** | | | | | | | | | ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ADDRESSED; HOWEVER THE APPROPIATE PLAN SHEETS WILL | | | BE STAMPED WHEN ALL PLAN REVIEWS HAVE BEEN SATISFIED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2006-12-14 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-12-14 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-12-14 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2006-12-14 15:24:01 | *****UNSAT***** | | | | | | | | | | | | 1.THE NUMERICAL ADDRESS FOR THIS PERMIT IN THE CITY'S | | | COMPUTER SYSTEM (WHICH IS BASED ON THE PROPERTY CONTROL | | | NUMBER) IS 6600 GEORGIA AVENUE, WHEREAS THE SUBMITTED | | | APPLICATION AND THE PLANS HAVE 6612 GEORGIA AVENUE. | | | FILE A NEW NOTICE OF COMMENCEMENT REFLECTING 6612 | | | GEORGIA AVENUE WHERE THE SCOPE OF WORK WILL BE DONE. | | | | | | 2.AS PER NFPA 101, INTERIOR FINISH IN AN | | | UNSPRINKLERED BUILDING SHALL BE CLASS "A" OR "B" IN ALL | | | AREAS. | | | | | | | | | PLEASE RESPOND TO THE ABOVE AND TO THE PREVIOUS FIRE | | | PLAN REVIEW.TO EXPEDITE THE FIRE PLAN REVIEW PROCESS, | | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | | ITEM WAS ADDRESSED. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-09-26 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-09-26 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-09-26 |
Time |
09:47 |
Sent To |
|
|
| Notes |
| 2006-09-26 00:00:00 | ***DENIED*** | | | | | | 1) PLEASE CLARIFY NOTE (5) ON LS PLAN | | | REF: DINING AND SEATING AREAS. IF NOT | | | APPLICABLE, PLEASE REMOVE FROM PLANS. | | | | | | 2) DUCT SMOKE DETECTORS SHALL INITIATE A | | | GENERAL FIRE ALARM IN ACCORDANCE WITH | | | LOCAL REQUIREMENTS. | | | | | | 3) SEPARATE SHOP DRAWINGS AND PERMITS | | | REQUIRED FOR EXHAUST HOOD AND | | | SUPPRESSION SYSTEMS. | | | | | | 4) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL IF APPLICABLE. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2007-08-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-08-17 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-08-10 |
Time |
18:19 |
Sent To |
|
|
| Notes |
| 2007-08-17 07:58:30 | | | | | | | PASSED/PROVISO | | | | | | 1. SHT P-1 THE FOLLOWING INFORMATION IS | | | REQUIRED FOR THE GAS PERMIT: | | | | | | A. OK | | | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE FROM CONTRACTOR IS THAT THE EQUIPMENT IS | | | USED AND WILL BE MOVED FROM AN EXISTING CATERING | | | SERVICE. ALL REQUIRED LABELING SHALL BE ON EQUIPMENT | | | AND VERIFIED AT TIME OF FINAL INSPECTION, (SEE THE | | | FOLLOWING CODE SECTION). THIS IS OK PROVIDING: 301.5 | | | LABEL INFORMATION. | | | A PERMANENT FACTORY-APPLIED NAMEPLATE(S) SHALL BE | | | AFFIXED TO APPLIANCES ON WHICH SHALL APPEAR IN LEGIBLE | | | LETTERING, THE MANUFACTURER?S NAME OR TRADEMARK, THE | | | MODEL NUMBER, SERIAL NUMBER AND, FOR LISTED APPLIANCES, | | | THE SEAL OR MARK OF THE TESTING AGENCY. A LABEL SHALL | | | ALSO INCLUDE THE HOURLY RATING IN BRITISH THERMAL UNITS | | | PER HOUR (BTU/H) (W); THE TYPE OF FUEL APPROVED FOR USE | | | WITH THE APPLIANCE; AND THE MINIMUM CLEARANCE | | | REQUIREMENTS. | | | | | | | | | C. OK | | | 8. OK | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2007-06-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-06-06 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-06-06 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2007-06-06 14:47:55 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | *****FROM PREVIOUS REVIEW: | | | | | | | | | 1. SHT P-1 THE FOLLOWING INFORMATION IS | | | REQUIRED FOR THE GAS PERMIT: | | | | | | A. OK | | | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE FROM CONTRACTOR IS THAT THE EQUIPMENT IS | | | USED AND WILL BE MOVED FROM AN EXISTING CATERING | | | SERVICE. ALL REQUIRED LABELING SHALL BE ON EQUIPMENT | | | AND VERIFIED AT TIME OF FINAL INSPECTION, (SEE THE | | | FOLLOWING CODE SECTION) | | | 301.5 LABEL INFORMATION. | | | A PERMANENT FACTORY-APPLIED NAMEPLATE(S) SHALL BE | | | AFFIXED TO APPLIANCES ON WHICH SHALL APPEAR IN LEGIBLE | | | LETTERING, THE MANUFACTURER?S NAME OR TRADEMARK, THE | | | MODEL NUMBER, SERIAL NUMBER AND, FOR LISTED APPLIANCES, | | | THE SEAL OR MARK OF THE TESTING AGENCY. A LABEL SHALL | | | ALSO INCLUDE THE HOURLY RATING IN BRITISH THERMAL UNITS | | | PER HOUR (BTU/H) (W); THE TYPE OF FUEL APPROVED FOR USE | | | WITH THE APPLIANCE; AND THE MINIMUM CLEARANCE | | | REQUIREMENTS. | | | | | | | | | C. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. TO BE SHOWN | | | ON THE GAS ISOMETRIC RISER DIAGRAM. | | | ****RESPONSE NOTED, BUT THERE IS NO MANUAL SHUT OFF | | | VALVE UPSTREAM OF THE AUTOMATIC SHUT OFF VALVE AS | | | REQUIRED. | | | ********NOW MANUAL VALVE IS LOCATED DOWNSTREAM OF THE | | | AUTOMATIC SHUT OFF VALVE. PLEASE SHOW THE MANUAL VALVE | | | UPSTREAM OF THE AUTOMATIC VALVE. | | | | | | 8. OK | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2006-12-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-12-07 |
Time |
06:44 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-12-07 |
Time |
06:44 |
Sent To |
|
|
| Notes |
| 2006-12-07 06:46:00 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | *****FROM PREVIOUS REVIEW: | | | | | | | | | 1. SHT P-1 THE FOLLOWING INFORMATION IS | | | REQUIRED FOR THE GAS PERMIT: | | | | | | A. OK | | | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE FROM CONTRACTOR IS THAT THE EQUIPMENT IS | | | USED AND WILL BE MOVED FROM AN EXISTING CATERING | | | SERVICE. ALL REQUIRED LABELING SHALL BE ON EQUIPMENT | | | AND VERIFIED AT TIME OF FINAL INSPECTION, (SEE THE | | | FOLLOWING CODE SECTION) | | | 301.5 LABEL INFORMATION. | | | A PERMANENT FACTORY-APPLIED NAMEPLATE(S) SHALL BE | | | AFFIXED TO APPLIANCES ON WHICH SHALL APPEAR IN LEGIBLE | | | LETTERING, THE MANUFACTURER?S NAME OR TRADEMARK, THE | | | MODEL NUMBER, SERIAL NUMBER AND, FOR LISTED APPLIANCES, | | | THE SEAL OR MARK OF THE TESTING AGENCY. A LABEL SHALL | | | ALSO INCLUDE THE HOURLY RATING IN BRITISH THERMAL UNITS | | | PER HOUR (BTU/H) (W); THE TYPE OF FUEL APPROVED FOR USE | | | WITH THE APPLIANCE; AND THE MINIMUM CLEARANCE | | | REQUIREMENTS. | | | | | | | | | C. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. TO BE SHOWN | | | ON THE GAS ISOMETRIC RISER DIAGRAM. | | | ****RESPONSE NOTED, BUT THERE IS NO MANUAL SHUT OFF | | | VALVE UPSTREAM OF THE AUTOMATIC SHUT OFF VALVE AS | | | REQUIRED. | | | | | | 8. OK | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2006-09-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-09-09 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-09-09 |
Time |
09:54 |
Sent To |
|
|
| Notes |
| 2006-09-09 00:00:00 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | 1. SHT P-1 THE FOLLOWING INFORMATION IS | | | REQUIRED FOR THE GAS PERMIT: | | | | | | A. TYPE OF GAS, (LP OR NATURAL) NOTE ON | | | P-1 STATES LP OR NATURAL GAS. PLEASE | | | CLARIFY. | | | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | C. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. TO BE SHOWN | | | ON THE GAS ISOMETRIC RISER DIAGRAM. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2008-04-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-04 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-04 |
Time |
10:53 |
Sent To |
M |
|
| Notes |
| 2008-04-04 10:53:47 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-09-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-13 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-13 |
Time |
09:57 |
Sent To |
|
|
| Notes |
| 2007-10-02 14:26:49 | TO "COMM" BD#9 | | 2007-09-13 09:57:25 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-06-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-07-13 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-06-29 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2007-07-17 14:39:11 | TO "COMM" BD#7 | | 2007-06-29 14:25:52 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-04-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-23 |
Time |
08:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-23 |
Time |
08:22 |
Sent To |
|
|
| Notes |
| 2007-04-23 08:22:32 | TO "COMM" BD#59 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-10-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-12 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-12 |
Time |
18:00 |
Sent To |
|
|
| Notes |
| 2006-10-25 10:54:34 | TO "COMM" BD#4 | | 2006-10-22 10:59:46 | THIS WILL BE A COMM BOARD PROJECT.. WAITING FOR COMM | | | BAORD. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-10-02 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-08-22 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2006-09-07 00:00:00 | TO "BOB"#1 | | 2006-08-22 00:00:00 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2008-04-23 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-04-23 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-04-17 |
Time |
15:31 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-05-04 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-05-04 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-05-04 |
Time |
15:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-11-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-11-01 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-11-01 |
Time |
08:38 |
Sent To |
|
|
| Notes |
| 2006-11-01 09:39:37 | DENIED: | | | PLEASE PROVIDE A SURVEY OF THE PROPERTY. | | | | | | 1.THE 8" EXHAUST, DRYWELL & GAS METER ARE ALL LOCATED | | | ON THE SOUTH WALL WHICH APPEARS TO BE A ZERO LOT LINE. | | | | | | PROVISO: | | | 1.DETAIL OF THE ROOF MOUNTED | | | CONDENSING UNIT SHOWN ON PLAN SHEET M-2 | | | DOES NOT INDICATE CLEARANCE BETWEEN THE | | | ROOF AND STAND AS REQUIRED PER 2004 FBC | | | TABLE 1509.7 | | | | | | 2.MAKEUP AIR FOR THE KITCHEN SHALL | | | COMPLY WITH 2004 FMC 508.1. | | | | | | 3.ADDITIONAL PERMITS REQUIRED FOR THE | | | HOOD, FIRE SUPPRESSION AND WALK-IN | | | COOLERS.PLEASE PROVIDE PLANS AND | | | MANUFACTURER'S SUBMITTAL DATA.PLEASE | | | INDICATE THE FOLLOWING INFORMATION WITH | | | REGARDS TO THE HOOD: | | | A) TERMINATION OF EXHAUST. PROVIDE | | | DISTANCE TO PROPERTY LINES, PARAPITS, | | | ADJOING BUILDINGS, INTAKE OPENINGS, | | | ETC. | | | B) PROVIDE EQUIPMENT SCHEDULE FOR THE | | | EXHAUST FAN. | | | C) PROVIDE DUCT SIZE, LAYOUT, & MATERIAL | | | D) VELOCITY THROUGH DUCT SHALL BE A | | | MINIMUM OF 1,500 FPM BUT NOT GREATER | | | THAN 2,500 FPM. | | | E) INDICATE CLEARANCES TO COMBUSTIBLES. | | | D) PROVIDE DETAIL FOR THE HANGING & | | | VIBRATION ISOLATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719 OR | | | E-MAIL [email protected]. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-10-02 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-10-02 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2006-10-02 00:00:00 | PROVISO: | | | 1.DETAIL OF THE ROOF MOUNTED | | | CONDENSING UNIT SHOWN ON PLAN SHEET M-2 | | | DOES NOT INDICATE CLEARANCE BETWEEN THE | | | ROOF AND STAND AS REQUIRED PER 2004 FBC | | | TABLE 1509.7 | | | | | | 2.MAKEUP AIR FOR THE KITCHEN SHALL | | | COMPLY WITH 2004 FMC 508.1. | | | | | | 3.ADDITIONAL PERMITS REQUIRED FOR THE | | | HOOD, FIRE SUPPRESSION AND WALK-IN | | | COOLERS.PLEASE PROVIDE PLANS AND | | | MANUFACTURER'S SUBMITTAL DATA.PLEASE | | | INDICATE THE FOLLOWING INFORMATION WITH | | | REGARDS TO THE HOOD: | | | A) TERMINATION OF EXHAUST. PROVIDE | | | DISTANCE TO PROPERTY LINES, PARAPITS, | | | ADJOING BUILDINGS, INTAKE OPENINGS, | | | ETC. | | | B) PROVIDE EQUIPMENT SCHEDULE FOR THE | | | EXHAUST FAN. | | | C) PROVIDE DUCT SIZE, LAYOUT, & MATERIAL | | | D) VELOCITY THROUGH DUCT SHALL BE A | | | MINIMUM OF 1,500 FPM BUT NOT GREATER | | | THAN 2,500 FPM. | | | E) INDICATE CLEARANCES TO COMBUSTIBLES. | | | D) PROVIDE DETAIL FOR THE HANGING & | | | VIBRATION ISOLATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719 OR | | | E-MAIL [email protected]. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2007-10-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-10-30 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-10-29 |
Time |
17:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2007-08-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-08-17 |
Time |
07:51 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-08-10 |
Time |
18:19 |
Sent To |
|
|
| Notes |
| 2007-08-17 07:56:47 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****FROM PREVIOUS REVIEW: | | | ******FROM PREVIOUS REVIEWS: | | | | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | 4. OK | | | 5. OK | | | | | | 6. THE TWO PAGE "WORKSHEET" FROM DBPR | | | PLAN REVIEW SHALL BE ATTACHED TO EACH | | | SET OF PLANS. SECTION 106.1.3. | | | ****NOT ADDRESSED, AND NOW THE DBPR STAMPED SHEETS ARE | | | NOT IN THE NEW SETS OF PLANS AS REQUIRED. PLEASE HAVE | | | STAMPED SHEETS FROM DBPR IN EACH SET OF PLANS ALONG | | | WITH THE TWO PAGE "WORKSHEETS". | | | ********COMMENT NOT ADDRESSED. PLEASE SUBMIT A MINIMUM | | | OF TWO SETS OF PLANS FOR REVIEW WILL ALL REQUIRED | | | SHEETS. | | | ******RESPONSE NOTED, THE DBPR SHEETS SHALL BE | | | RESEALED, SIGNED & DATED BY THE ARCHITECT OF RECORD AND | | | INSERTED IN THE PLANS WITH THE NOTE THAT THE SHEET IS | | | FOR DBPR REVIEW STAMP ONLY. | | | | | | 7. SHT P-1 THE FOLLOWING INFORMATION IS | | | REQUIRED FOR THE GAS PERMIT: | | | | | | A. OK | | | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE FROM CONTRACTOR IS THAT THE EQUIPMENT IS | | | USED AND WILL BE MOVED FROM AN EXISTING CATERING | | | SERVICE. ALL REQUIRED LABELING SHALL BE ON EQUIPMENT | | | AND VERIFIED AT TIME OF FINAL INSPECTION, (SEE THE | | | FOLLOWING CODE SECTION). THIS IS OK PROVIDING: | | | 301.5 LABEL INFORMATION. | | | A PERMANENT FACTORY-APPLIED NAMEPLATE(S) SHALL BE | | | AFFIXED TO APPLIANCES ON WHICH SHALL APPEAR IN LEGIBLE | | | LETTERING, THE MANUFACTURER?S NAME OR TRADEMARK, THE | | | MODEL NUMBER, SERIAL NUMBER AND, FOR LISTED APPLIANCES, | | | THE SEAL OR MARK OF THE TESTING AGENCY. A LABEL SHALL | | | ALSO INCLUDE THE HOURLY RATING IN BRITISH THERMAL UNITS | | | PER HOUR (BTU/H) (W); THE TYPE OF FUEL APPROVED FOR USE | | | WITH THE APPLIANCE; AND THE MINIMUM CLEARANCE | | | REQUIREMENTS. | | | | | | | | | C. OK | | | 8. OK | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2007-06-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-06-06 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-06-06 |
