Plan Review Details - Permit 06081216
Plan Review Stops For Permit 06081216
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-03-02 Cont ID  
Sent By shill Date 2007-03-02 Time 09:29 Rev Time 0.00
Received By shill Date 2007-03-02 Time 09:29 Sent To  
Notes
2007-03-02 11:04:37****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ITEMS FROM PREVIOUS LIST.ALL CORRECTIONS ARE TO BE
 INCORPORATED INTO THE PLAN BY THE DESIGNER OF RECORD.
  
  
 1.)PROVIDE INFORMATION (CODE SUMMARY)
 IN REGARDS TO THE EXISTING BUILDING;
 BUILDING TYPE FBC6, AREA FBC5.IS THIS
 AREA A TENANT SPACE OR THE ENTIRE
 BUILDING?PROVIDE OCCUPANCY INFORMATION
 FBC3 AND FBC4, FOR BOTH THIS SPACE AND
 ADJACENT SPACES IF APPLICABLE, OCCUPANCY
 OR TENANT SEPARATIONS IF REQUIRED.IS
 THE BUILDING SPRINKLERED OR UNSPRINKLERED?
  
 2.)WHAT IS THE CURRENT OCCUPANCY
 CLASSIFICATION?IS THIS A CHANGE OF
 OCCUPANCY?
  
 3.)ADDRESSED.
  
 4.)PROVIDE DIMENSIONS FOR THE EGRESS
 DOOR, FBC1008, FBC11-4.13.
  
 5.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS,
 FS713.13.
  
 6.)ALL INFORMATION REQUIRED BY
 FAC61G15-23.002 IS REQUIRED (ENGINEER'S INFORMATION) ON
 EACH SHEET.
  
 7.)ARE THE PAINTS USED FLAMMABLE?SEE
 FBC416, SHOW COMPLIANCE WITH 416.2 AND 416.3, FBC TABLE
 307.7(1) (SHOW QUANTITIES STORED).MSDS SHEETS WERE
 SUBMITTED, PLEASE ADDRESS QUANITITES ON THE PLAN.ALSO
 ADDRESS MATERIAL AND QUANTITY USED IN CLEANING OF SPRAY
 EQUIPMENT; FLAMMABILITY, HOW AND WHERE IT WILL BE
 STORED AND IN WHAT QUANITITY.
  
 8.)SEE FIRST AID REQUIREMENT ON THE MSDS.EYE WASH
 REQUIRED.
  
 9.)SEE ATTACHED FS553.80(2)(B).
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-03 Cont ID  
Sent By shill Date 2007-01-03 Time 14:13 Rev Time 0.00
Received By shill Date 2007-01-03 Time 14:13 Sent To  
Notes
2007-01-03 14:17:10****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 ITEMS FROM PREVIOUS LIST.ALL CORRECTIONS ARE TO BE
 INCORPORATED INTO THE PLAN BY THE DESIGNER OF RECORD.
  
 1.)PROVIDE INFORMATION (CODE SUMMARY)
 IN REGARDS TO THE EXISTING BUILDING;
 BUILDING TYPE FBC6, AREA FBC5.IS THIS
 AREA A TENANT SPACE OR THE ENTIRE
 BUILDING?PROVIDE OCCUPANCY INFORMATION
 FBC3 AND FBC4, FOR BOTH THIS SPACE AND
 ADJACENT SPACES IF APPLICABLE, OCCUPANCY
 OR TENANT SEPARATIONS IF REQUIRED.IS
 THE BUILDING SPRINKLERED OR UNSPRINKLERED?
  
 2.)WHAT IS THE CURRENT OCCUPANCY
 CLASSIFICATION?IS THIS A CHANGE OF
 OCCUPANCY?
  
 3.)PROVIDE SPECIFICATIONS FOR THE FIRE PROTECTION
 SYSTEM.
  
 4.)PROVIDE DIMENSIONS FOR THE EGRESS
 DOOR, FBC1008, FBC11-4.13.
  
 5.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS,
 FS713.13.
  
 6.)ALL INFORMATION REQUIRED BY
 FAC61G15-23.002 IS REQUIRED (ENGINEER'S INFORMATION) ON
 EACH SHEET.
  
 7.)ARE THE PAINTS USED FLAMMABLE?SEE
 FBC416, SHOW COMPLIANCE WITH 416.2 AND 416.3.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-11 Cont ID  
Sent By shill Date 2006-09-11 Time 16:34 Rev Time 0.00
Received By shill Date 2006-09-11 Time 15:03 Sent To  
Notes
2006-09-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)PROVIDE INFORMATION (CODE SUMMARY)
 IN REGARDS TO THE EXISTING BUILDING;
 BUILDING TYPE FBC6, AREA FBC5.IS THIS
 AREA A TENANT SPACE OR THE ENTIRE
 BUILDING?PROVIDE OCCUPANCY INFORMATION
 FBC3 AND FBC4, FOR BOTH THIS SPACE AND
 ADJACENT SPACES IF APPLICABLE, OCCUPANCY
 OR TENANT SEPARATIONS IF REQUIRED.IS
 THE BUILDING SPRINKLED OR UNSPRINKLED?
  
