Plan Review Details - Permit 06081555
Plan Review Stops For Permit 06081555
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-12-21 Cont ID  
Sent By jwitmer Date 2006-12-21 Time 10:55 Rev Time 0.77
Received By jwitmer Date 2006-12-21 Time 07:46 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-08 Cont ID  
Sent By jwitmer Date 2006-11-08 Time 16:41 Rev Time 0.00
Received By jwitmer Date 2006-11-08 Time 16:41 Sent To  
Notes
2006-11-08 16:45:08BUILDING PLAN REVIEW
 PERMIT: 06100696UNIT# 1
 06100693UNIT# 2
 06100695UNIT# 3
 06081555UNIT# 4
 ADD: 255 EVERNIA ST
 UNITS MU1-MU4
 CONT: INPROSFL, INC
 TEL: (954)2020500
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) COMPLIED.
  
 3)2ND REQUEST,SINCE EACH UNIT WILL REQUIRE ITS OWN
 PERMIT APPLICATION,A NOTICE OF
 COMMENCEMENT WILL ALSO NEED TO BE
 RECORDED AT THE CLERK OF THE COURT.
 FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6A) COMPLIED.
  
 6B)2ND REQUEST, USE AND OCCUPANCY, IN ACCORDANCE WITH
 THE PROVISIONS OF SECTION 302.1.FBC.
  
 6C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601. PLANS INDICATE TYPE V-PROTECTED TABLE 500,
 SEE THE HEIGHT AND AREA REQUIREMENTS TABLE 503, THIS IS
 FOR THE ENTIRE BLDG, HIGHRISE!!!!!
  
 6D)TO BE DETERMINED @ TENANT BUILD OUT.
  
 6E) COMPLIED.
  
 6F) COMPLIED.
  
 7)2ND REQUEST, THE STRUCTURAL SHEETS DO
 NOT PROVIDE THE WIND DESIGN PERAMETERS
 THATWILLIAM COOK P.E. DESIGNED TOO.
 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 PLEASE PROVIDE THE POSITIVE/ NEGATIVE PRESSURESFOR
 BOTH ZONE 4 & ZONE 5, INDICATE THESE ZONES ON THE
 PLANS.
  
 8) COMPLIED.
  
 9) COMPLIED.
  
 10) STOREFRONT PLANS AND CALCULATIONS ARE FOR ZONE 4,
 ALSO SHOW CALCULATIONS AND LOCATION FOR END ZONES (ZONE
 5).
  
 11) COMPLIED.
  
 12) COMPLIED.
  
 13) 2ND REQUEST, THE DESIGNER OF RECORD REVIEWED THIS
 PRODUCT FOR ZONE 4, WITH THE
 NEW CALCULATIONS FOR ZONE# 5, THE PRESSURES SHALL BE
 GREATER AND REQUIRE ADDITIONAL
 SUPPORTS.
 PLEASE HIGHLIGHT IN THE REPORT WHICH ANCHORING SYSTEM
 TO BE USED, MULLIONS AND GLASS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-05 Cont ID  
Sent By jwitmer Date 2006-09-05 Time 09:12 Rev Time 3.33
Received By jwitmer Date 2006-09-05 Time 09:12 Sent To  
Notes
2006-09-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06081555
 ADD: 255 EVERNIA ST
 UNITS MU1-MU4
 CONT: INPROSFL, INC
 TEL: (954)2020500
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) 106.1.2* ADDITIONAL INFORMATION
 REQUIRED. IT APPEARS THAT A PERMIT TO
 SUBDIVIDE A SINGLE SPACE INTO 4 SEPERATE
 TENANT SPACES HAS BEEN APPLIED FOR.
 SINCE THESE ARE CONDO UNITS WHICH HAVE
 SEPERATE PROPERTY CONTROL NUMBERS &
 OWNERS, SEPERATE PERMIT APPLICATIONS
 SHALL BE APPLIED FOR, FOR EACH UNIT.
 NOTE ALSO THE PERMIT APPLICATION
 APPLIED FOR NEEDS TO CORRECT THE
 PROPERTY CONTROL NUMBER FOR THE UNIT FOR
 WHICH IT WILL APPLY FOR PERMIT.
  
 3) SINCE EACH UNIT WILL REQUIRE ITS OWN
 PERMIT APPLICATION,A NOTICE OF
 COMMENCEMENT WILL ALSO NEED TO BE
 RECORDED AT THE CLERK OF THE COURT.
 FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 4) BROMLEY COOK ENGINEERING, INC. IS
 MISSING THEIR CERTIFICATE OF
 AUTHORIZATION:471.023 F.S.
 CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF
 AN ENGINEER PRACTICING UNDER A
 FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE
 OF AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 5) WILLIAM D. COOK P.E. PLEASE PROVIDE A
 NOTIRIZED LETTER TO THIS OFFICE STATING
 AND SIGNING YOUR LEGAL SIGNATURE. THIS
 LEGAL SIGNATURE TO BE USED ON PLANS.
 FL S S 117.05.
  
