Plan Review Details - Permit 06081713
Plan Review Stops For Permit 06081713
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2007-04-30 Cont ID  
Sent By lursu Date 2007-04-30 Time 08:30 Rev Time 0.00
Received By lursu Date 2007-04-30 Time 08:31 Sent To  
Notes
2007-04-30 08:33:48PERMIT WAS ATTACHED TO 6612 GEORGIA AVE .THE JOB
 LOCATION IS AT THE SOUTH SIDE OF THE PROPERTY , BASED
 ON PREVIOUS COMMENTS.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-09-25 Cont ID  
Sent By lursu Date 2006-09-25 Time 08:11 Rev Time 0.00
Received By lursu Date 2006-09-25 Time 08:11 Sent To  
Notes
2006-09-25 00:00:00FIELD VERIFICATION DONE BE FD ON SEPT 22
 , JOB LOCATION IS AT 6612 GEORGIA AVE,
 THE SOUTH SIDE BLDG ON THE PCN =
 74434408050002770

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-09-11 Cont ID  
Sent By lursu Date 2006-09-11 Time 15:53 Rev Time 0.00
Received By lursu Date 2006-09-11 Time 15:52 Sent To  
Notes
2006-09-11 00:00:002 PARCELS HAVE THE SAME ADDRESS AND SAME
 OWNER .PROJECT UNDER REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-09-25 Cont ID  
Sent By shill Date 2007-09-25 Time 09:24 Rev Time 0.00
Received By shill Date 2007-09-25 Time 09:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-07-25 Cont ID  
Sent By shill Date 2007-07-25 Time 17:34 Rev Time 0.00
Received By shill Date 2007-07-25 Time 17:34 Sent To  
Notes
2007-07-25 17:45:59****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)A SITE PLAN WAS PROVIDED IN RESPONSE TO CORRECTION
 #7, A REQUEST FOR A SURVEY TO DETERMINE COMPLIANCE WITH
 FBC TABLE 602.A SITE PLAN WAS PROVIDED, BUT IT SHOWS
 A SECTION OF THE BUILDING HATCHED WHICH ENCROACHES THE
 PROPERTY LINE.DOES THIS BUILDING ENCROACH THE
 PROPERTY LINE?NORTH ON THE SITE PLAN DOES NOT
 CORRELATE WITH THE NORTH ON THE FLOOR PLAN.IT APPEARS
 THAT NORTH ON THE FLOOR PLAN IS ACTUALLY WEST.IT
 APPEARS THAT THE WEST AND NORTH ELEVATIONS OF THE
 BUILDING ARE ON THE PROPERTY LINE, REQUIRING A 3 HOUR
 FIRE RATING FBC TABLE 602.NOTE THAT THE FEC EASEMENT
 IS NOT CONSIDERED OPEN SPACE.TYPE IIIB REQUIRES 2
 HOUR BEARING WALLS FBC TABLE 601.
  
 THE SITE PLAN IS NOT LEGIBLE.PROVIDE A COPY OF THE
 SURVEY AS REQUESTED WHICH WILL CLEARLY SHOW THE
 BUILDING FOOTPRINT IN RELATION TO THE PROPERTY LINE.
  
 2.)SEE ELECTRIC COMMENTS REGARDING THE ENERGY CALCS.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-05-08 Cont ID  
Sent By shill Date 2007-05-08 Time 08:43 Rev Time 0.00
Received By shill Date 2007-05-08 Time 08:43 Sent To  
Notes
2007-05-08 09:44:27****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM THE PREVIOUS LISTS, NUMBERING REMAINING THE SAME
 FOR CONSISTENCY:
  
 1.)ADDRESSED.
  
 2.)AS AGREED, THIS IS A CHANGE OF OCCUPANCY.PLEASE
 INCLUDE THIS INFORMATION (CHANGE OF OCCUPANCY) IN THE
 BUILDING CODE CHECKLIST AS THE CHANGE OF OCCUPANCY
 REQUIRES COMPLIANCE WITH ALL REQUIREMENTS OF FBC EB
 CHAPTER 8.SOME COMMENTS ARE DUE TO THE CHAPTER 8
 REQUIREMENTS.
 7.)PROVIDE A SURVEY FOR THIS PROPERTY
 TO DETERMINE COMPLIANCE WITH FBC TABLE
 602.
  
 8.)1ST REVIEW COMMENT - THE NORTH WALL APPEARS TO BE
 A
 TENANT SEPARATION WALL; WHAT OCCUPANCY CLASSIFICATION
 IS THAT SPACE?SHOW
 COMPLIANCE WITH FBC TABLE 302.3.2.
  
 2ND REVIEW COMMENT - THE PLAN WAS REVISED TO SHOW B
 OCCUPANCY.NO COMPLIANCE WITH FBC TABLE 302.3.2
 SHOWN.
  
 3RD REVIEW COMMENT - AS DISCUSSED, IF THIS IS A
 SEPARATED USE FBC302.3.2, A 3 HOUR OCCUPANCY SEPARATION
 IS REQUIRED BETWEEN B AND F1, FBC TABLE 302.3.2.IF
 THIS IS A NON SEPARATED USE FBC302.3.1, YOU MUST SHOW
 COMPLIANCE WITH THE MOST STRINGENT OCCUPANCY FBC TABLE
 503, FBC TABLE 601, FBC TABLE 602.IF ALLOWABLE AREA
 INCREASES ARE USED, SHOW ALL CALCULATIONS ON THE PLAN.
 CODE COMPLIANCE IS TO BE CLEAR AND IS TO BE
 INCORPORATED INTO THE PLAN (CANNOT BE ADDRESSED THROUGH
 A RESPONSE LETTER).
  
 WHEN SHOWING REQUIRED FIRE RESISTANCE, EITHER SPECIFY
 AN APPROVED LISTING OR CALCULATED FIRE RESISTANCE
 (LISTING ALL COMPONENTS AS WELL AS TIME ASSIGNED TO
 EACH COMPONENT), FBC CHAPTER 7.
  
 10.)PROVIDE OVERALL DIMENSIONS OF THE
 SPACE ON THE LIFE SAFETY SHEET A120.1. (NOT ADDRESSED.
 OVERALL DIMENSIONS ARE NOT SHOWN ON ANY OF THE FLOOR
 PLANS PROVIDED.)
  
 11.)SEE FBC306.2.FOOD PROCESSING IS
 FACTORY OCCUPANCY CLASSIFICATION.
 CLARIFY WHY YOU HAVE DECLARED BUSINESS
 OCCUPANCY FOR THE FOOD PROCESSING AREA.
 SEE FBC302.1, PORTIONS OF STRUCTURES ARE
 TO BE CLASSIFIEDWITH RESPECT TO
 OCCUPANCY.
  
 3RD REVIEW - NOT ADDRESSED.PER MY CONVERSATION WITH
 THE ARCHITECT, THE FOOD IS PREPARED AND SERVED HOT AT
 ANOTHER LOCATION.DESPITE THIS ADDITIONAL INFORMATION
 (THE FACT THAT THE FOOD LEAVES THE FACILITY HOT RATHER
 THAN COLD), I THINK THAT THE CORRECT OCCUPANCY
 CLASSIFICATION IS F1, FBC306.2.ARCHITECT IS TO EITHER
 REVISE THE OCCUPANCY CLASSIFICATION ON THE PLAN AND
 SHOW CODE COMPLIANCE OR SUBMIT JUSTIFICATION (IN
 WRITING, PRIOR TO THE NEXT RESUBMITTAL) FOR THE
 BUSINESS OCCUPANCY DECLARED TO BE REVIEWED BY ASSISTANT
 BUILDING OFFICIAL.AS DISCUSSED IN OUR TELEPHONE
 CONVERSATION, IT APPEARS THAT A NON SEPARATED USE
 FBC302.3.1 MAY BE AN OPTION.
  
 16.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC FBC13-103.1.
  
 3RD REVIEW - THE PREPARER AND OWNER AGENT ARE TO SIGN
 THE ENERGY CALCS.
  
 17.)THE SQUARE FOOT AREA ON THE ENERGY
 CALC DOES NOT MATCH THE PLAN.NO
 UNCONDITIONED AREA SHOWN ON THE ENERGY
 CALC, UNCONDITIONED AREA SHOWN ON PLAN.
  
 3RD REVIEW - PLEASE DECLARE TOTAL SF AREA FOR THE
 TENANT SPACE, BOTH CONDITIONED AND UNCONDITIONED.WHEN
 SCALED, THE AREA IS APPROXIMATELY 1568 SQUARE FEET.
 ENERGY CALCS STATE 1750 CONDITIONED, 1750
 CONDITIONED/UNCONDITIONED.OCCUPANT LOAD IS 30 AT
 100SF PER PERSON.CODE COMPLIANCE WITH OCCUPANT LOAD
 AND EGRESS REQUIREMENTS CANNOT BE DETEREMINED DUE TO
 INSUFFICIENT/INCOMPLETE/INCONSISTENT INFORMATION.
  
 THE ENERGY CALCS DID NOT PASS ELECTRIC REVIEW.NOTE
 THAT ENERGY CALCS ARE REQUIRED; CORRECT, CODE COMPLIANT
 ENERGY CALCS ARE REQUIRED FOR PERMIT ISSUANCE.
 STATUTORY REQUIREMENTS CAN NEVER BE WAIVED OR
 PROVISO'D.
  
 18.)INTERIOR FINISHES TO COMPLY WITH TABLE 803.5.
  
 3RD REVIEW - THIS WAS ADDRESSED ON SHEET A130. HOWEVER,
 THE ARCHITECT HAS DECLARED BUSINESS OCCUPANCY BUT THE
 INTERIOR FINISHES REQUIREMENTS DO NOT COMPLY WITH TABLE
 803.5 FOR BUSINESS OCCUPANCY, BUT ARE COMPLIANT FOR
 F1.
  
 19.)SEE ATTACHED FS 553.80(2)(B).
  
 3RD REVIEW - DUE TO SEVERAL OF THE ABOVE COMMENTS, A 4X
 PLAN REVIEW FEE HAS BEEN ASSESSED AS REQUIRED BY
 FLORIDA STATUTE.A BILL IS ATTACHED AND MUST BE PAID
 WHEN RESUBMITTING.
  
 18.)PROVIDE INFORMATION IN REGARDS TO ACCESSIBLE
 PARKING, ACCESSIBLE ROUTE.SEE FBC11-4.1.4.6(2).
  
 3RD REVIEW - SEE ATTACHED DETAIL WHICH IS THE CITY OF
 WEST PALM BEACH STANDARD PARKING DETAIL AND REVISE
 A110.1.ALSO SHOW THE ACCESSIBLE ROUTE; FROM THE
 PUBLIC WAY, AND FROM THE ACCESSIBLE PARKING.THIS CAN
 BE DONE ON THE SITE PLAN.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-14 Cont ID  
Sent By shill Date 2006-11-14 Time 13:04 Rev Time 0.00
Received By shill Date 2006-11-14 Time 13:04 Sent To  
Notes
2006-11-14 13:15:55****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM THE PREVIOUS LIST, COMMENTS NOT ADDRESSED
  
 1.)DECLARE LEVEL OF ALTERATION FBC EB3
 AND INCLUDE FBC EB AS GOVERNING CODE.
 SEE FBC EB CHAPTER 3 TO DETERMINE LEVEL
 OF ALTERATION.
  
 THE ARCHITECT DECLARED A LEVEL 3 AND FBC EB3.THE
 CORRECT CODE REFERENCE IS FBC 2004 EXISTING BUILDING.
 LEVEL 3 IS FOR OVER 50% IMPROVEMENT.THE PLAN SHOWS
 THAT LESS THAN 30% OF THE BUILDING IS BEING IMPROVED.
 IF THIS IS A LEVEL 3, PLEASE SHOW COMPLIANCE WITH ALL
 REQUIREMENTS.IF IT IS NOT,PLEASE REVISE THE NOTE.
 ALSO THIS IS A CHANGE OF OCCUPANCY; DESIGNER IS TO
 REVIEW REQUIREMENTS IN CHAPTER 8 FBC EB AND SHOW
 COMPLIANCE WITH ALL REQUIREMENTS.
  
 2.)THIS APPEARS TO BE A CHANGE OF
 OCCUPANCY BASED ON OCCUPATIONAL LICENSE
 ISSUED AND ON RECORD, SEE WWW.WPB.ORG
 (ONE STOP SHOP, OCCUPATIONAL LICENSES).
 THE PREVIOUS OCCUPANCY CLASSIFICATION
 APPEARS TO BE MERCANTILE.SEE FBC306.
  
 7.)PROVIDE A SURVEY FOR THIS PROPERTY
 TO DETERMINE COMPLIANCE WITH FBC TABLE
 602.
  
 8.)THE NORTH WALL APPEARS TO BE A
 TENANT SEPARATION WALL; WHAT OCCUPANCY CLASSIFICATION
 IS THAT SPACE?SHOW
 COMPLIANCE WITH FBC TABLE 302.3.2.
  
 THE PLAN WAS REVISED TO SHOW B OCCUPANCY.NO
 COMPLIANCE WITH FBC TABLE 302.3.2 SHOWN.
  
 10.)PROVIDE OVERALL DIMENSIONS OF THE
 SPACE ON THE LIFE SAFETY SHEET A120.1.
  
 11.)SEE FBC306.2.FOOD PROCESSING IS
 FACTORY OCCUPANCY CLASSIFICATION.
 CLARIFY WHY YOU HAVE DECLARED BUSINESS
 OCCUPANCY FOR THE FOOD PROCESSING AREA.
 SEE FBC302.1, PORTIONS OF STRUCTURES ARE
 TO BE CLASSIFIEDWITH RESPECT TO
 OCCUPANCY.
  
 16.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC FBC13-103.1.
  
 17.)THE SQUARE FOOT AREA ON THE ENERGY
 CALC DOES NOT MATCH THE PLAN.NO
 UNCONDITIONED AREA SHOWN ON THE ENERGY
 CALC, UNCONDITIONED AREA SHOWN ON PLAN.
  
 NEW COMMENT:
  
 18.)INTERIOR FINISHES TO COMPLY WITH TABLE 803.5.
  
 19.)SEE ATTACHED FS 553.80(2)(B).
  
 18.)PROVIDE INFORMATION IN REGARDS TO ACCESSIBLE
 PARKING, ACCESSIBLE ROUTE.SEE FBC11-4.1.4.6(2).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-18 Cont ID  
Sent By shill Date 2006-09-18 Time 09:58 Rev Time 0.00
Received By shill Date 2006-09-18 Time 09:57 Sent To  
Notes
2006-09-18 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)DECLARE LEVEL OF ALTERATION FBC EB3
 AND INCLUDE FBC EB AS GOVERNING CODE.
 SEE FBC EB CHAPTER 3 TO DETERMINE LEVEL
 OF ALTERATION.
  
 2.)THIS APPEARS TO BE A CHANGE OF
 OCCUPANCY BASED ON OCCUPATIONAL LICENSE
 ISSUED AND ON RECORD, SEE WWW.WPB.ORG
 (ONE STOP SHOP, OCCUPATIONAL LICENSES).
 THE PREVIOUS OCCUPANCY CLASSIFICATION
 APPEARS TO BE MERCANTILE.SEE FBC306.
  
 3.)THE COMPANY RJS ARCHITECTS, INC. IS
 REQUIRED TO HAVE AN ARCHITECT BUSINESS
 LICENSE.I WAS UNABLE TO LOCATE THIS ON
 WWW.MYFLORIDALICENSE.COM.PLEASE
 PROVIDE THE LICENSE NUMBER ON THE PLAN
 FAC61G1-16.003,004.
  
 4.)SEE COMMENTS FROM ADDRESSING AND
 ELECTRIC REGARDING THE BUILDING ADDRESS
 ON THE PLAN.PLEASE RESOLVE AND REVISE
 PLAN IF NECESSARY.
  
 5.)A120.1 IS USED TWICE, BOTH MARKED
 LIFE SAFETY PLAN, BUT ONE IS A DEMO
 PLAN.
  
 6.)BUILDING CODE CHECKLIST, PROVIDE
 THE TOTAL BUILDING AREA, BUILDING
 HEIGHT, OTHER TENANT SPACES AND
 OCCUPANCY TO DETERMINE COMPLIANCE WITH
 FBC TABLE 503.
  
 7.)PROVIDE A SURVEY FOR THIS PROPERTY
 TO DETERMINE COMPLIANCE WITH FBC TABLE
 602.
  
 8.)THE NORTH WALL APPEARS TO BE A
 TENANT SEPARATION WALL; WHAT OCCUPANCY
 CLASSIFICATION IS THAT SPACE?SHOW
 COMPLIANCE WITH FBC TABLE 302.3.2.
  
 9.)A120.1 SHOWS 1 AND 2 HOUR
 PENETRATION DETAILS; WHERE WILL THIS BE
 INSTALLED?NO FIRE RATED WALLS ARE
 SHOWN ON THE PLAN.SHOW ALL REQUIRED
 FIRE SEPARATIONS REQUIRED ON THE PLAN.
  
 10.)PROVIDE OVERALL DIMENSIONS OF THE
 SPACE ON THE LIFE SAFETY SHEET A120.1.
  
 11.)SEE FBC306.2.FOOD PROCESSING IS
 FACTORY OCCUPANCY CLASSIFICATION.
 CLARIFY WHY YOU HAVE DECLARED BUSINESS
 OCCUPANCY FOR THE FOOD PROCESSING AREA.
 SEE FBC302.1, PORTIONS OF STRUCTURES ARE
 TO BE CLASSIFIEDWITH RESPECT TO
 OCCUPANCY.
  
 12.)SEE FBC302.1, FBC302.2.ADDRESS
 THE MIXED USE OF THE OFFICE AREAS
 (BUSINESS) AND THE PROCESSING AREA
 (FACTORY).SHOW COMPLIANCE WITH
 FBC302.2 OR SHOW REQUIRED FIRE
 SEPARATION.
  
 13.)LIFE SAFETY NOTE #5 REFERS TO
 DINING AND SEATING AREAS.NONE SHOWN ON
 THE PLAN AND THIS CONFLICTS WITH THE
 NOTE ON THE COVER SHEET WHICH STATES
 THAT ALL FOOD WILL BE CONSUMED OFF
 PREMISES.PLEASE CLARIFY.
  
 14.)NOTE 1 HAS REFERENCES TO A, E, I,
 R OCCUPANCIES.PLEASE REMOVE AS THEY
 ARE NOT PERTINENT TO THIS JOB AND DO NOT
 APPEAR TO BE FBC2004 NOTES.
  
 15.)RESTROOM DOOR 3 BLOCKS OVER HALF
 THE REQUIRED EGRESS WIDTH, SEE
 FBC1005.2.
  
 16.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC FBC13-103.1.
  
 17.)THE SQUARE FOOT AREA ON THE ENERGY
 CALC DOES NOT MATCH THE PLAN.NO
 UNCONDITIONED AREA SHOWN ON THE ENERGY
 CALC, UNCONDITIONED AREA SHOWN ON PLAN.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-10-04 Cont ID  
Sent By dpalmer Date 2007-10-04 Time 10:41 Rev Time 0.00
Received By dpalmer Date 2007-10-04 Time 10:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-07-13 Cont ID  
Sent By dpalmer Date 2007-07-13 Time 08:40 Rev Time 0.00
Received By dpalmer Date 2007-07-07 Time 14:33 Sent To I
Notes
2007-07-13 08:41:082007-07-13 08:41:08
  
 ** UNSAT 4TH REVIEW**
  
 1) NOTE:PLEASE SEE THE PREVIOUS COMMENTS REQUESTED
 THE ENERGY CALCULATIONS WHICH WERE SUBMITTED TO
 COORDINATE WITH THE ELECTRICAL PLANS. THERE WAS NO
 COMMENT THAT THE VERSION OF THE CALCULATIONS NEEDED TO
 CHANGE.
 PLEASE SEE THE ENERGY CALCULATIONS NOW SUBMITTED IS
 VERSION 3.0 WHICH WENT INTO EFFECT DECEMBER 8TH, 2006.
 PLEASE KNOW HOWEVER AS THIS PROJECT WAS SUBMITTED UNDER
 THE PREVIOUS CODE BEFORE THE CODE CHANGE OF DECEMBER
 8TH, 2006, THE CALCULATIONS NEED TO BE DONE UNDER THE
 PREVIOUS 2.11 AS SUBMITTED UNDER THE PREVIOUS REVIEW.
 PLEASE BE SURE TO TRANSFER ALL INFORMATION OVER TO THE
 CALCULATIONS.
 PLEASE SEE THE PREVIOUS CALCULATIONS SUBMITTED
 INDICATED 1750 SQ FT AND NOW THE NEW ONES INDICATE 2970
 SQ FT? PLEASE BE SURE THE CALCULATIONS COORDINATE WITH
 PLANS AND THE CORRECT VERSION.
 IF THERE ARE ANY QUESTIONS ON THIS PLEASE CALL.
  
  
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-07 14:54:062007-07-07 14:54:06
  
  
 CONTRACTOR CAME IN AND CORRECTED SETS FOR REVIEW ON
 7/11
2007-07-07 14:34:212007/07/07 14:34:21
 PLANS REMOVED FROM INCOMING. PLANS WILL BE RETURNED TO
 INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL REVIEW
 IS COMPLETED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-04-25 Cont ID  
Sent By dpalmer Date 2007-04-25 Time 13:32 Rev Time 0.00
Received By dpalmer Date 2007-04-25 Time 09:32 Sent To  
Notes
2007-04-25 13:33:06 
  
 ** UNSAT3RD REVIEW**
  
 1) NOTE: PLEASE SEE THEAIC RATINGS SHOW DIFFERENT
 LENGTHS ON PLANS FROM THE ACTUAL LENGTHS SHOWN ON
 SHEETS WHERE CONDUITS ARE RUN.
 PLEASE SEE THE LENGTH SHOWN AS 60FT IS ACTUALLY LONGER
 BY WHAT IS BEING SHOWN ON PLANS.
 THE AVAILABLE FAULT CURRENT WILL ACTUALLY BE LESS.
 110.9,
 FBC 106.1.2
  
 2) NOTE: PLEASE VERIFY VOLTAGE DROP FOR THESE SAME
 SERVICE CONDUCTORS AS THE LENGTH ON PLANS IS LONGER
 THAN FIGURES.
 13-413.
  
 3) NOTE: PLEASE SEE THE SAME ENERGY CALCULATIONS WERE
 SUBMITTED BACK AS SUBMITTED ON PREVIOUS SUBMITTAL.
 PLEASE SEE THE LIGHTING ON CALCULATIONS DO NOT
 CORRELATE WITH PLANS FOR TYPES OF FIXTURES, NUMBER OF
 FIXTURES AND WATTAGE. ONLY ONE FIXTURE IS NOTED ON
 CALCULATIONS.
 PLEASE ALSO SEE THAT THE ENERGY CALCULATIONS ALSO
 INDICATE MANUAL MEANS FOR CONTROL OF LIGHTING WHEN THE
 PLANS INDICATE AUTOMATED MEANS.
 PLEASE ADJUST.
 PLEASE ALSO SEE THE SHEETS WHICH ARE REQUIRED TO BE
 SIGNED DATED AND SEALED NEEDS TO BE THE SHEETS WHICH
 CONTAIN THE LICENSEE INFORMATION. (2ND SHEET IN).
 PLEASE SEE THE METHOD AS SHOWN ON PLANS IS *B*, YET
 ENERGY CALCULATIONS ARE *A*.?
 PLEASE COORDINATE.
 13-415.1.A, 13-415.1.B, 13-415.C, 13-415.2
 13-103.1.1.1
  
 4) NOTE: PLEASE CLARIFY HOW MANY MAINS ARE ON THE
 EXISTING SERVICE AND LABEL MAINS , 1OF ? , 2OF ? ETC.
 230.2
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-27 Cont ID  
Sent By dpalmer Date 2006-10-27 Time 16:25 Rev Time 0.00
Received By dpalmer Date 2006-10-27 Time 13:48 Sent To  
Notes
2006-10-27 16:25:55*** UNSAT2ND REVIEW******
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW AND
 SOME NEW COMMENTS DUE TO THE PLANS SUBMITTED.
 PLEASE SEE NOTES BELOW WHICH ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW.
  
