| 2006-09-05 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 06081555 |
| | ADD: 255 EVERNIA ST |
| | UNITS MU1-MU4 |
| | CONT: INPROSFL, INC |
| | TEL: (954)2020500 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) 106.1.2* ADDITIONAL INFORMATION |
| | REQUIRED. IT APPEARS THAT A PERMIT TO |
| | SUBDIVIDE A SINGLE SPACE INTO 4 SEPERATE |
| | TENANT SPACES HAS BEEN APPLIED FOR. |
| | SINCE THESE ARE CONDO UNITS WHICH HAVE |
| | SEPERATE PROPERTY CONTROL NUMBERS & |
| | OWNERS, SEPERATE PERMIT APPLICATIONS |
| | SHALL BE APPLIED FOR, FOR EACH UNIT. |
| | NOTE ALSO THE PERMIT APPLICATION |
| | APPLIED FOR NEEDS TO CORRECT THE |
| | PROPERTY CONTROL NUMBER FOR THE UNIT FOR |
| | WHICH IT WILL APPLY FOR PERMIT. |
| | |
| | 3) SINCE EACH UNIT WILL REQUIRE ITS OWN |
| | PERMIT APPLICATION,A NOTICE OF |
| | COMMENCEMENT WILL ALSO NEED TO BE |
| | RECORDED AT THE CLERK OF THE COURT. |
| | FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 4) BROMLEY COOK ENGINEERING, INC. IS |
| | MISSING THEIR CERTIFICATE OF |
| | AUTHORIZATION:471.023 F.S. |
| | CERTIFICATE OF AUTHORIZATION.THE TITLE |
| | BLOCK FOR ANY SHEET BEARING THE NAME OF |
| | AN ENGINEER PRACTICING UNDER A |
| | FICTITIOUS NAME, A CORPORATION, OR A |
| | PARTNERSHIP, OFFERING ENGINEERING |
| | SERVICES, SHALL INCLUDE THE CERTIFICATE |
| | OF AUTHORIZATION NUMBER. |
| | ADD THE NUMBER TO EACH SHEET.THIS MAY |
| | BE ADDED BY HAND. |
| | |
| | 5) WILLIAM D. COOK P.E. PLEASE PROVIDE A |
| | NOTIRIZED LETTER TO THIS OFFICE STATING |
| | AND SIGNING YOUR LEGAL SIGNATURE. THIS |
| | LEGAL SIGNATURE TO BE USED ON PLANS. |
| | FL S S 117.05. |
| | |
| | 6) PLANS ARE MISSING: |
| | ) 110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | |
| | 7) WIND REQUIREMENTS MISSING: |
| | 2004 FL. BLD CODE 1603.1.4 THE |
| | FOLLOWING INFORMATION RELATED TO WIND |
| | SHALL BE SHOWN ON THE CONSTRUCTION |
| | DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 8) SHEET S-1 INDICATES BEHIND THE NEWLY |
| | CREATED SUITES, A COMMON AREA, WHAT IS |
| | THIS AREA TO BE USED FOR? |
| | |
| | 9) THE LEFT OF THE SHEET S-1 A STAIR |
| | ENCLOSURE IS PRESENT, THIS APPEARS TO BE |
| | |
| | ONE OF THE EGRESS STAIRS REQUIRING A 2HR |
| | RATED ASSEMBLY TO THE EXTERIOR OF THE |
| | BUILDING, PLANS ONLY INDICATE A 1 HR |
| | TENANT SEPERATION.1019.1. |
| | |
| | 10) STOREFRONT PLANS SHEET 1/3 HAVE |
| | WHITE OUT AND HAND WRITTEN INFORMATION |
| | ON PLANS. 104.2.1.3 THE BUILDING |
| | OFFICIAL MAY SET STANDARDS THROUGH |
| | DEPARTMENTAL POLICY STANDARDS FOR PLANS |
| | AND SPRCIFICA TIONS. "NO WHITE OUT". |
| | |
| | 11) INDICATE ON THE PERMIT APPLICATION |
| | IF THESE PLANS ARE FOR TENANT SEPERATION |
| | WALLS, NOT A TENANT BUILD OUT. |
| | |
| | 12) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 13)W P B ADMINISTRTIVE CODE 106.3.3* |
| | PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |