| 2006-08-24 00:00:00 | BUILDING REVIEW 2ND CHECKLIST: |
| | 1- FLAT ROOF SYSTEM WITH INSULATION |
| | PRODUCT APPROVAL SUBMITTED (NOA NO |
| | 03-0501.09): |
| | A) CLEARLY IDENTIFY APPROVED ASSEMBLY |
| | TO BE INSTALLED AS REQUIRED BY CITY |
| | POLICY FOR RE-ROOFING PERMITS. SEE |
| | ATTACHED COPY. |
| | |
| | B) IF SELECTED APPROVED ASSEMBLY IS |
| | LIMITED BY GENERAL LIMITATION #7, THEN, |
| | PROVIDE COMPLETE RAS 117 CALCULATIONS. |
| | CALCULATIONS SHALL BE DONE AND SIGNED |
| | AND SEALED BY ANY ONE OF THE |
| | PROFESSIONALS LISTED IN THE GENERAL |
| | LIMITATION #7. |
| | |
| | C) IF SELECTED APPROVED ASSEMBLY IS |
| | LIMITED BY GENERAL LIMITATION #9, THEN |
| | THIS ASSEMBLY CAN'T BE USED IN THIS |
| | LOCATION. IT DOESN'T MEET THE DESIGN |
| | PRESSURES FOR THIS LOCATION. SEE TABLE |
| | 1609.6B FBC 2004. |
| | |
| | 2- PRODUCT APPROVAL NOA NO 06-0417.06 IS |
| | A COAT ROOF MAINTENANCE SYSTEM. IT NEEDS |
| | TO BE INSTALLED ON ANY OF THE SUBSTRATES |
| | IDENTIFYIED IN THE PRODUCT APPROVAL. |
| | CLARIFY IF THIS SYSTEM IS GOING TO BE |
| | INSTALLED OVER THE NEW FLAT ROOF |
| | SYSTEM?. SEE NOA FOR APPROVED SUBSTRATES |
| | TO VERIFY COMPLIANCE WITH THIS PRODUCT |
| | APPROVAL. |
| | |
| | 3- NOTICE OF COMMENCEMENT DOESN'T |
| | PROVIDE THE GENERAL DESCRIPTION OF THE |
| | IMPROVEMENTS. PROVIDE SUCH INFORMATION |
| | AND RE-RECORD NOTICE OF COMMENCEMENT. |
| | |
| | 4- NEW PERMIT APPLICATION SUBMITTED HAS |
| | THE SIGNATURE OF THE OWNER AND THE |
| | CONTRACTOR ON THE WRONG PLACE. REVISE AS |
| | REQUIRED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |