Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-24 Cont ID  
Sent By amorse Date 2006-08-24 Time 07:13 Rev Time 0.00
Received By amorse Date 2006-08-24 Time 07:13 Sent To PC
Notes
2006-08-24 00:00:00 
  
 DENIED
  
 1) PRODUCT APPROVALS FOR MODIFIED SHALL
 CONTAIN THE APPROVED MATERIAL PAGES 2-9
 OF PRODUCT APPROVAL
  
 2) IF THIS IS A RECOVER IT SHALL FIRST
 BE PRE-INSPECTED PLEASE CONTACT KEN
 CONRAD AT 805-6666
  
 3) THE SYSTEM THAT WAS CHOSEN HAS A
 DESIGN PRESSURE OF -45 PSF (IN OUR
 JURISTICTION THE WIND LOADS OF 140 MPH
 EXP B REQUIRE THAT THE EDGE ZONES MEET
 OR EXCEED -59.2 AND THE CORNER ZONES
 MEET OR EXCEED -89.0) THE SYSTEM CHOSEN
 IS ALSO A LIMITATION 9 WHICH CANNOT BE
 ENHANCED
  
 4) WHEN MIXED ROOFING IS USED SUCH AS
 ROOF TILE AND BUR SPECIFY HOW MANY
 SQUARES OF EACH TYPE OF ROOF
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716