Plan Review Details - Permit 06081563
Plan Review Stops For Permit 06081563
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-29 Cont ID  
Sent By rmcdouga Date 2007-01-29 Time 17:18 Rev Time 0.00
Received By rmcdouga Date 2007-01-29 Time 17:18 Sent To  
Notes
2007-01-29 18:16:16DENIED BY BUILDING
  
 1)LETTER FROM THE PROPERTY OWNER REQUIRES THE
 GENERATOR TO BE FULLY ENCLOSED BY MASONRY WALLS. THIS
 IS NOT INDICATED ON THE SITE PLAN. PLEASE CLARIFY. SHOW
 LOCATION OF THE WALL AND PROVIDE STRUCTURAL DETAILS, IF
 IT WILL BE INSTALLED.
  
 2) ADDRESS COMMENTS OF OTHER TRADES.
  
 3) THE TOP THE EQUIPMENT PAD IS REQUIRED TO BE 17 FEET
 PLUS THE 6 INCHES REQUIRED BY CITY ORDINANCE ABOVE
 NGVD. AN ELEVATION CERTIFICATE WILL BE REQUIRED,
  
 4) ADDRESS COMMENTS FROM OTHER TRADES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-28 Cont ID  
Sent By rmcdouga Date 2006-08-28 Time 13:28 Rev Time 0.00
Received By rmcdouga Date 2006-08-28 Time 12:44 Sent To  
Notes
2006-08-28 00:00:00DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE EQUIPMENT IS LOACTED IN AN "A8"
 FLOOD ZONE AND ELEVATION CERTIFICATE
 WILL BE REQUIRED. BASE FLOOD ELEVATION
 IS 16 FEET PLUS THE .5 FEET REQUIRED BY
 CITY ORDINANCE.
  
 3) PROVIDE DETAILS OF THE SLAB THAT WILL
 SUPPORT THE GENERATOR. INDICATE HOW THE
 GENERATOR WILL BE ANCHORED TO THE SLAB.
 SHOW COMPLIANCE WITH FBC 1609.1.3 FOR
 ANCHORAGE AGAINST OVERTURNING, UPLIFT
 AND SLIDING. PROVIDE PLANS ENOUGH TO
 VERIFY LOCATION OF GENERATOR VERSES
 BUILDING OPENINGS WINDOWS, DOORS OR
 SOFFIT TYPE VENTS, ETC.
 GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BE USED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-29 Cont ID  
Sent By dpalmer Date 2007-01-29 Time 08:02 Rev Time 0.00
Received By dpalmer Date 2007-01-28 Time 18:32 Sent To  
Notes
2007-01-29 08:03:07***** UNSAT 2ND REVIEW *******
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
 PLEASE SEE COMMENTS BELOW WHICH ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A *NO* OR *OK* IN FRONT OF
 PREVIOUS NOTE.
  
 **IMPORTANT**
 *PLEASE SEE NEW NOTES NOW ADDED FOR THESE PLANS NOW
 SUBMITTED.
  
  
 1) NOTE:NO, PLEASE SEE PLANS, PERMIT APPLICATION AND
 GENERATOR SPECS DO NOT CORRELATE.
 A) PLEASE SEE PLANS NOW SHOW TWO COMPLETELY DIFFERENT
 SIZES OF GENERATORS (ONE 80KW AND ONE 60KW).
 B) PLEASE SEE SPECS FOR UNIT ARE FOR A NATURAL GAS UNIT
 AND PLANS AND APPLICATION IS FOR DIESEL.
 C) PLEASE SEE FUEL TANK IS FOR A DIESEL UNIT.
 D) PLEASE SEE PLANS CALL FOR NATURAL GAS ALSO??
 E) PLEASE PROVIDE DOCUMENTATION ON THIS LEGALLY
 REQUIRED STANDBY UNIT AND HOW MUCH ON SITE FUEL IS
 REQUIRED AND FUEL CONSUMPTION ON THIS UNIT ONCE ALL HAS
 BEEN COORDINATED
  
 ** PLEASE CORRELATE ALL AND CORRECT PLANS.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1**
 PLEASE CORRELATE PLANS, SPECS AND APPLICATION. PLEASE
 SEE APPLICATION IS FOR A DIESEL GEN, SPECS FOR A DIESEL
 AND SPEC FOR NAT GAS. PLEASE SEE PLANS DO NOT INDICATE
 WHICH ONE OF EITHER.
 PLEASE KNOW, AS BEING LEGALLY REQUIRED, PLEASE SEE
 701.11B3
  
 2) NOTE: OK.
  
 3) NOTE:NO, PLEASE KNOW AS THE UNIT IS STILL IN
 QUESTION, THE SET BACKS CAN NOT BE CONFIRMED AT THIS
 TIME. PLEASE ALSO SEE THE MANUFACTURES SPECS/CUT SHEETS
 DO NOT CORRELATE SO THE CORRECT SET BACKS CAN NOT BE
 DETERMINED AT THIS TIME. PLEASE SEE THE SPEC/CUT SHEETS
 FROM THE MANUFACTURE DO NOT CONTAIN ANY INFORMATION AS
 TO THEIR MINIMUM REQUIRED CLEARANCES. PLEASE KNOW BASED
 ON THE MANUFACTURE AND TYPE OF UNIT BEING INSTALLED,
 THIS WILL VARY MANY TIMES FROM 3FT TO 5FT OR MORE.
 PLEASE SEE AS DOCUMENTATION IN PLANS CALLS FOR WALLS
 ETC TO BE INSTALLED AND NOT ON PLANS THIS CAN NOT BE
 CONFIRMED AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1**
 PLEASE SEE PLANS DO NOT SHOW ALL SET BACKS AND
 DISTANCES FROM SURROUNDING BUILDINGS FOR MINIMUM
 CLEARANCES FROM WINDOWS STRUCTURES ETC.
 PLEASE BE SURE THE MIN CLEARANCES FROM ALL CLEARANCES
 ARE SHOWN/ AND STATED FROM MANUFACTURE. PLEASE SEE A
 MIN OF 5FT FROM BUILDING FOR CLEARANCE MAY BE REQUIRED
 DEPENDING ON MANUFACTURE. 10FT MAY BE REQUIRED FOR ANY
 OPENINGS INTO BUILDING FOR MECHANICAL VENTILATION,
 PLEASE SEE 3FT IS MIN FOR ELECTRICAL/WORKING
 CLEARANCE.
 PLEASE SEE 110.26, 90.7, 110.3 AND NOTES FROM OTHER
 TRADES.
  
 4) NOTE: NO, SAME NOTE FOR ANY VERTICAL RUNS.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1**
 PLEASE SEE HEIGHT OF BUILDING IS NOT SHOWN; PLEASE SEE
 300.19 FOR STRAIN RELIEF REQUIRED FOR CONDUCTORS ON
 VERTICAL RUNS.
  
 5) NOTE:NO, PLEASE SEE THE PLANS NOW INDICATE A NEW
 DISCONNECT HOWEVER NO INFORMATION FOR LOCATION AND
 WHERE THIS IS SHOWN ON PLAN OVER VIEW IN COMPARISON TO
 THE MAIN ELECTRICAL ROOM.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1**
 PLEASE SEE MISSING MEANS OF DISCONNECT FOR FEEDERS FROM
 GEN TO BUILDING. PLEASE SHOW LOCATION OF ALL EXISTING
 MEANS OF DISCONNECTS FOR MAIN BLDG.
 PLEASE SEE 225.34, 230.72.
 225.31-225.39,701.11B5, ALSO 110.27
  
 6) NOTE: NO, NO INFORMATION IS BEING SHOWN FOR ROUTING
 OF THESE CONDUITS.
 ARE THERE ANY CONDUITS BEING RUN IN BUILDING?
 ARE THERE ANY CONDUITS RUN IN EGRESS STAIRS OR ELEVATOR
 EQUIPMENT ROOMS?
 ** PLEASE PROVIDE THIS INFORMATION.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1**
 PLEASE SHOW HOW AND WHERE CONDUITS FOR FEEDERS ARE
 BEING RUN IN
 BLDG. (PLEASE KNOW, NO CONDUITS ARE PERMITTED IN
 EXIT/EGRESS STAIRS.
 FBC 106.1.2
  
 7) NOTE: OK
  
 8) NOTE: NO, THE APPLIED AMOUNT WHICH WAS INCREASED TO
 $25K WAS INCREASED TO $35K BASED ON THE PLANS SUBMITTED
 AND THE SCOPE OF WORK IN DOCUMENTATION.
 PLEASE KNOW BASED ON THE PLANS, DOCUMENTATION NOW
 PROVIDED ADDITIONAL FEES OF $222.00 IS NOW OWED.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1**
 PLEASE KNOW, DEPENDING ON THE TOTAL SCOPE OF WORK THE
 APPLIED VALUE IS REQUIRED TO BASED ON ALL LABOR AND
 MATERIALS. FBC 108.3. (EVEN OF ANY EQUIPMENT/MATERIALS
 ARE OWNER SUPPLIED.
  
  
 **** NEW NOTES ****
  
 9) NOTE: PLEASE SEE PAPER WORK AND DOCUMENTATION NOW
 SUBMITTED WHICH STATES NEW MASONRY WALLS ARE TO BE
 INSTALLED, HOWEVER NO PLANS, SET BACKS ETC WERE
 SUBMITTED TO SHOW SCOPE OF WORK. PLEASE KNOW THE VALUE
 MAY ALSO BE ADJUSTED.
  
 10) NOTE: PLEASE SEE LETTERS MENTIONS THIS JOB LOCATION
 TO BE IN PALM BEACH COUNTY JURISDICTION; HOWEVER THIS
 IS IN THE CITY OF WEST PALM BEACH.
  
 12) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
  
 13) NOTE: PLEASE KNOW THAT BASED ON THE COORDINATION OF
 PLANS AND SPECS SUBMITTED, THERE MAY BE COMMENTS ONCE
 AGAIN ON THE FOLLOWING REVIEW WHICH HAS NOT YET BEEN
 MADE AT THIS TIME.
  
 14) NOTE: PLEASE KNOW SINCE THIS IS NOW BEING STATED IN
 A FLOOD ZONE, A CERTIFIED ELEVATION CERTIFICATE WILL BE
 REQUIRED BEFORE FINAL. PLEASE SUBMIT TWO COPIES, ONE
 WILL BE RETAINED AND PLACED IN FILE AND THE OTHER WILL
 BE STAMPED FOR JOBSITE FOR FINAL INSPECTION. THIS IS
 NOT REQUIRED AT THIS TIME AND IS ONLY BEING NOTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-28 19:02:142007-01-28 19:02:14
  
 IN ELEC FOR REVIEW
 NOTES TO FOLLOW. WILL BE IN *F* STATUS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-27 Cont ID  
Sent By dpalmer Date 2006-08-27 Time 13:28 Rev Time 0.00
Received By dpalmer Date 2006-08-27 Time 13:15 Sent To  
Notes
2006-08-27 00:00:00***** UNSAT *******
  
 1) NOTE: PLEASE CORRELATE PLANS, SPECS
 AND APPLICATION. PLEASE SEE APPLICATION
 IS FOR A DIESEL GEN, SPECS FOR A DIESEL
 AND SPEC FOR NAT GAS. PLEASE SEE PLANS
 DO NOT INDICATE WHICH ONE OF EITHER.
 PLEASE KNOW, AS BEING LEGALLY REQUIRED,
 PLEASE SEE 701.11B3
  
 2) NOTE: PLEASE SEE PLANS SHOULD REFLECT
 ALL CURRRENTS CODES IN EFFECT.
 2004 FBC, 2002 NFPA-70, 2002 NFPA-110,
 2003 NFPA-101 (MIN).
  
 3) NOTE: PLEASE SEE PLANS DO NOT SHOW
 ALL SET BACKS AND DISTANCES FROM
 SURROUNDING BUILDINGS FOR MINIMUM
 CLEARENCES FROM WINDOWS STRUCTURES ETC.
 PLEASE BE SURE THE MIN CLEARENCES FRO
 ALL CLEARENCES ARE SHOWN/ AND STATD FROM MANUFACTURE.
 PLEASE SEE A MIN OF 5FT
 FROM BUILDING FOR CLEARNCE MAY BE
 REQUIRED DEPENDING ON MANUFACTURE. 10FT
 MAY BE REQUIRED FOR ANY OPENINGS INTO
 BUIDLIGN FOR MECHANICAL VENTILATION,
 PLEASE SEE 3FT IS MIN FOR
 ELECTRICAL/WORKING CLEARENCE.
 PLEASE SEE 110.26,90.7,110.3 AND NOTES
 FROM OTHER TRADES.
  
 4) NOTE: PLEASE SEE HEIGHT OF BUILDING
 IS NOT SHOWN, PLEASE SEE 300.19 FOR
 STRAIN RELIEF REQUIRED FOR CONDUCTORS ON
 VERTICAL RUNS.
  
 5) NOTE: PLEASE SEE MISSING MEANS OF
 DISCONNECT FOR FEEDERS FROM GEN TO
 BUILDING. PLEASE SHOW LOCATION OF ALL
 EIXSTING MEANS OF DISCONNECTS FOR MAIN
 BLDG.
 PLEASE SEE 225.34, 230.72.
 225.31-225.39,701.11B5, ALSO 110.27
  
 6) NOTE: PLEASE SHOW HOW AND WHERE
 CONDUITS FOR FEEDERS ARE BEING RUN IN
 BLDG. (PLEASE KNOW, NO CONDUITS ARE
 PERMITTED IN EXIT/EGRESS STAIRS.
 FBC 106.1.2
  
 7) NOTE: PLEASE PROVIDE INFORMATION FOR
 LOADS ON PROPOSED GENERATOR.
 701.6, 220
  
 8) NOTE: PLEASE KNOW, DEPENDING ON THE
 TOTAL SCOPE OF WORK THE APPLIED VALUE IS
 REQUIRED TO BASED ON ALL LABOUR AND
 MATERIALS. FBC 108.3. (EVEN OF ANY EQUIPMENT/MATERIALS
 ARE OWNER SUPPLIED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-02-23 Cont ID  
Sent By mawillia Date 2007-02-23 Time 18:58 Rev Time 0.00
Received By mawillia Date 2007-02-23 Time 18:58 Sent To  
Notes
2007-02-23 19:02:26*****DENIED*****
  
  
 THE PREVIOUS FIRE PLAN REVIEW COMMENTS HAVE BEEN
 SATISFIED, HOWEVER, THE CONCERNS/COMMENTS OF THE OTHER
 PLAN REVIEWERS MUST BE ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-02 Cont ID  
Sent By mawillia Date 2006-10-02 Time 10:29 Rev Time 0.00
Received By mawillia Date 2006-10-02 Time 10:28 Sent To  
Notes
2006-10-02 00:00:00*****DENIED*****
  
  
  
  
 1.) NFPA 101-2003 EDITION, FLORIDA FIRE
 PREVENTION CODE-2004 EDITION, AND NFPA
 110-2002 EDITION SHALL BE REFERENCED.
  
  
 2.) CONSTRUCTION AND/OR DEMOLITION
 OPERATIONS SHALL NOT INTERFERE OR HINDER
 EMERGENCY ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF.
  
 3.) INDICATE THE TYPE(S) AND AMOUNT OF
 FUEL(S) TO BE USED AND/OR STORED FOR
 THIS OPERATION.
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2007-01-28 18:33:13NEEDS

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-02-14 Cont ID  
Sent By kstevens Date 2007-02-14 Time 18:24 Rev Time 0.00
Received By kstevens Date 2007-02-14 Time 18:24 Sent To  
Notes
2007-02-14 18:35:58DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 FROM PREVIOUS REVIEW:
  
 A. AS OF 8-25-06 ALL ELECTRICAL, GAS OR
 DIESEL INFORMATION IS REQUIRED WHEN THE
 GEN-COM PERMIT IS APPLIED FOR.
 ****NATURAL GAS INDICATED ON SHT E2.1.
  
 B. OK
  
 C. IF NATURAL GAS OR LP GAS THE
 FOLLOWING INFORMATION IS REQUIRED:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****NO RESPONSE, NOT ADDRESSED.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ****NO RESPONSE, NOT ADDRESSED.
  
 3. OK -NATURAL.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 ****NO RESPONSE, NOT ADDRESSED.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ****NO RESPONSE, NOT ADDRESSED.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ****NO RESPONSE, NOT ADDRESSED
  
 7. OK
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. INSTALLATION
 INSTRUCTIONS ARE REQUIRED
 AT TIME OF PLAN REVIEW TO VERIFY
 REQUIRED CLEARANCES FOR SERVICE ETC.
 ****THE MAXIMUM BTU LOAD IS NOT SHOWN ON THE MANUF.
 SPECIFICATION SHEETS.
  
 9.N/A
 10. N/A
  
 *************NEW COMMENT*************
  
 1B. SHOW THE LOCATION OF THE GAS METER ON THE PLANS.
 SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-09-09 Cont ID  
Sent By kstevens Date 2006-09-09 Time 14:32 Rev Time 0.00
Received By kstevens Date 2006-09-09 Time 14:32 Sent To  
Notes
2006-09-09 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 A. AS OF 8-25-06 ALL ELECTRICAL, GAS OR
 DIESEL INFORMATION IS REQUIRED WHEN THE
 GEN-COM PERMIT IS APPLIED FOR.
  
 B. BOTH DIESEL AND GAS MODEL MANUF.
 SPECIFICATION SHEETS HAVE BEEN
 SUBMITTED. PLEASE INDICATE FUEL SOURCE
 FOR THIS GENERATOR. SECTION 106.1.1.
  
 C. IF NATURAL GAS OR LP GAS THE
 FOLLOWING INFORMATION IS REQUIRED:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF. INSTALLATION
 INSTRUCTIONS ARE REQUIRED
 AT TIME OF PLAN REVIEW TO VERIFY
 REQUIRED CLEARANCES FOR SERVICE ETC.
  
 9. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 10. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-17 Cont ID  
Sent By adarroug Date 2007-01-17 Time 16:30 Rev Time 0.00
Received By adarroug Date 2007-01-17 Time 16:30 Sent To  
Notes
2007-01-24 09:13:07TO "COMM" BD#64
2007-01-17 16:30:29WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-05 Cont ID  
Sent By adarroug Date 2006-10-05 Time 16:29 Rev Time 0.00
Received By adarroug Date 2006-08-17 Time 18:09 Sent To  
Notes
2006-08-25 00:00:00TO "COMM" BD#31
2006-08-17 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-02-24 Cont ID  
Sent By hmoser Date 2007-02-24 Time 09:40 Rev Time 0.00
Received By hmoser Date 2007-02-24 Time 09:40 Sent To  
Notes
2007-02-24 09:43:59PLAN DENIED
 IF NATURAL GAS IS USED NO MECHANICAL PERMIT IS REQUIRED
 . IF DIESAL IS USED PLEASE REFER TO GAS REVIEW NOTE (A)
 .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-05 Cont ID  
Sent By hmoser Date 2006-10-05 Time 10:48 Rev Time 0.00
Received By hmoser Date 2006-10-05 Time 10:51 Sent To  
Notes
2006-10-05 00:00:00PLAN DENIED
 PLEASE REFER TO GAS REVIEW FOR
 MECHANICAL .
 PLAN REVIRW BY HAROLD MOSER 561-805-6732

Review Stop Z ZONING
Rev No 3 Status F Date 2007-02-08 Cont ID  
Sent By mmclean Date 2007-02-08 Time 13:49 Rev Time 0.00
Received By mmclean Date 2007-02-08 Time 13:48 Sent To  
Notes
2007-02-08 14:50:01DENIED,
 1. SEE ELECTRICAL COMMENTS 1 (A)
 2. PLEASE PROVIDE MASONARY WALL DETAIL AS INDICATED IN
 THE WRITTEN CONTRACT.
 3. PLEASE PROVIDE COPIES OF THE LEASE AGREEMENT TO PUT
 THE PROPOSED GENERATOR.
 4. THE SITEPLAN PROVIDE DOES NOT PROVIDE THE PARKING
 DETAIL SHOWING THE LOCATION OF THE PROPOSED GENERATOR.
 5. THE PROPERTY IS SHOWN AS A SUB-DIVIDED PROPERTY,
 PLEASE PROVIDE THE UNITY OF TITLE COMBINING THE
 PROPERTY INTO ONE.
 6. THE PROPOSED GENERATOR CANNOT ENROACH ON PROPERTY
 LINE.NEED TO PROVIDE TWO SEPARATE SITEPLANS FOR THE
 PROPERTY TO WHICH THE GENERATOR WILL BE PLACED AND SHOW
 THE SETBACKS FROM PROPERTY LINE AND STRUCTURE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
2007-01-28 18:45:41NEEDS, NEW SHEETS FOR ZONING.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-10-03 Cont ID  
Sent By eschneid Date 2006-09-29 Time 18:46 Rev Time 0.00
Received By MMCLEAN Date 2006-09-29 Time 18:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-09-05 Cont ID  
Sent By mmclean Date 2006-09-05 Time 16:29 Rev Time 0.00
Received By mmclean Date 2006-09-05 Time 16:29 Sent To  
Notes
2006-09-05 00:00:00DENIED,
 1. THE SITEPLAN SUBMITTED DOES NOT
 PROVIDE THE ADDRESS OF THE PROPERTY.
 2. THE SITPLAN MUST PROVIDE THE SETBACKS
 OF THE STRUCTURE FROM PROPERTY LINE.
 3. PLEASE INDICATE IF THE GENERATOR WILL
 IN ANY ASSIGNED PARKING SPACE.
  
 NOTE: THE PROPOSED GENERATOR MUST BE
 SCREEN FROM VISBILITY WITH LANDSCAPE
 HEDGES 94-444(B)