Time |
14:41 |
Sent To |
|
|
| Notes |
| 2007-06-06 14:47:01 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | 4. OK | | | 5. OK | | | | | | 6. THE TWO PAGE "WORKSHEET" FROM DBPR | | | PLAN REVIEW SHALL BE ATTACHED TO EACH | | | SET OF PLANS. SECTION 106.1.3. | | | ****NOT ADDRESSED, AND NOW THE DBPR STAMPED SHEETS ARE | | | NOT IN THE NEW SETS OF PLANS AS REQUIRED. PLEASE HAVE | | | STAMPED SHEETS FROM DBPR IN EACH SET OF PLANS ALONG | | | WITH THE TWO PAGE "WORKSHEETS". | | | ********COMMENT NOT ADDRESSED. PLEASE SUBMIT A MINIMUM | | | OF TWO SETS OF PLANS FOR REVIEW WILL ALL REQUIRED | | | SHEETS. | | | | | | 7. SHT P-1 THE FOLLOWING INFORMATION IS | | | REQUIRED FOR THE GAS PERMIT: | | | | | | A. OK | | | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE FROM CONTRACTOR IS THAT THE EQUIPMENT IS | | | USED AND WILL BE MOVED FROM AN EXISTING CATERING | | | SERVICE. ALL REQUIRED LABELING SHALL BE ON EQUIPMENT | | | AND VERIFIED AT TIME OF FINAL INSPECTION, (SEE THE | | | FOLLOWING CODE SECTION) | | | 301.5 LABEL INFORMATION. | | | A PERMANENT FACTORY-APPLIED NAMEPLATE(S) SHALL BE | | | AFFIXED TO APPLIANCES ON WHICH SHALL APPEAR IN LEGIBLE | | | LETTERING, THE MANUFACTURER?S NAME OR TRADEMARK, THE | | | MODEL NUMBER, SERIAL NUMBER AND, FOR LISTED APPLIANCES, | | | THE SEAL OR MARK OF THE TESTING AGENCY. A LABEL SHALL | | | ALSO INCLUDE THE HOURLY RATING IN BRITISH THERMAL UNITS | | | PER HOUR (BTU/H) (W); THE TYPE OF FUEL APPROVED FOR USE | | | WITH THE APPLIANCE; AND THE MINIMUM CLEARANCE | | | REQUIREMENTS. | | | | | | | | | C. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. TO BE SHOWN | | | ON THE GAS ISOMETRIC RISER DIAGRAM. | | | ****RESPONSE NOTED, BUT THERE IS NO MANUAL SHUT OFF | | | VALVE UPSTREAM OF THE AUTOMATIC SHUT OFF VALVE AS | | | REQUIRED. | | | ********NOW MANUAL VALVE IS LOCATED DOWNSTREAM OF THE | | | AUTOMATIC SHUT OFF VALVE. PLEASE SHOW THE MANUAL VALVE | | | UPSTREAM OF THE AUTOMATIC VALVE. | | | | | | 8. OK | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-12-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-12-07 |
Time |
06:23 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-12-06 |
Time |
18:58 |
Sent To |
|
|
| Notes |
| 2006-12-07 06:36:13 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | | | | 1. PER TABLES 1004.1.2 AND 403.1 2-W/C'S | | | AND SEPARATE FACILITIES ARE REQUIRED. - | | | ALSO A DRINKING FOUNTAIN IS REQUIRED. | | | ****RESPONSE NOTED, BUT NO DRINKING FOUNTAIN PROVIDED. | | | | | | 2. ALL ARCHITECTURAL SHEETS. PER FAC 61G1-16.004(2) A | | | BUSINESS NUMBER IS REQUIRED. FS 481.219. ****RESPONSE | | | NOTED, BUT THE GENERAL NOTES REFER TO RJS ARCHITECTS | | | INC. IN NOTES 1, (TWICE), 4, & 8. ALL REFERENCES TO RJS | | | ARCHITECTS INC. SHALL BE DELETED FROM PLANS OR A | | | BUSINESS NUMBER WILL BE REQUIRED. | | | | | | 3. OK | | | 4. OK | | | 5. OK | | | | | | 6. THE TWO PAGE "WORKSHEET" FROM DBPR | | | PLAN REVIEW SHALL BE ATTACHED TO EACH | | | SET OF PLANS. SECTION 106.1.3. | | | ****NOT ADDRESSED, AND NOT THE DBPR STAMPED SHEETS ARE | | | NOT IN THE NEW SETS OF PLANS AS REQUIRED. PLEASE HAVE | | | STAMPED SHEETS FROM DBPR IN EACH SET OF PLANS ALONG | | | WITH THE TWO PAGE "WORKSHEETS". | | | | | | 7. SHT P-1 THE FOLLOWING INFORMATION IS | | | REQUIRED FOR THE GAS PERMIT: | | | | | | A. OK | | | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE FROM CONTRACTOR IS THAT THE EQUIPMENT IS | | | USED AND WILL BE MOVED FROM AN EXISTING CATERING | | | SERVICE. ALL REQUIRED LABELING SHALL BE ON EQUIPMENT | | | AND VERIFIED AT TIME OF FINAL INSPECTION, (SEE THE | | | FOLLOWING CODE SECTION) | | | 301.5 LABEL INFORMATION. | | | A PERMANENT FACTORY-APPLIED NAMEPLATE(S) SHALL BE | | | AFFIXED TO APPLIANCES ON WHICH SHALL APPEAR IN LEGIBLE | | | LETTERING, THE MANUFACTURER?S NAME OR TRADEMARK, THE | | | MODEL NUMBER, SERIAL NUMBER AND, FOR LISTED APPLIANCES, | | | THE SEAL OR MARK OF THE TESTING AGENCY. A LABEL SHALL | | | ALSO INCLUDE THE HOURLY RATING IN BRITISH THERMAL UNITS | | | PER HOUR (BTU/H) (W); THE TYPE OF FUEL APPROVED FOR USE | | | WITH THE APPLIANCE; AND THE MINIMUM CLEARANCE | | | REQUIREMENTS. | | | | | | | | | C. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. TO BE SHOWN | | | ON THE GAS ISOMETRIC RISER DIAGRAM. | | | ****RESPONSE NOTED, BUT THERE IS NO MANUAL SHUT OFF | | | VALVE UPSTREAM OF THE AUTOMATIC SHUT OFF VALVE AS | | | REQUIRED. | | | | | | 8. OK | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-09-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-09-07 |
Time |
12:57 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-09-07 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2006-09-07 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 BUILDING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | | | | 1. PER TABLES 1004.1.2 AND 403.1 2-W/C'S | | | AND SEPARATE FACILITIES ARE REQUIRED. - | | | ALSO A DRINKING FOUNTATIN IS REQUIRED. | | | | | | 2. ALL ARCHITECTURAL SHEETS. PER FAC 61G1-16.004(2) A | | | BUSINESS NUMBER IS | | | REQUIRED. FS 481.219. | | | | | | 3. ALL ARCHITECTURAL SHEETS. ONE CAN NOT | | | GLEAN THE REQUIRED INFORMATION FROM THE | | | SEAL AS STATED IN 61G1-16.002(1). PLEASE | | | RESEAL SO REQUIRED INFORMATION CAN BE | | | READ. FS 481.2055. | | | | | | 4. THE GREASE INTERCEPTOR SHALL BE SIZED | | | BY LYNN MASSON, ENVIRONMENTAL COMPLIANCE | | | MANAGER. PLEASE CONTACT LYNN AT (561) | | | 822-2271, OR (561) 822-2279 (FAX) OR | | | E-MAIL AT [email protected]. | | | | | | 5. SHTS A125.1 AND A130.1. A125.1 SHOWS | | | 1 TOILET ROOM WHEREAS SHT A130.1 SHOWS | | | TWO TOILET ROOMS. PLEASE CLARIFY. | | | SECTION 106.1.1. | | | | | | 6. THE TWO PAGE "WORKSHEET" FROM DBPR | | | PLAN REVIEW SHALL BE ATTACHED TO EACH | | | SET OF PLANS. SECTION 106.1.3. | | | | | | 7. SHT P-1 THE FOLLOWING INFORMATION IS | | | REQUIRED FOR THE GAS PERMIT: | | | | | | A. TYPE OF GAS, (LP OR NATURAL) NOTE ON | | | P-1 STATES LP OR NATURAL GAS. PLEASE | | | CLARIFY. | | | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | C. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. TO BE SHOWN | | | ON THE GAS ISOMETRIC RISER DIAGRAM. | | | | | | 8. SHT P-3 GREASE INTERCEPTOR DETAIL. | | | SEE ATTACHED SHEET FOR STANDARD GREAS | | | INTERCEPTOR DETAIL. SEE MINIMUM | | | REQUIREMENTS FOR SIDE WALLS, BOTTOM, | | | ETC. NO FIBERGLASS INTERCEPTORS | | | APPROVED. INTERCEPTOR SHALL BE MADE OF | | | STEEL REINFORCED CONCRETE PER MUNICIPAL | | | CODE SECTION 90-124(7)(F). PLEASE SUBMIT | | | A MANUF. SPECIFICATION SHEET FOR GREASE INTERCEPTOR FOR | | | APPROVAL. INDICATE MODEL | | | NUMBER. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2007-08-06 |
|
|
Cont ID |
|
| Sent By |
kdfreema |
Date |
2007-08-06 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
kdfreema |
Date |
2007-08-06 |
Time |
16:02 |
Sent To |
|
|
| Notes |
|
|