 6) PLANS ARE MISSING:
 ) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 7) WIND REQUIREMENTS MISSING:
 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 8) SHEET S-1 INDICATES BEHIND THE NEWLY
 CREATED SUITES, A COMMON AREA, WHAT IS
 THIS AREA TO BE USED FOR?
  
 9) THE LEFT OF THE SHEET S-1 A STAIR
 ENCLOSURE IS PRESENT, THIS APPEARS TO BE
  
 ONE OF THE EGRESS STAIRS REQUIRING A 2HR
 RATED ASSEMBLY TO THE EXTERIOR OF THE
 BUILDING, PLANS ONLY INDICATE A 1 HR
 TENANT SEPERATION.1019.1.
  
 10) STOREFRONT PLANS SHEET 1/3 HAVE
 WHITE OUT AND HAND WRITTEN INFORMATION
 ON PLANS. 104.2.1.3 THE BUILDING
 OFFICIAL MAY SET STANDARDS THROUGH
 DEPARTMENTAL POLICY STANDARDS FOR PLANS
 AND SPRCIFICA TIONS. "NO WHITE OUT".
  
 11) INDICATE ON THE PERMIT APPLICATION
 IF THESE PLANS ARE FOR TENANT SEPERATION
 WALLS, NOT A TENANT BUILD OUT.
  
 12) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 13)W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2006-10-27 Cont ID  
Sent By dpalmer Date 2006-10-27 Time 17:48 Rev Time 0.00
Received By dpalmer Date 2006-10-27 Time 17:42 Sent To  
Notes
2006-10-27 17:50:07NO ELECTRICAL IN SCOPE, ALL EXIT EM LTS EXISTING, IF
 REQUIRED BY FIRE MARSHAL'S OFFICE, PLANS WILL BE
 REQUIRED.
 LS 1015.8, 7.9

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-27 Cont ID  
Sent By dpalmer Date 2006-08-27 Time 13:31 Rev Time 0.00
Received By dpalmer Date 2006-08-27 Time 13:31 Sent To  
Notes
2006-08-27 00:00:00***** UNSAT *****
  
 1) NOTE: PLEASE VERIFY IF THERE ARE ANY
 EXISTING ORNEW ELECTRICAL BEING
 PROVIDE TO FEED NEW TENANTS/SPACES.
 PLEASE KNOW MIN EGRESS LIGHTING IS GOING
 TO BE REQUIRED FOR NEW SPACES AND EGRESS
 HALLS.
 THIS MIN LIGHTING EVEN IF FED FROM
 EXISTING HOUSE SERVICE IS REQUIRED AT
 THIS TIME.
 PLEASE ALSO SEE FIRE REVIEW COMMENTS FOR
 THIS.
 NFPA-101 2003, 7.8, 7.9
 PLEASE SEE 700.12E FOR CIRCUITING PER
 NFPA-70 2002
  
 2) NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION REQUIRED ON TITLE BLOCKS PER
 FAC 61G15-23.002 AND FS 471.023.
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER.
  
 3) NOTE: PLEASE SEE PLANS MAY NOT
 CONTAIN HAND WRITTEN INFORMATION OR
 WHITE-OUT OF ANY KIND ON PLANS WHICH ARE
 SIGNED, DATED AND SEALED BY AN ENGINEER.
 FS 471.023
  
 4) NOTE: PLEASE SEE PLANS APPEAR TO BE
 SIGNED WITH SOME SORTOF INITIAL(S). IF
 INDEEDTHE IS THE LEGAL SIGNATURE OF
 THE ENGINEER PLEASE SUBMIT A LETTER
 WHICH STATES THIS AS LEGAL SIGNATURE,
 LETTER TO BE SIGNED, DATED AND SEALED
 ALSO IS REQUIRED TO BE NOTARIZED
 PROPERLY PER FS 117.05
  
 5) NOTE: PLEASE BE SURE PLANS REFLECT
 ALL THE CURRENT CODE S IN EFFECT FOR
 DESIGN.
 2004 FBC , 2002 NFPA-70, 2003 NFPA-101
 (MIN) PLEASE SEE ANY OHER CODES WHICH
 MAY BE REQUIRED FROM OTHER
 TRADES/REVIEWS.
  
 6) NOTE: PLEASE SEE THE NOTICE OF
 COMMENCMENT SUBMITTED WAS NOT RECORDED.
 PLEASE SEE FS 713.13(2).
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-12-21 Cont ID  
Sent By mawillia Date 2006-12-21 Time 11:35 Rev Time 0.00
Received By mawillia Date 2006-12-21 Time 11:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-11-13 Cont ID  
Sent By mawillia Date 2006-11-13 Time 09:56 Rev Time 0.00
Received By mawillia Date 2006-11-13 Time 09:56 Sent To  
Notes
2006-11-13 10:06:55*****UNSAT*****
  
  
  
 THIS WRITER WAS UNABLE TO DETERMINE IF THE PREVIOUS
 FIRE PLAN REVIEW COMMENTS OF 09/22/2006 WERE ADDRESSED.
 TO EXPEDITE PLAN REVIEW PROCESS, INDICATE HOW EACH
 ITEM/COMMENT WAS ADDRESSED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-22 Cont ID  
Sent By mwennerg Date 2006-09-22 Time 13:57 Rev Time 0.00
Received By mwennerg Date 2006-09-22 Time 13:57 Sent To  
Notes
2006-09-22 00:00:00***DENIED***
  
 1) PLEASE PROVIDE ADOPTED EDITIONS OF
 REFERENCED CODES. LIFE SAFETY SHALL
 COMPLY WITH NFPA 101, 2003 EDITION.
  
 2) PLEASE SHOW LOCATIONS OF REQUIRED
 EXIT SIGN AND EMERGENCY LIGHTING.
  
 3) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED FOR EACH SPACE.
  
 4) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-01 Cont ID  
Sent By adarroug Date 2006-12-01 Time 11:23 Rev Time 0.00
Received By adarroug Date 2006-12-01 Time 11:23 Sent To  
Notes
2006-12-18 14:09:02TO "COMM" BD#60
2006-12-01 11:24:17WAITIING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-20 Cont ID  
Sent By adarroug Date 2006-10-20 Time 17:00 Rev Time 0.00
Received By adarroug Date 2006-10-20 Time 17:00 Sent To  
Notes
2006-10-24 16:55:03TO "COMM" BD#52
2006-10-20 17:00:53WAITING FOR "COMM' BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-22 Cont ID  
Sent By mwennerg Date 2006-09-22 Time 14:09 Rev Time 0.00
Received By mwennerg Date 2006-08-17 Time 16:51 Sent To  
Notes
2006-08-24 00:00:00TO "COMM"#44
2006-08-17 00:00:00WAITING FOR "COMM" BD

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-09-06 Cont ID  
Sent By kstevens Date 2006-09-06 Time 18:14 Rev Time 0.00
Received By kstevens Date 2006-09-06 Time 18:14 Sent To  
Notes
2006-09-06 00:00:00TENANT SEPARATION ONLY, NO DEMOLITION OF
 PLUMBING SYSTEMS, PIPING ETC. SEPARATE
 PLUMBING PERMITS REQUIRED FOR EACH SPACE
 FOR BUILD-OUT. SEPARATE FACILITIES
 REQUIRED FOR EACH SPACE.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-10-25 Cont ID  
Sent By mflis Date 2006-10-25 Time 09:47 Rev Time 0.00
Received By mflis Date 2006-10-25 Time 09:47 Sent To  
Notes
2006-10-25 09:48:07REVIEWED-
  
 THESE GROUND FLOOR SPACES WILL BE FOR COMMERCIAL USES
 ONLY.
  
 -MJF

Review Stop Z ZONING
Rev No 1 Status F Date 2006-09-08 Cont ID  
Sent By mflis Date 2006-09-08 Time 11:00 Rev Time 0.00
Received By mflis Date 2006-09-08 Time 11:00 Sent To  
Notes
2006-09-08 00:00:001. PLEASE PROVIDE KEY PLAN IDENTIFYING
 LIMITS OF WORK. PLAN DOES NOT SHOW WHERE
 IN EXISTING BUILDING THESE RENOVATIONS
 WILL OCCUR (NO NORTH ARROW - REVIEW
 CANNOT ORIENT).
  
 2. PLEASE PROVIDE EXISTING FLOOR PLAN
 FOR COMPARISON TO MODIFICATIONS. ARE
 THERE NO DIVIDING WALLS CURRENTLY
 BETWEEN THESE LEASE SPACES? PERMIT
 INDICATES FOUR UNITS WITH SEPARATE PCNS.
  
 3. ANY NEWLY CREATED LEASE SPACES WILL
 BE FOR COMMERCIAL USE ONLY.
  
 -MATTHEW J. FLIS - 822-1445