 2.)WHAT IS THE CURRENT OCCUPANCY
 CLASSIFICATION?IS THIS A CHANGE OF
 OCCUPANCY?
  
 3.)PROVIDE SPECIFICATIONS FOR THE FIRE
 PROTECTION SYSTEM.
  
 4.)PROVIDE DIMENSIONS FOR THE EGRESS
 DOOR, FBC1008, FBC11-4.13.
  
 5.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS,
 FS713.13.
  
 6.)ALL INFORMATION REQUIRED BY
 FAC61G15-23.002 IS REQUIRED (ENGINEER?S
 INFORMATION) ON EACH SHEET.
  
 7.)ARE THE PAINTS USED FLAMMABLE?SEE
 FBC416, SHOW COMPLIANCE WITH 416.2 AND
 416.3.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-01-29 Cont ID  
Sent By btrobaug Date 2007-01-29 Time 15:35 Rev Time 1.00
Received By btrobaug Date 2007-01-29 Time 12:06 Sent To  
Notes
2007-01-29 14:03:27 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW PRIOR TO ROUGH
 INSPECTION.
  
 1} PLEASE LOCATE THE "METER TRANSFORMER" SHOWN ON THE
 RISER , ON THE PLAN. CLARIFY THAT THIS IS ONE PIECE OF
 EQUIPMENT?
  
 2} IF IN FACT THE ENGINEEER MEANT THERE IS A
 TRANSFORMER AFTER THE METER IN THIS SYSTEM, INDICATE
 THE PRIMARY AND SECONDARY OCP. 240.16(D) AND 450.4. AND
 KVA.
  
 3} THE RISER LISTS A 200 AMP. 120/240VOLT,MLO PANEL
 MARKED "B". LOCATE THE REQUIRED DISCONNECTING MEANS FOR
 THAT PANEL PER 230.70(A)(1). THE PANEL SHOWN ON THE
 PLAN IS RATED 120/208. PLEASE CORRELATE PER ARTICLE
 408.16.
  
 4} THERE ARE 5 #12 CONDUCTORS FEEDING THE "BOOTH
 CONTROLLER" THE PANEL SCHEDULE SHOWS 6 CIRCUITS BEING
 USED.
  
 5} LOCATE THE BOOTH CONTROLLER ON THE BOOTH THIS WAS
 NOTE #1 ON THE PREVIOUS REVIEW, AND WAS STATED- 1} THE
 ELECTRICAL CONNECTION TO THE
 BOOTH IS NOT SHOWN. PLEASE SHOW THE
 LOCATION OF CONNECTIONS AND COMPLIANCE
 WITH 516 NEC AND NFPA-33, CHAPTER 6.
  
 6} THE BRANCH CIRCUITS IN THE PANEL SCHEDULE ARE ALL
 LISTED ON "A" PHASE, PLEASE CORRECT.
  
 7} SHEET 1 OF 4 HAS THE LOCATION OF THE PROJECT ON THE
 WRONG PROPERTY.
  
 8} THE DESIGNER OF RECORD MUST COMPLY WITH FS 471.025,
 ALL SHEETS. ALSO NOTE THE DATE THE PLANS WERE SEALED IS
 NOT CLEAR, ALL SHEETS.
  
 9} SHEET #1 LISTS "LIGHTS ON ELECTRIC INC." AS THE
 ELECTRICAL CONTRACTOR. THE CONTRACTOR THAT APPLIED FOR
 AN ELECTRICALPERMITFOR THIS WORK IS "VAL ELECTRIC".
 THERE SEEMS TO BE ALOT OF CONFUSION WITH THIS PROJECT.
 PLEASE CONSULT THE GENERAL CONTRACTOR TO CLEAR THESE
 ISSUES UP.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-09 Cont ID  
Sent By btrobaug Date 2007-01-09 Time 08:59 Rev Time 1.00
Received By btrobaug Date 2007-01-05 Time 12:32 Sent To  
Notes
2007-01-09 08:33:02 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW. THIS IS THE SECOND REQUEST FOR THESE COMMENTS.
 THE CHANGES TO THE PLAN MUST BE DONE BY THE DESIGNER OF
 RECORD PER 471 FS.
  
 1} THE ELECTRICAL CONNECTION TO THE
 BOOTH IS NOT SHOWN. PLEASE SHOW THE
 LOCATION OF CONNECTIONS AND COMPLIANCE
 WITH 516 NEC AND NFPA-33, CHAPTER 6.
  
 2} PLEASE INDICATE PANEL LOCATION,
 DESIGNATION, AND BRANCH CIRCUIT NUMBERS
 FEEDING THE BOOTH.
  
 3} THE REFERENCE TO THE 2003 NEC IN THE
 NOTES IS INCORRECT AND SHOULD READ 2002,
 WHICH IS THE ONE ADOPTED BY STATUTE.
  
