| 2007-01-29 08:03:07 | ***** UNSAT 2ND REVIEW ******* |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING. |
| | PLEASE SEE COMMENTS BELOW WHICH ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW WITH A *NO* OR *OK* IN FRONT OF |
| | PREVIOUS NOTE. |
| | |
| | **IMPORTANT** |
| | *PLEASE SEE NEW NOTES NOW ADDED FOR THESE PLANS NOW |
| | SUBMITTED. |
| | |
| | |
| | 1) NOTE:NO, PLEASE SEE PLANS, PERMIT APPLICATION AND |
| | GENERATOR SPECS DO NOT CORRELATE. |
| | A) PLEASE SEE PLANS NOW SHOW TWO COMPLETELY DIFFERENT |
| | SIZES OF GENERATORS (ONE 80KW AND ONE 60KW). |
| | B) PLEASE SEE SPECS FOR UNIT ARE FOR A NATURAL GAS UNIT |
| | AND PLANS AND APPLICATION IS FOR DIESEL. |
| | C) PLEASE SEE FUEL TANK IS FOR A DIESEL UNIT. |
| | D) PLEASE SEE PLANS CALL FOR NATURAL GAS ALSO?? |
| | E) PLEASE PROVIDE DOCUMENTATION ON THIS LEGALLY |
| | REQUIRED STANDBY UNIT AND HOW MUCH ON SITE FUEL IS |
| | REQUIRED AND FUEL CONSUMPTION ON THIS UNIT ONCE ALL HAS |
| | BEEN COORDINATED |
| | |
| | ** PLEASE CORRELATE ALL AND CORRECT PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE FROM REVIEW #1** |
| | PLEASE CORRELATE PLANS, SPECS AND APPLICATION. PLEASE |
| | SEE APPLICATION IS FOR A DIESEL GEN, SPECS FOR A DIESEL |
| | AND SPEC FOR NAT GAS. PLEASE SEE PLANS DO NOT INDICATE |
| | WHICH ONE OF EITHER. |
| | PLEASE KNOW, AS BEING LEGALLY REQUIRED, PLEASE SEE |
| | 701.11B3 |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE:NO, PLEASE KNOW AS THE UNIT IS STILL IN |
| | QUESTION, THE SET BACKS CAN NOT BE CONFIRMED AT THIS |
| | TIME. PLEASE ALSO SEE THE MANUFACTURES SPECS/CUT SHEETS |
| | DO NOT CORRELATE SO THE CORRECT SET BACKS CAN NOT BE |
| | DETERMINED AT THIS TIME. PLEASE SEE THE SPEC/CUT SHEETS |
| | FROM THE MANUFACTURE DO NOT CONTAIN ANY INFORMATION AS |
| | TO THEIR MINIMUM REQUIRED CLEARANCES. PLEASE KNOW BASED |
| | ON THE MANUFACTURE AND TYPE OF UNIT BEING INSTALLED, |
| | THIS WILL VARY MANY TIMES FROM 3FT TO 5FT OR MORE. |
| | PLEASE SEE AS DOCUMENTATION IN PLANS CALLS FOR WALLS |
| | ETC TO BE INSTALLED AND NOT ON PLANS THIS CAN NOT BE |
| | CONFIRMED AT THIS TIME. |
| | |
| | ** PREVIOUS REVIEW NOTE FROM REVIEW #1** |
| | PLEASE SEE PLANS DO NOT SHOW ALL SET BACKS AND |
| | DISTANCES FROM SURROUNDING BUILDINGS FOR MINIMUM |
| | CLEARANCES FROM WINDOWS STRUCTURES ETC. |
| | PLEASE BE SURE THE MIN CLEARANCES FROM ALL CLEARANCES |
| | ARE SHOWN/ AND STATED FROM MANUFACTURE. PLEASE SEE A |
| | MIN OF 5FT FROM BUILDING FOR CLEARANCE MAY BE REQUIRED |
| | DEPENDING ON MANUFACTURE. 10FT MAY BE REQUIRED FOR ANY |
| | OPENINGS INTO BUILDING FOR MECHANICAL VENTILATION, |
| | PLEASE SEE 3FT IS MIN FOR ELECTRICAL/WORKING |
| | CLEARANCE. |
| | PLEASE SEE 110.26, 90.7, 110.3 AND NOTES FROM OTHER |
| | TRADES. |
| | |
| | 4) NOTE: NO, SAME NOTE FOR ANY VERTICAL RUNS. |
| | |
| | ** PREVIOUS REVIEW NOTE FROM REVIEW #1** |
| | PLEASE SEE HEIGHT OF BUILDING IS NOT SHOWN; PLEASE SEE |
| | 300.19 FOR STRAIN RELIEF REQUIRED FOR CONDUCTORS ON |
| | VERTICAL RUNS. |
| | |
| | 5) NOTE:NO, PLEASE SEE THE PLANS NOW INDICATE A NEW |
| | DISCONNECT HOWEVER NO INFORMATION FOR LOCATION AND |
| | WHERE THIS IS SHOWN ON PLAN OVER VIEW IN COMPARISON TO |
| | THE MAIN ELECTRICAL ROOM. |
| | |
| | ** PREVIOUS REVIEW NOTE FROM REVIEW #1** |
| | PLEASE SEE MISSING MEANS OF DISCONNECT FOR FEEDERS FROM |
| | GEN TO BUILDING. PLEASE SHOW LOCATION OF ALL EXISTING |
| | MEANS OF DISCONNECTS FOR MAIN BLDG. |
| | PLEASE SEE 225.34, 230.72. |
| | 225.31-225.39,701.11B5, ALSO 110.27 |
| | |
| | 6) NOTE: NO, NO INFORMATION IS BEING SHOWN FOR ROUTING |
| | OF THESE CONDUITS. |
| | ARE THERE ANY CONDUITS BEING RUN IN BUILDING? |
| | ARE THERE ANY CONDUITS RUN IN EGRESS STAIRS OR ELEVATOR |
| | EQUIPMENT ROOMS? |
| | ** PLEASE PROVIDE THIS INFORMATION. |
| | |
| | ** PREVIOUS REVIEW NOTE FROM REVIEW #1** |
| | PLEASE SHOW HOW AND WHERE CONDUITS FOR FEEDERS ARE |
| | BEING RUN IN |
| | BLDG. (PLEASE KNOW, NO CONDUITS ARE PERMITTED IN |
| | EXIT/EGRESS STAIRS. |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: OK |
| | |
| | 8) NOTE: NO, THE APPLIED AMOUNT WHICH WAS INCREASED TO |
| | $25K WAS INCREASED TO $35K BASED ON THE PLANS SUBMITTED |
| | AND THE SCOPE OF WORK IN DOCUMENTATION. |
| | PLEASE KNOW BASED ON THE PLANS, DOCUMENTATION NOW |
| | PROVIDED ADDITIONAL FEES OF $222.00 IS NOW OWED. |
| | |
| | ** PREVIOUS REVIEW NOTE FROM REVIEW #1** |
| | PLEASE KNOW, DEPENDING ON THE TOTAL SCOPE OF WORK THE |
| | APPLIED VALUE IS REQUIRED TO BASED ON ALL LABOR AND |
| | MATERIALS. FBC 108.3. (EVEN OF ANY EQUIPMENT/MATERIALS |
| | ARE OWNER SUPPLIED. |
| | |
| | |
| | **** NEW NOTES **** |
| | |
| | 9) NOTE: PLEASE SEE PAPER WORK AND DOCUMENTATION NOW |
| | SUBMITTED WHICH STATES NEW MASONRY WALLS ARE TO BE |
| | INSTALLED, HOWEVER NO PLANS, SET BACKS ETC WERE |
| | SUBMITTED TO SHOW SCOPE OF WORK. PLEASE KNOW THE VALUE |
| | MAY ALSO BE ADJUSTED. |
| | |
| | 10) NOTE: PLEASE SEE LETTERS MENTIONS THIS JOB LOCATION |
| | TO BE IN PALM BEACH COUNTY JURISDICTION; HOWEVER THIS |
| | IS IN THE CITY OF WEST PALM BEACH. |
| | |
| | 12) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | |
| | 13) NOTE: PLEASE KNOW THAT BASED ON THE COORDINATION OF |
| | PLANS AND SPECS SUBMITTED, THERE MAY BE COMMENTS ONCE |
| | AGAIN ON THE FOLLOWING REVIEW WHICH HAS NOT YET BEEN |
| | MADE AT THIS TIME. |
| | |
| | 14) NOTE: PLEASE KNOW SINCE THIS IS NOW BEING STATED IN |
| | A FLOOD ZONE, A CERTIFIED ELEVATION CERTIFICATE WILL BE |
| | REQUIRED BEFORE FINAL. PLEASE SUBMIT TWO COPIES, ONE |
| | WILL BE RETAINED AND PLACED IN FILE AND THE OTHER WILL |
| | BE STAMPED FOR JOBSITE FOR FINAL INSPECTION. THIS IS |
| | NOT REQUIRED AT THIS TIME AND IS ONLY BEING NOTED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-01-28 19:02:14 | 2007-01-28 19:02:14 |
| | |
| | IN ELEC FOR REVIEW |
| | NOTES TO FOLLOW. WILL BE IN *F* STATUS. |