Plan Review Details - Permit 06081415
Plan Review Stops For Permit 06081415
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-10-10 Cont ID  
Sent By jgomez Date 2006-10-10 Time 17:09 Rev Time 1.00
Received By jgomez Date 2006-10-10 Time 17:08 Sent To PC
Notes
2006-10-10 17:10:47TALKED TO CONTRACTOR. NEED RE-RECORDED NOC WITH
 COMPLETE DESCRIPTION OF WORK INFORMATION. APPLICATION
 UNDER "D".

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-24 Cont ID  
Sent By jgomez Date 2006-08-24 Time 13:32 Rev Time 0.50
Received By jgomez Date 2006-08-24 Time 13:31 Sent To  
Notes
2006-08-24 00:00:00BUILDING REVIEW 2ND CHECKLIST:
 1- FLAT ROOF SYSTEM WITH INSULATION
 PRODUCT APPROVAL SUBMITTED (NOA NO
 03-0501.09):
 A) CLEARLY IDENTIFY APPROVED ASSEMBLY
 TO BE INSTALLED AS REQUIRED BY CITY
 POLICY FOR RE-ROOFING PERMITS. SEE
 ATTACHED COPY.
  
 B) IF SELECTED APPROVED ASSEMBLY IS
 LIMITED BY GENERAL LIMITATION #7, THEN,
 PROVIDE COMPLETE RAS 117 CALCULATIONS.
 CALCULATIONS SHALL BE DONE AND SIGNED
 AND SEALED BY ANY ONE OF THE
 PROFESSIONALS LISTED IN THE GENERAL
 LIMITATION #7.
  
 C) IF SELECTED APPROVED ASSEMBLY IS
 LIMITED BY GENERAL LIMITATION #9, THEN
 THIS ASSEMBLY CAN'T BE USED IN THIS
 LOCATION. IT DOESN'T MEET THE DESIGN
 PRESSURES FOR THIS LOCATION. SEE TABLE
 1609.6B FBC 2004.
  
 2- PRODUCT APPROVAL NOA NO 06-0417.06 IS
 A COAT ROOF MAINTENANCE SYSTEM. IT NEEDS
 TO BE INSTALLED ON ANY OF THE SUBSTRATES
 IDENTIFYIED IN THE PRODUCT APPROVAL.
 CLARIFY IF THIS SYSTEM IS GOING TO BE
 INSTALLED OVER THE NEW FLAT ROOF
 SYSTEM?. SEE NOA FOR APPROVED SUBSTRATES
 TO VERIFY COMPLIANCE WITH THIS PRODUCT
 APPROVAL.
  
 3- NOTICE OF COMMENCEMENT DOESN'T
 PROVIDE THE GENERAL DESCRIPTION OF THE
 IMPROVEMENTS. PROVIDE SUCH INFORMATION
 AND RE-RECORD NOTICE OF COMMENCEMENT.
  
 4- NEW PERMIT APPLICATION SUBMITTED HAS
 THE SIGNATURE OF THE OWNER AND THE
 CONTRACTOR ON THE WRONG PLACE. REVISE AS
 REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-17 Cont ID  
Sent By jgomez Date 2006-08-17 Time 15:58 Rev Time 0.33
Received By jgomez Date 2006-08-17 Time 15:58 Sent To  
Notes
2006-08-17 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- FLAT ROOF TILE (NOA # 06-0201.01)
 CAN'T BE INSTALLED IN FLAT ROOFS. SEE
 PRODUCT APPROVAL FOR MINIMUM ROOF SLOPE.
  
 2- CLEARLY SPECIFY WHICH FLAT ROOF
 SYSTEM IS GOING TO BE INSTALLED AND
 PROVIDE ALL INFORMATION AS REQUIRED BY
 CITY POLICY FOR RE-ROOFING PERMITS.SEE
 ATTACHED COPY OF CITY POLICY AND PROVIDE
 ALL THE INFORMATION..
  
 3- THERE ARE 2 DIFFERENT PRODUCT
 APPROVALS SUBMITTED FOR FLAT ROOF.
 PROVIDE COMPLETE INFORMATION ONLY FOR
 PRODUCT TO BE INSTALLED.
  
 4- FLAT ROOF REQUIRES NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS. SEE TABLE
 1609.6B FBC 2004. PROVIDE ALL
 INFORMATION AS REQUIRED BY GENERAL
 LIMITATION #7.
  
 ***NOTE: IF FLAT ROOF ASSEMBLY IS
 LIMITED BY GENERAL LIMITATION #9, THEN
 IT CAN'T BE USED BECAUSE ADDITIONAL NAIL
 ENHANCING IS NOT ALLOWED.
  
 5- PROVIDE RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7.
 CALCULATIONS TO BE PERFORMED BY PEOPLE
 LISTED IN GENERAL LIMITATION #7. SEE
 GENERAL LIMITATIONS ON LAST PAGE OF DADE
 COUNTY NOA SUBMITTED.
  
 6- REVISE PERMIT APPLICATION AND NOTICE
 OF COMMENCEMENT. CORRECT FBC CHAPTER FOR
 ROOFS IS CHAPTER 15 FBC 2004, NOT
 CHAPTER 9. REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712