 4} THE REFERENCE TO SBCCI FL FIRE
 PREVENTION CODE, IS ALSO OUTDATED AND NO
 LONGER IN USE.
 PLEASE ELIMINATE ALL REFERENCES THAT DO
 NOT APPLY, AND USE THE CORRECT CODE
 REFERENCED BY THE 2004 FBC, IN THE
 NOTES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-06 Cont ID  
Sent By btrobaug Date 2006-09-06 Time 11:41 Rev Time 1.00
Received By btrobaug Date 2006-09-06 Time 06:49 Sent To  
Notes
2006-09-06 00:00:00 
  
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ELECTRICAL CONNECTION TO THE
 BOOTH IS NOT SHOWN. PLEASE SHOW THE
 LOCATION OF CONNECTIONS AND COMPLIANCE
 WITH 516 NEC AND NFPA-33, CHAPTER 6.
  
 2} PLEASE INDICATE PANEL LOCATION,
 DESIGNATION, AND BRANCH CIRCUIT NUMBERS
 FEEDING THE BOOTH.
  
 3} THE REFERENCE TO THE 2003 NEC IN THE
 NOTES IS INCORRECT AND SHOULD READ 2002,
 WHICH IS THE ONE ADOPTED BY STATUTE.
  
 4} THE REFERENCE TO SBCCI FL FIRE
 PREVENTION CODE, IS ALSO OUTDATED AND NO
 LONGER IN USE.
 PLEASE ELIMINATE ALL REFERENCES THAT DO
 NOT APPLY, AND USE THE CORRECT CODE
 REFERENCED BY THE 2004 FBC, IN THE
 NOTES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-02-26 Cont ID  
Sent By mawillia Date 2007-02-26 Time 18:47 Rev Time 0.00
Received By mawillia Date 2007-02-26 Time 18:47 Sent To  
Notes
2007-02-26 18:56:01***PROVISO*****
  
  
 TO BE STAMPED APPROVED WHEN ALL OTHER PLAN REVIEWS HAVE
 BEEN SATISFIED

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-01-09 Cont ID  
Sent By mawillia Date 2007-01-09 Time 17:56 Rev Time 0.00
Received By mawillia Date 2007-01-09 Time 17:56 Sent To  
Notes
2007-01-09 18:00:06****DENIED*****
  
  
 COMMENTS FROM PREVIOUS FIRE PLAN REVIEW OF 09/08/2006
 STILL HAVE NOT BEEN ADDRESSED.TO EXPEDITE THE PLAN
 REVIEW PROCESS WHEN RESUBMITTING, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-08 Cont ID  
Sent By mwennerg Date 2006-09-08 Time 11:40 Rev Time 0.00
Received By mwennerg Date 2006-09-08 Time 11:40 Sent To  
Notes
2006-09-08 00:00:00***DENIED***
  
 1) PLEASE PROVIDE NOTE TO PLANS
 INDICATING HOW THE PREVENTION OF STATIC
 ELECTRICITY WILL OCCUR.
  
 2) OCCUPANT NOTIFICATION APPLIANCE IS
 REQUIRED. IF BUILDING IS PROTECTED BY
 FIRE ALARM SYSTEM, THE SPRAY BOOTH SHALL
 BE CONNECTED TO THE FIRE ALARM SYSTEM.
  
 3) PLEASE PROVIDE INFORMATION REGARDING
 WHAT TYPE OF FIRE PROTECTION SYSTEM TO
 BE USED, SPRINKLER OR DRY CHEMICAL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-24 Cont ID  
Sent By adarroug Date 2007-01-24 Time 13:45 Rev Time 0.00
Received By adarroug Date 2007-01-24 Time 13:45 Sent To  
Notes
2007-01-24 13:48:40TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-15 Cont ID  
Sent By adarroug Date 2006-12-15 Time 14:45 Rev Time 0.00
Received By adarroug Date 2006-12-15 Time 14:45 Sent To  
Notes
2007-01-03 07:43:09TO BOB SPACE #11
2006-12-15 14:45:30WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-11 Cont ID  
Sent By shill Date 2006-09-11 Time 16:39 Rev Time 0.00
Received By shill Date 2006-08-15 Time 13:50 Sent To  
Notes
2006-09-05 00:00:00TO "BOB"#13
2006-08-15 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-09-07 Cont ID  
Sent By tgordon Date 2006-09-07 Time 16:26 Rev Time 0.40
Received By tgordon Date 2006-09-07 Time 16:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-03 Cont ID  
Sent By jleech Date 2007-03-03 Time 07:11 Rev Time 0.00
Received By jleech Date 2007-03-03 Time 07:11 Sent To  
Notes
2007-03-03 07:17:18DENIED;
 AN EYE WASH STATION IS REQUIRED. SEE MATERIAL SAFETY
 DATA SHEET SECTION 4 "SKIN OR EYE CONTACT". EYE WASH
 SHOULD BE LOCATED CLOSE TO PAINT BOTH DOOR FOR EASY
 ACCESS.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695