 1) NOTE: OK, HOWEVER PLEASE BE SURE TO CORRECT PERMIT
 APPLICATION AS ADDRESS STILLS SHOWS 6600.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PERMIT APPLICATION
 DOES NOT MATCH WITH THE LEGAL OWNER OF
 RECORD ON OUR SYSTEM, THE PALM BEACH
 COUNTY PROPERTY APPRAISER'S WEBSITE OR
 THE NOTICE OF COMMENCEMENT SUBMITTED.
 PLEASE CORRECT AND REVISE.
  
  
 2) NOTE: OK. NOTE #1
  
 3) NOTE: OK.
  
 4) NOTE:NO, PLEASE SEE AS SHOWN ON PLANS , THIS IS
 "NOT" CLASSIFIED AS SEPARATE BUILDING BY RATING THE
 WALL 4HRS. PLEASE SEE DEFINITION OF "FIRE WALL " IN THE
 FBC.
 ONE SERVICE OR COMING FROM THE EXISTING SERVICE OR
 MEETING AN EXCEPTION. PLEASE KNOW, AS SHOWN IN ORDER
 FOR THIS OFFICE TO GRANT SPECIAL PERMISSION, PLEASE
 CALL TO GO OVER. PLEASE KNOW A PHONE MEETING WITH THE
 ENGINEER OF RECORD WOULD BE RECOMMEND AND POSSIBLY THE
 ARCHITECT TO RESOLVE THIS MATTER MAY BE NEEDED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THIS IS A TENANT
 SPACE PART OF A LARGER BUILDING AND THE
 NEW SERVICE AS SHOWN IS NOT GRANTED OR
 PERMITTED. 230.2
 ** PLEASE SEE AERIAL MAP PROVIDED.
 PLEASE SEE SERVICE LOCATION FOR THE
 EXISTING SERVICE IS TO BE SHOWN.
 PLEASE SEE SERVICE AS SHOWN IS BEING
 SHOWN AS AN OVERHEAD SERVICE LOCATED ON
 THE SOUTH SIDE OF BUILDING WHERE THE
 BUILDING FROM THE ADJOINING PROPERTY IS
 LOCATED. CLEARANCES AS REQUIRED UNDER
 THE FPL SERVICE GUIDELINES AND NEC ARE
 NOTMET IN EITHER CASE.
 PLEASE KNOW, THE EXISTING SERVICE FOR
 THE BUILDING MUST BE USED OR UPGRADED.
 PLEASE SEE THE 1HR SEPARATION DOES NOT
 MAKE THIS SPACE A SEPARATE BUILDING.
 PLEASE SEE FBC DEFINITIONS OF BUILDING,
 AND REQUIRED "FIRE WALL" IN ORDER TO
 BECOME A SEPARATE BUILDING. PLEASE SEE
 REQUIRED "FIRE WALL" WOULD BE A FOUR HR
 RATED WALL WHICH WOULD PERMIT THE
 COLLAPSE THE ADJOINING STRUCTURE WITHOUT
 AFFECT THE STRUCTURAL INTEGRITY OF THE
 ADJOINING REMAINING BUILDING.
  
 5) NOTE: OK.
  
 6) NOTE:NO, PLEASE SEE MEANS OF EGRESS INTO ANY ONE
 AREA/ KITCHEN ETC WILL REQUIRE A MEANS FOR OVER RIDING
 THE TIME OF DAY SCHEDULING.PLEASE SEE REDLINED AREAS
 ON PLANS. PLEASE ALSO SEE THAT THE OVER RIDES SWITCH IF
 TIMER TYPE IS TO BE SHOWN WITH A MAX OF 4HRS OR IF AN
 OCC SENSOR TYPE 30MINS MAX).
 PLEASE SEE ENERGY CALCULATIONS ARE NOT SIGNED, DATED
 AND SEALED ON THE CORRECT SHEET.
  
 ** PREVIOUS REVIEW NOTE **
 IF TRYING TO OBTAIN COMPLIANCE
 WITH THE 2004 FBC CHAPTER 13,THE
 LIGHTING CONTROLS AS NOTED ARE NOT
 COMPLETE AT THIS TIME.PLEASE SHOW THE
 DETAIL FOR "SYSTEM" BEING PROPOSED.
 PLEASE ALSO INCLUDE EXISTING OFFICE
 AREAS ARE REQUIRED TO BE CONTROLLED BY
 THIS SYSTEM.
 PLEASE PROVIDE SCHEDULING, OVER RIDE
 DEVICES ALONG WITH MAX PERMITTED TIMES
 ON OVER RIDE DEVICES.
 (4HRS MAX FOR TIMER TYPES, 30MIN MAX ON
 OCCUPANT SENSOR TYPES).
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND
 .1.3.
  
 7) NOTE: ??
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE COMMENTS BASED ON
 THE PROPOSED ELECTRICAL RISER ARE MUTE
 AT THIS TIME AS SERVICE SHOWN IS NOT
 PERMITTED. PLEASE HOWEVER SEE SOME ITEMS
 BELOW AS ANY SERVICE UPGRADE WILL
 REQUIRE SOME OF THE SAME ITEMS.
 PLEASE SEE THE FOLLOWING.
 MISSING GAS BOND ON THE GROUNDING
 ELECTRODE SYSTEM, MISSING THE THE
 EQUIPMENT GROUNDING CONDUCTOR FROM MAIN
 TO SUB PANELS. PLEASE SEE WHAT APPEARS
 TO BE A MISPRINT AS 1/4" FOR EQUIPMENT
 GROUND.
 PLEASE SEE MISSING AIC RATING FOR
 MAIN.(SHOWN FOR NEW SUB PANELS).
  
  
 8) NOTE: OK, NO PANEL "E" SHOWN .
  
 9) NOTE:OK.
  
  
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT THE
 ELECTRICAL DESIGN/PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-10 Cont ID  
Sent By dpalmer Date 2006-09-10 Time 09:44 Rev Time 0.00
Received By dpalmer Date 2006-09-10 Time 08:29 Sent To  
Notes
2006-09-10 00:00:00*** UNSAT******
  
 1) NOTE: PLEASE SEE PERMIT APPLICATION
 DOES NOT MATCH WITH THE LEGAL OWNER OF
 RECORD ON OUR SYSTEM, THE PALM BEACH
 COUNTY PROPERTY APPRAISER'S WEBSITE OR
 THE NOTICE OF COMMENCEMENT SUBMITTED.
 PLEASE CORRECT AND REVISE.
  
  
 2) NOTE: PLEASE SEE THE ADDRESS ON PLANS
 NEEDS TO CORRELATE WITH THE LEGAL
 ADDRESS OF PROPERTY. PLEASE KNOW THAT
 PERMIT APPLICATION WILL BE ROUTED TO THE ADDRESSING
 PERSON TO OBTAIN AN ADDRESS
 EXTENSION FOR THE TENANT SPACE.
 (UNIT/SUITER #).
 PLEASE BE SURE TO PLACE CORRECT ADDRESS
 ON PLANS ALONG WITH ANY REVISED/ NEW
 SUITE .
 FAC 61G1-16.004, FAC 61G15-23.002
  
 3) NOTE: PLEASE SEE MISSING REQUIRED
 LICENSE INFORMATION ON ALL TITLE BLOCKS
 FOR ARCHITECTURAL FIRM. PLEASE SEE FAC
 61G1-16.004 AND FS 481.219.
 MISSING THE REQUIRED CERTIFICATE OF
 AUTHORIZATION NUMBER.
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 4) NOTE: PLEASE SEE THIS IS A TENANT
 SPACE PART OF A LARGER BUILDING AND THE
 NEW SERVICE AS SHOWN IS NOT GRANTED OR
 PERMITTED. 230.2
 ** PLEASE SEE AERIAL MAP PROVIDED.
 PLEASE SEE SERVICE LOCATION FOR THE
 EXISTING SERVICE IS TO BE SHOWN.
 PLEASE SEE SERVICE AS SHOWN IS BEING
 SHOWN AS AN OVERHEAD SERVICE LOCATED ON
 THE SOUTH SIDE OF BUILDING WHERE THE
 BUILDING FROM THE ADJOINING PROPERTY IS
 LOCATED. CLEARANCES AS REQUIRED UNDER
 THE FPL SERVICE GUIDELINES AND NEC ARE
 NOTMET IN EITHER CASE.
 PLEASE KNOW, THE EXISTING SERVICE FOR
 THE BUILDING MUST BE USED OR UPGRADED.
 PLEASE SEE THE 1HR SEPARATION DOES NOT
 MAKE THIS SPACE A SEPARATE BUILDING.
 PLEASE SEE FBC DEFINITIONS OF BUILDING,
 AND REQUIRED "FIRE WALL" IN ORDER TO
 BECOME A SEPARATE BUILDING. PLEASE SEE
 REQUIRED "FIRE WALL" WOULD BE A FOUR HR
 RATED WALL WHICH WOULD PERMIT THE
 COLLAPSE THE ADJOINING STRUCTURE WITHOUT
 AFFECT THE STRUCTURAL INTEGRITY OF THE
 ADJOINING REMAINING BUILDING.
  
 5) NOTE: PLEASE SEE THE SIGN CIRCUIT AS
 BEING SHOWN IS LOCATEDAT THE REAR DOOR
 WHICH BACKS UP TO THE FEC RAILROAD
 TRACKS. PLEASE SEE 600.5 WHICH REQUIRES
 THIS CIRCUIT TO BE LOCATED AT THE FRONT
 ENTRANCE SUBJECT TO PEDESTRIAN TRAFFIC.
  
 6) NOTE: IF TRYING TO OBTAIN COMPLIANCE
 WITH THE 2004 FBC CHAPTER 13,THE
 LIGHTING CONTROLS AS NOTED ARE NOT
 COMPLETE AT THIS TIME.PLEASE SHOW THE
 DETAIL FOR "SYSTEM" BEING PROPOSED.
 PLEASE ALSO INCLUDE EXISTING OFFICE
 AREAS ARE REQUIRED TO BE CONTROLLED BY
 THIS SYSTEM.
 PLEASE PROVIDE SCHEDULING, OVER RIDE
 DEVICES ALONG WITH MAX PERMITTED TIMES
 ON OVER RIDE DEVICES.
 (4HRS MAX FOR TIMER TYPES, 30MIN MAX ON
 OCCUPANT SENSOR TYPES).
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND
 .1.3.
  
 7) NOTE: PLEASE SEE COMMENTS BASED ON
 THE PROPOSED ELECTRICAL RISER ARE MUTE
 AT THIS TIME AS SERVICE SHOWN IS NOT
 PERMITTED. PLEASE HOWEVER SEE SOME ITEMS
 BELOW AS ANY SERVICE UPGRADE WILL
 REQUIRE SOME OF THE SAME ITEMS.
 PLEASE SEE THE FOLLOWING.
 MISSING GAS BOND ON THE GROUNDING
 ELECTRODE SYSTEM, MISSING THE THE
 EQUIPMENT GROUNDING CONDUCTOR FROM MAIN
 TO SUB PANELS. PLEASE SEE WHAT APPEARS
 TO BE A MISPRINT AS 1/4" FOR EQUIPMENT
 GROUND.
 PLEASE SEE MISSING AIC RATING FOR
 MAIN.(SHOWN FOR NEW SUB PANELS).
  
  
 8) NOTE: PLEASE SEE MISSING THE PANEL
 SCHEDULE FOR EXISTING PANEL "E" AND WHERE
 LOADS ARE DERIVED.
 408.4,310.16,240.4, 215.5 ETC
 FBC 106.1.2 ADMIN SECT.
  
 9) NOTE: PLEASE SEE PLANS SHALL STATE
 THE ADOPTED CODES RELEVANT TO PLANS AND
 DESIGN. PLEASE SEE 2002 NFPA-70, 2002
 NFPA-72, 2003 NFPA-101 (SHOWN ON "A"
 SHEETS) AND NFPA-96 2004 ARE ALL
 REQUIRED AT A MINIMUM.
 PLEASE SEE NOTES FROM OTHER TRADES FOR
 OTHER POSSIBLE RELEVANT CODES REQUIRED.
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT THE
 ELECTRICAL DESIGN/PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-10-25 Cont ID  
Sent By mawillia Date 2007-10-25 Time 12:15 Rev Time 0.00
Received By mawillia Date 2007-10-25 Time 12:02 Sent To  
Notes
2007-10-25 12:15:19*****APPROVED*****
  
  
 PLAN SHEETSA120.1 AND E-1 WERE STAMPED, INTIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 15:44 Rev Time 0.00
Received By mawillia Date 2007-07-26 Time 15:42 Sent To  
Notes
2007-07-26 15:44:00*****PROVISO*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED; HOWEVER THE APPROPIATE PLAN SHEETS WILL
 BE STAMPED WHEN ALL PLAN REVIEWS HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-05-07 Cont ID  
Sent By mawillia Date 2007-05-07 Time 13:49 Rev Time 0.00
Received By mawillia Date 2007-05-07 Time 13:38 Sent To  
Notes
2007-05-07 13:49:34*****PROVISO*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED; HOWEVER THE APPROPIATE PLAN SHEETS WILL
 BE STAMPED WHEN ALL PLAN REVIEWS HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-12-14 Cont ID  
Sent By mawillia Date 2006-12-14 Time 15:48 Rev Time 0.00
Received By mawillia Date 2006-12-14 Time 15:10 Sent To  
Notes
2006-12-14 15:24:01*****UNSAT*****
  
  
  
 1.THE NUMERICAL ADDRESS FOR THIS PERMIT IN THE CITY'S
 COMPUTER SYSTEM (WHICH IS BASED ON THE PROPERTY CONTROL
 NUMBER) IS 6600 GEORGIA AVENUE, WHEREAS THE SUBMITTED
 APPLICATION AND THE PLANS HAVE 6612 GEORGIA AVENUE.
 FILE A NEW NOTICE OF COMMENCEMENT REFLECTING 6612
 GEORGIA AVENUE WHERE THE SCOPE OF WORK WILL BE DONE.
  
 2.AS PER NFPA 101, INTERIOR FINISH IN AN
 UNSPRINKLERED BUILDING SHALL BE CLASS "A" OR "B" IN ALL
 AREAS.
  
  
 PLEASE RESPOND TO THE ABOVE AND TO THE PREVIOUS FIRE
 PLAN REVIEW.TO EXPEDITE THE FIRE PLAN REVIEW PROCESS,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-26 Cont ID  
Sent By mwennerg Date 2006-09-26 Time 09:47 Rev Time 0.00
Received By mwennerg Date 2006-09-26 Time 09:47 Sent To  
Notes
2006-09-26 00:00:00***DENIED***
  
 1) PLEASE CLARIFY NOTE (5) ON LS PLAN
 REF: DINING AND SEATING AREAS. IF NOT
 APPLICABLE, PLEASE REMOVE FROM PLANS.
  
 2) DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR EXHAUST HOOD AND
 SUPPRESSION SYSTEMS.
  
 4) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL IF APPLICABLE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-08-17 Cont ID  
Sent By kstevens Date 2007-08-17 Time 07:56 Rev Time 0.00
Received By kstevens Date 2007-08-10 Time 18:19 Sent To  
Notes
2007-08-17 07:58:30 
  
 PASSED/PROVISO
  
 1. SHT P-1 THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
  
 A. OK
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE FROM CONTRACTOR IS THAT THE EQUIPMENT IS
 USED AND WILL BE MOVED FROM AN EXISTING CATERING
 SERVICE. ALL REQUIRED LABELING SHALL BE ON EQUIPMENT
 AND VERIFIED AT TIME OF FINAL INSPECTION, (SEE THE
 FOLLOWING CODE SECTION). THIS IS OK PROVIDING: 301.5
 LABEL INFORMATION.
 A PERMANENT FACTORY-APPLIED NAMEPLATE(S) SHALL BE
 AFFIXED TO APPLIANCES ON WHICH SHALL APPEAR IN LEGIBLE
 LETTERING, THE MANUFACTURER?S NAME OR TRADEMARK, THE
 MODEL NUMBER, SERIAL NUMBER AND, FOR LISTED APPLIANCES,
 THE SEAL OR MARK OF THE TESTING AGENCY. A LABEL SHALL
 ALSO INCLUDE THE HOURLY RATING IN BRITISH THERMAL UNITS
 PER HOUR (BTU/H) (W); THE TYPE OF FUEL APPROVED FOR USE
 WITH THE APPLIANCE; AND THE MINIMUM CLEARANCE
 REQUIREMENTS.
  
  
 C. OK
 8. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-06-06 Cont ID  
Sent By kstevens Date 2007-06-06 Time 14:47 Rev Time 0.00
Received By kstevens Date 2007-06-06 Time 14:47 Sent To  
Notes
2007-06-06 14:47:55DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 *****FROM PREVIOUS REVIEW:
  
  
 1. SHT P-1 THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
  
 A. OK
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE FROM CONTRACTOR IS THAT THE EQUIPMENT IS
 USED AND WILL BE MOVED FROM AN EXISTING CATERING
 SERVICE. ALL REQUIRED LABELING SHALL BE ON EQUIPMENT
 AND VERIFIED AT TIME OF FINAL INSPECTION, (SEE THE
 FOLLOWING CODE SECTION)
 301.5 LABEL INFORMATION.
 A PERMANENT FACTORY-APPLIED NAMEPLATE(S) SHALL BE
 AFFIXED TO APPLIANCES ON WHICH SHALL APPEAR IN LEGIBLE
 LETTERING, THE MANUFACTURER?S NAME OR TRADEMARK, THE
 MODEL NUMBER, SERIAL NUMBER AND, FOR LISTED APPLIANCES,
 THE SEAL OR MARK OF THE TESTING AGENCY. A LABEL SHALL
 ALSO INCLUDE THE HOURLY RATING IN BRITISH THERMAL UNITS
 PER HOUR (BTU/H) (W); THE TYPE OF FUEL APPROVED FOR USE
 WITH THE APPLIANCE; AND THE MINIMUM CLEARANCE
 REQUIREMENTS.
  
  
 C. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. TO BE SHOWN
 ON THE GAS ISOMETRIC RISER DIAGRAM.
 ****RESPONSE NOTED, BUT THERE IS NO MANUAL SHUT OFF
 VALVE UPSTREAM OF THE AUTOMATIC SHUT OFF VALVE AS
 REQUIRED.
 ********NOW MANUAL VALVE IS LOCATED DOWNSTREAM OF THE
 AUTOMATIC SHUT OFF VALVE. PLEASE SHOW THE MANUAL VALVE
 UPSTREAM OF THE AUTOMATIC VALVE.
  
 8. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-12-07 Cont ID  
Sent By kstevens Date 2006-12-07 Time 06:44 Rev Time 0.00
Received By kstevens Date 2006-12-07 Time 06:44 Sent To  
Notes
2006-12-07 06:46:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 *****FROM PREVIOUS REVIEW:
  
  
 1. SHT P-1 THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
  
 A. OK
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE FROM CONTRACTOR IS THAT THE EQUIPMENT IS
 USED AND WILL BE MOVED FROM AN EXISTING CATERING
 SERVICE. ALL REQUIRED LABELING SHALL BE ON EQUIPMENT
 AND VERIFIED AT TIME OF FINAL INSPECTION, (SEE THE
 FOLLOWING CODE SECTION)
 301.5 LABEL INFORMATION.
 A PERMANENT FACTORY-APPLIED NAMEPLATE(S) SHALL BE
 AFFIXED TO APPLIANCES ON WHICH SHALL APPEAR IN LEGIBLE
 LETTERING, THE MANUFACTURER?S NAME OR TRADEMARK, THE
 MODEL NUMBER, SERIAL NUMBER AND, FOR LISTED APPLIANCES,
 THE SEAL OR MARK OF THE TESTING AGENCY. A LABEL SHALL
 ALSO INCLUDE THE HOURLY RATING IN BRITISH THERMAL UNITS
 PER HOUR (BTU/H) (W); THE TYPE OF FUEL APPROVED FOR USE
 WITH THE APPLIANCE; AND THE MINIMUM CLEARANCE
 REQUIREMENTS.
  
  
 C. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. TO BE SHOWN
 ON THE GAS ISOMETRIC RISER DIAGRAM.
 ****RESPONSE NOTED, BUT THERE IS NO MANUAL SHUT OFF
 VALVE UPSTREAM OF THE AUTOMATIC SHUT OFF VALVE AS
 REQUIRED.
  
 8. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-09-09 Cont ID  
Sent By kstevens Date 2006-09-09 Time 09:55 Rev Time 0.00
Received By kstevens Date 2006-09-09 Time 09:54 Sent To  
Notes
2006-09-09 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT P-1 THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
  
 A. TYPE OF GAS, (LP OR NATURAL) NOTE ON
 P-1 STATES LP OR NATURAL GAS. PLEASE
 CLARIFY.
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 C. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. TO BE SHOWN
 ON THE GAS ISOMETRIC RISER DIAGRAM.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-04-04 Cont ID  
Sent By adarroug Date 2008-04-04 Time 10:53 Rev Time 0.00
Received By adarroug Date 2008-04-04 Time 10:53 Sent To M
Notes
2008-04-04 10:53:47TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-09-13 Cont ID  
Sent By adarroug Date 2007-09-13 Time 09:57 Rev Time 0.00
Received By adarroug Date 2007-09-13 Time 09:57 Sent To  
Notes
2007-10-02 14:26:49TO "COMM" BD#9
2007-09-13 09:57:25WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-29 Cont ID  
Sent By dpalmer Date 2007-07-13 Time 08:41 Rev Time 0.00
Received By adarroug Date 2007-06-29 Time 14:23 Sent To  
Notes
2007-07-17 14:39:11TO "COMM" BD#7
2007-06-29 14:25:52WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-23 Cont ID  
Sent By adarroug Date 2007-04-23 Time 08:22 Rev Time 0.00
Received By adarroug Date 2007-04-23 Time 08:22 Sent To  
Notes
2007-04-23 08:22:32TO "COMM" BD#59

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-12 Cont ID  
Sent By adarroug Date 2006-10-12 Time 08:16 Rev Time 0.00
Received By adarroug Date 2006-10-12 Time 18:00 Sent To  
Notes
2006-10-25 10:54:34TO "COMM" BD#4
2006-10-22 10:59:46THIS WILL BE A COMM BOARD PROJECT.. WAITING FOR COMM
 BAORD.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-02 Cont ID  
Sent By pkrauss Date 2006-10-02 Time 14:49 Rev Time 0.00
Received By pkrauss Date 2006-08-22 Time 15:38 Sent To  
Notes
2006-09-07 00:00:00TO "BOB"#1
2006-08-22 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-04-23 Cont ID  
Sent By rregueir Date 2008-04-23 Time 14:53 Rev Time 0.00
Received By rregueir Date 2008-04-17 Time 15:31 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-05-04 Cont ID  
Sent By rregueir Date 2007-05-04 Time 15:53 Rev Time 0.00
Received By rregueir Date 2007-05-04 Time 15:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-11-01 Cont ID  
Sent By pkrauss Date 2006-11-01 Time 09:32 Rev Time 0.00
Received By pkrauss Date 2006-11-01 Time 08:38 Sent To  
Notes
2006-11-01 09:39:37DENIED:
 PLEASE PROVIDE A SURVEY OF THE PROPERTY.
  
 1.THE 8" EXHAUST, DRYWELL & GAS METER ARE ALL LOCATED
 ON THE SOUTH WALL WHICH APPEARS TO BE A ZERO LOT LINE.
  
 PROVISO:
 1.DETAIL OF THE ROOF MOUNTED
 CONDENSING UNIT SHOWN ON PLAN SHEET M-2
 DOES NOT INDICATE CLEARANCE BETWEEN THE
 ROOF AND STAND AS REQUIRED PER 2004 FBC
 TABLE 1509.7
  
 2.MAKEUP AIR FOR THE KITCHEN SHALL
 COMPLY WITH 2004 FMC 508.1.
  
 3.ADDITIONAL PERMITS REQUIRED FOR THE
 HOOD, FIRE SUPPRESSION AND WALK-IN
 COOLERS.PLEASE PROVIDE PLANS AND
 MANUFACTURER'S SUBMITTAL DATA.PLEASE
 INDICATE THE FOLLOWING INFORMATION WITH
 REGARDS TO THE HOOD:
 A) TERMINATION OF EXHAUST. PROVIDE
 DISTANCE TO PROPERTY LINES, PARAPITS,
 ADJOING BUILDINGS, INTAKE OPENINGS,
 ETC.
 B) PROVIDE EQUIPMENT SCHEDULE FOR THE
 EXHAUST FAN.
 C) PROVIDE DUCT SIZE, LAYOUT, & MATERIAL
 D) VELOCITY THROUGH DUCT SHALL BE A
 MINIMUM OF 1,500 FPM BUT NOT GREATER
 THAN 2,500 FPM.
 E) INDICATE CLEARANCES TO COMBUSTIBLES.
 D) PROVIDE DETAIL FOR THE HANGING &
 VIBRATION ISOLATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-10-02 Cont ID  
Sent By pkrauss Date 2006-10-02 Time 11:14 Rev Time 0.00
Received By pkrauss Date 2006-10-02 Time 10:34 Sent To  
Notes
2006-10-02 00:00:00PROVISO:
 1.DETAIL OF THE ROOF MOUNTED
 CONDENSING UNIT SHOWN ON PLAN SHEET M-2
 DOES NOT INDICATE CLEARANCE BETWEEN THE
 ROOF AND STAND AS REQUIRED PER 2004 FBC
 TABLE 1509.7
  
 2.MAKEUP AIR FOR THE KITCHEN SHALL
 COMPLY WITH 2004 FMC 508.1.
  
 3.ADDITIONAL PERMITS REQUIRED FOR THE
 HOOD, FIRE SUPPRESSION AND WALK-IN
 COOLERS.PLEASE PROVIDE PLANS AND
 MANUFACTURER'S SUBMITTAL DATA.PLEASE
 INDICATE THE FOLLOWING INFORMATION WITH
 REGARDS TO THE HOOD:
 A) TERMINATION OF EXHAUST. PROVIDE
 DISTANCE TO PROPERTY LINES, PARAPITS,
 ADJOING BUILDINGS, INTAKE OPENINGS,
 ETC.
 B) PROVIDE EQUIPMENT SCHEDULE FOR THE
 EXHAUST FAN.
 C) PROVIDE DUCT SIZE, LAYOUT, & MATERIAL
 D) VELOCITY THROUGH DUCT SHALL BE A
 MINIMUM OF 1,500 FPM BUT NOT GREATER
 THAN 2,500 FPM.
 E) INDICATE CLEARANCES TO COMBUSTIBLES.
 D) PROVIDE DETAIL FOR THE HANGING &
 VIBRATION ISOLATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-10-30 Cont ID  
Sent By kstevens Date 2007-10-30 Time 10:51 Rev Time 0.00
Received By kstevens Date 2007-10-29 Time 17:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2007-08-17 Cont ID  
Sent By kstevens Date 2007-08-17 Time 07:51 Rev Time 0.00
Received By kstevens Date 2007-08-10 Time 18:19 Sent To  
Notes
2007-08-17 07:56:47DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEWS:
  
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
  
 6. THE TWO PAGE "WORKSHEET" FROM DBPR
 PLAN REVIEW SHALL BE ATTACHED TO EACH
 SET OF PLANS. SECTION 106.1.3.
 ****NOT ADDRESSED, AND NOW THE DBPR STAMPED SHEETS ARE
 NOT IN THE NEW SETS OF PLANS AS REQUIRED. PLEASE HAVE
 STAMPED SHEETS FROM DBPR IN EACH SET OF PLANS ALONG
 WITH THE TWO PAGE "WORKSHEETS".
 ********COMMENT NOT ADDRESSED. PLEASE SUBMIT A MINIMUM
 OF TWO SETS OF PLANS FOR REVIEW WILL ALL REQUIRED
 SHEETS.
 ******RESPONSE NOTED, THE DBPR SHEETS SHALL BE
 RESEALED, SIGNED & DATED BY THE ARCHITECT OF RECORD AND
 INSERTED IN THE PLANS WITH THE NOTE THAT THE SHEET IS
 FOR DBPR REVIEW STAMP ONLY.
  
 7. SHT P-1 THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
  
 A. OK
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE FROM CONTRACTOR IS THAT THE EQUIPMENT IS
 USED AND WILL BE MOVED FROM AN EXISTING CATERING
 SERVICE. ALL REQUIRED LABELING SHALL BE ON EQUIPMENT
 AND VERIFIED AT TIME OF FINAL INSPECTION, (SEE THE
 FOLLOWING CODE SECTION). THIS IS OK PROVIDING:
 301.5 LABEL INFORMATION.
 A PERMANENT FACTORY-APPLIED NAMEPLATE(S) SHALL BE
 AFFIXED TO APPLIANCES ON WHICH SHALL APPEAR IN LEGIBLE
 LETTERING, THE MANUFACTURER?S NAME OR TRADEMARK, THE
 MODEL NUMBER, SERIAL NUMBER AND, FOR LISTED APPLIANCES,
 THE SEAL OR MARK OF THE TESTING AGENCY. A LABEL SHALL
 ALSO INCLUDE THE HOURLY RATING IN BRITISH THERMAL UNITS
 PER HOUR (BTU/H) (W); THE TYPE OF FUEL APPROVED FOR USE
 WITH THE APPLIANCE; AND THE MINIMUM CLEARANCE
 REQUIREMENTS.
  
  
 C. OK
 8. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-06-06 Cont ID  
Sent By kstevens Date 2007-06-06 Time 14:41 Rev Time 0.00
Received By kstevens Date 2007-06-06 Time 14:41 Sent To  
Notes
2007-06-06 14:47:01DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
  
 6. THE TWO PAGE "WORKSHEET" FROM DBPR
 PLAN REVIEW SHALL BE ATTACHED TO EACH
 SET OF PLANS. SECTION 106.1.3.
 ****NOT ADDRESSED, AND NOW THE DBPR STAMPED SHEETS ARE
 NOT IN THE NEW SETS OF PLANS AS REQUIRED. PLEASE HAVE
 STAMPED SHEETS FROM DBPR IN EACH SET OF PLANS ALONG
 WITH THE TWO PAGE "WORKSHEETS".
 ********COMMENT NOT ADDRESSED. PLEASE SUBMIT A MINIMUM
 OF TWO SETS OF PLANS FOR REVIEW WILL ALL REQUIRED
 SHEETS.
  
 7. SHT P-1 THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
  
 A. OK
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE FROM CONTRACTOR IS THAT THE EQUIPMENT IS
 USED AND WILL BE MOVED FROM AN EXISTING CATERING
 SERVICE. ALL REQUIRED LABELING SHALL BE ON EQUIPMENT
 AND VERIFIED AT TIME OF FINAL INSPECTION, (SEE THE
 FOLLOWING CODE SECTION)
 301.5 LABEL INFORMATION.
 A PERMANENT FACTORY-APPLIED NAMEPLATE(S) SHALL BE
 AFFIXED TO APPLIANCES ON WHICH SHALL APPEAR IN LEGIBLE
 LETTERING, THE MANUFACTURER?S NAME OR TRADEMARK, THE
 MODEL NUMBER, SERIAL NUMBER AND, FOR LISTED APPLIANCES,
 THE SEAL OR MARK OF THE TESTING AGENCY. A LABEL SHALL
 ALSO INCLUDE THE HOURLY RATING IN BRITISH THERMAL UNITS
 PER HOUR (BTU/H) (W); THE TYPE OF FUEL APPROVED FOR USE
 WITH THE APPLIANCE; AND THE MINIMUM CLEARANCE
 REQUIREMENTS.
  
  
 C. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. TO BE SHOWN
 ON THE GAS ISOMETRIC RISER DIAGRAM.
 ****RESPONSE NOTED, BUT THERE IS NO MANUAL SHUT OFF
 VALVE UPSTREAM OF THE AUTOMATIC SHUT OFF VALVE AS
 REQUIRED.
 ********NOW MANUAL VALVE IS LOCATED DOWNSTREAM OF THE
 AUTOMATIC SHUT OFF VALVE. PLEASE SHOW THE MANUAL VALVE
 UPSTREAM OF THE AUTOMATIC VALVE.
  
 8. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-12-07 Cont ID  
Sent By kstevens Date 2006-12-07 Time 06:23 Rev Time 0.00
Received By kstevens Date 2006-12-06 Time 18:58 Sent To  
Notes
2006-12-07 06:36:13DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
  
 1. PER TABLES 1004.1.2 AND 403.1 2-W/C'S
 AND SEPARATE FACILITIES ARE REQUIRED. -
 ALSO A DRINKING FOUNTAIN IS REQUIRED.
 ****RESPONSE NOTED, BUT NO DRINKING FOUNTAIN PROVIDED.
  
 2. ALL ARCHITECTURAL SHEETS. PER FAC 61G1-16.004(2) A
 BUSINESS NUMBER IS REQUIRED. FS 481.219. ****RESPONSE
 NOTED, BUT THE GENERAL NOTES REFER TO RJS ARCHITECTS
 INC. IN NOTES 1, (TWICE), 4, & 8. ALL REFERENCES TO RJS
 ARCHITECTS INC. SHALL BE DELETED FROM PLANS OR A
 BUSINESS NUMBER WILL BE REQUIRED.
  
 3. OK
 4. OK
 5. OK
  
 6. THE TWO PAGE "WORKSHEET" FROM DBPR
 PLAN REVIEW SHALL BE ATTACHED TO EACH
 SET OF PLANS. SECTION 106.1.3.
 ****NOT ADDRESSED, AND NOT THE DBPR STAMPED SHEETS ARE
 NOT IN THE NEW SETS OF PLANS AS REQUIRED. PLEASE HAVE
 STAMPED SHEETS FROM DBPR IN EACH SET OF PLANS ALONG
 WITH THE TWO PAGE "WORKSHEETS".
  
 7. SHT P-1 THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
  
 A. OK
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE FROM CONTRACTOR IS THAT THE EQUIPMENT IS
 USED AND WILL BE MOVED FROM AN EXISTING CATERING
 SERVICE. ALL REQUIRED LABELING SHALL BE ON EQUIPMENT
 AND VERIFIED AT TIME OF FINAL INSPECTION, (SEE THE
 FOLLOWING CODE SECTION)
 301.5 LABEL INFORMATION.
 A PERMANENT FACTORY-APPLIED NAMEPLATE(S) SHALL BE
 AFFIXED TO APPLIANCES ON WHICH SHALL APPEAR IN LEGIBLE
 LETTERING, THE MANUFACTURER?S NAME OR TRADEMARK, THE
 MODEL NUMBER, SERIAL NUMBER AND, FOR LISTED APPLIANCES,
 THE SEAL OR MARK OF THE TESTING AGENCY. A LABEL SHALL
 ALSO INCLUDE THE HOURLY RATING IN BRITISH THERMAL UNITS
 PER HOUR (BTU/H) (W); THE TYPE OF FUEL APPROVED FOR USE
 WITH THE APPLIANCE; AND THE MINIMUM CLEARANCE
 REQUIREMENTS.
  
  
 C. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. TO BE SHOWN
 ON THE GAS ISOMETRIC RISER DIAGRAM.
 ****RESPONSE NOTED, BUT THERE IS NO MANUAL SHUT OFF
 VALVE UPSTREAM OF THE AUTOMATIC SHUT OFF VALVE AS
 REQUIRED.
  
 8. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-07 Cont ID  
Sent By kstevens Date 2006-09-07 Time 12:57 Rev Time 0.00
Received By kstevens Date 2006-09-07 Time 12:57 Sent To  
Notes
2006-09-07 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
 1. PER TABLES 1004.1.2 AND 403.1 2-W/C'S
 AND SEPARATE FACILITIES ARE REQUIRED. -
 ALSO A DRINKING FOUNTATIN IS REQUIRED.
  
 2. ALL ARCHITECTURAL SHEETS. PER FAC 61G1-16.004(2) A
 BUSINESS NUMBER IS
 REQUIRED. FS 481.219.
  
 3. ALL ARCHITECTURAL SHEETS. ONE CAN NOT
 GLEAN THE REQUIRED INFORMATION FROM THE
 SEAL AS STATED IN 61G1-16.002(1). PLEASE
 RESEAL SO REQUIRED INFORMATION CAN BE
 READ. FS 481.2055.
  
 4. THE GREASE INTERCEPTOR SHALL BE SIZED
 BY LYNN MASSON, ENVIRONMENTAL COMPLIANCE
 MANAGER. PLEASE CONTACT LYNN AT (561)
 822-2271, OR (561) 822-2279 (FAX) OR
 E-MAIL AT [email protected].
  
 5. SHTS A125.1 AND A130.1. A125.1 SHOWS
 1 TOILET ROOM WHEREAS SHT A130.1 SHOWS
 TWO TOILET ROOMS. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 6. THE TWO PAGE "WORKSHEET" FROM DBPR
 PLAN REVIEW SHALL BE ATTACHED TO EACH
 SET OF PLANS. SECTION 106.1.3.
  
 7. SHT P-1 THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
  
 A. TYPE OF GAS, (LP OR NATURAL) NOTE ON
 P-1 STATES LP OR NATURAL GAS. PLEASE
 CLARIFY.
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 C. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. TO BE SHOWN
 ON THE GAS ISOMETRIC RISER DIAGRAM.
  
 8. SHT P-3 GREASE INTERCEPTOR DETAIL.
 SEE ATTACHED SHEET FOR STANDARD GREAS
 INTERCEPTOR DETAIL. SEE MINIMUM
 REQUIREMENTS FOR SIDE WALLS, BOTTOM,
 ETC. NO FIBERGLASS INTERCEPTORS
 APPROVED. INTERCEPTOR SHALL BE MADE OF
 STEEL REINFORCED CONCRETE PER MUNICIPAL
 CODE SECTION 90-124(7)(F). PLEASE SUBMIT
 A MANUF. SPECIFICATION SHEET FOR GREASE INTERCEPTOR FOR
 APPROVAL. INDICATE MODEL
 NUMBER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2007-08-06 Cont ID  
Sent By kdfreema Date 2007-08-06 Time 16:02 Rev Time 0.00
Received By kdfreema Date 2007-08-06 Time 16:02 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved