| Plan Review Stops For Permit 06081216 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-03-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-03-02 |
Time |
09:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-03-02 |
Time |
09:29 |
Sent To |
|
|
| Notes |
| 2007-03-02 11:04:37 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC RFLORIDA BUILDING CODE 2004 | | | RESIDENTIAL | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | ITEMS FROM PREVIOUS LIST.ALL CORRECTIONS ARE TO BE | | | INCORPORATED INTO THE PLAN BY THE DESIGNER OF RECORD. | | | | | | | | | 1.)PROVIDE INFORMATION (CODE SUMMARY) | | | IN REGARDS TO THE EXISTING BUILDING; | | | BUILDING TYPE FBC6, AREA FBC5.IS THIS | | | AREA A TENANT SPACE OR THE ENTIRE | | | BUILDING?PROVIDE OCCUPANCY INFORMATION | | | FBC3 AND FBC4, FOR BOTH THIS SPACE AND | | | ADJACENT SPACES IF APPLICABLE, OCCUPANCY | | | OR TENANT SEPARATIONS IF REQUIRED.IS | | | THE BUILDING SPRINKLERED OR UNSPRINKLERED? | | | | | | 2.)WHAT IS THE CURRENT OCCUPANCY | | | CLASSIFICATION?IS THIS A CHANGE OF | | | OCCUPANCY? | | | | | | 3.)ADDRESSED. | | | | | | 4.)PROVIDE DIMENSIONS FOR THE EGRESS | | | DOOR, FBC1008, FBC11-4.13. | | | | | | 5.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS, | | | FS713.13. | | | | | | 6.)ALL INFORMATION REQUIRED BY | | | FAC61G15-23.002 IS REQUIRED (ENGINEER'S INFORMATION) ON | | | EACH SHEET. | | | | | | 7.)ARE THE PAINTS USED FLAMMABLE?SEE | | | FBC416, SHOW COMPLIANCE WITH 416.2 AND 416.3, FBC TABLE | | | 307.7(1) (SHOW QUANTITIES STORED).MSDS SHEETS WERE | | | SUBMITTED, PLEASE ADDRESS QUANITITES ON THE PLAN.ALSO | | | ADDRESS MATERIAL AND QUANTITY USED IN CLEANING OF SPRAY | | | EQUIPMENT; FLAMMABILITY, HOW AND WHERE IT WILL BE | | | STORED AND IN WHAT QUANITITY. | | | | | | 8.)SEE FIRST AID REQUIREMENT ON THE MSDS.EYE WASH | | | REQUIRED. | | | | | | 9.)SEE ATTACHED FS553.80(2)(B). | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-01-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-01-03 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-01-03 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2007-01-03 14:17:10 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC RFLORIDA BUILDING CODE 2004 | | | RESIDENTIAL | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | ITEMS FROM PREVIOUS LIST.ALL CORRECTIONS ARE TO BE | | | INCORPORATED INTO THE PLAN BY THE DESIGNER OF RECORD. | | | | | | 1.)PROVIDE INFORMATION (CODE SUMMARY) | | | IN REGARDS TO THE EXISTING BUILDING; | | | BUILDING TYPE FBC6, AREA FBC5.IS THIS | | | AREA A TENANT SPACE OR THE ENTIRE | | | BUILDING?PROVIDE OCCUPANCY INFORMATION | | | FBC3 AND FBC4, FOR BOTH THIS SPACE AND | | | ADJACENT SPACES IF APPLICABLE, OCCUPANCY | | | OR TENANT SEPARATIONS IF REQUIRED.IS | | | THE BUILDING SPRINKLERED OR UNSPRINKLERED? | | | | | | 2.)WHAT IS THE CURRENT OCCUPANCY | | | CLASSIFICATION?IS THIS A CHANGE OF | | | OCCUPANCY? | | | | | | 3.)PROVIDE SPECIFICATIONS FOR THE FIRE PROTECTION | | | SYSTEM. | | | | | | 4.)PROVIDE DIMENSIONS FOR THE EGRESS | | | DOOR, FBC1008, FBC11-4.13. | | | | | | 5.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS, | | | FS713.13. | | | | | | 6.)ALL INFORMATION REQUIRED BY | | | FAC61G15-23.002 IS REQUIRED (ENGINEER'S INFORMATION) ON | | | EACH SHEET. | | | | | | 7.)ARE THE PAINTS USED FLAMMABLE?SEE | | | FBC416, SHOW COMPLIANCE WITH 416.2 AND 416.3. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-09-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-09-11 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-09-11 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2006-09-11 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC RFLORIDA BUILDING CODE 2004 | | | RESIDENTIAL | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)PROVIDE INFORMATION (CODE SUMMARY) | | | IN REGARDS TO THE EXISTING BUILDING; | | | BUILDING TYPE FBC6, AREA FBC5.IS THIS | | | AREA A TENANT SPACE OR THE ENTIRE | | | BUILDING?PROVIDE OCCUPANCY INFORMATION | | | FBC3 AND FBC4, FOR BOTH THIS SPACE AND | | | ADJACENT SPACES IF APPLICABLE, OCCUPANCY | | | OR TENANT SEPARATIONS IF REQUIRED.IS | | | THE BUILDING SPRINKLED OR UNSPRINKLED? | | | | | | 2.)WHAT IS THE CURRENT OCCUPANCY | | | CLASSIFICATION?IS THIS A CHANGE OF | | | OCCUPANCY? | | | | | | 3.)PROVIDE SPECIFICATIONS FOR THE FIRE | | | PROTECTION SYSTEM. | | | | | | 4.)PROVIDE DIMENSIONS FOR THE EGRESS | | | DOOR, FBC1008, FBC11-4.13. | | | | | | 5.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS, | | | FS713.13. | | | | | | 6.)ALL INFORMATION REQUIRED BY | | | FAC61G15-23.002 IS REQUIRED (ENGINEER?S | | | INFORMATION) ON EACH SHEET. | | | | | | 7.)ARE THE PAINTS USED FLAMMABLE?SEE | | | FBC416, SHOW COMPLIANCE WITH 416.2 AND | | | 416.3. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-01-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-01-29 |
Time |
15:35 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2007-01-29 |
Time |
12:06 |
Sent To |
|
|
| Notes |
| 2007-01-29 14:03:27 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW PRIOR TO ROUGH | | | INSPECTION. | | | | | | 1} PLEASE LOCATE THE "METER TRANSFORMER" SHOWN ON THE | | | RISER , ON THE PLAN. CLARIFY THAT THIS IS ONE PIECE OF | | | EQUIPMENT? | | | | | | 2} IF IN FACT THE ENGINEEER MEANT THERE IS A | | | TRANSFORMER AFTER THE METER IN THIS SYSTEM, INDICATE | | | THE PRIMARY AND SECONDARY OCP. 240.16(D) AND 450.4. AND | | | KVA. | | | | | | 3} THE RISER LISTS A 200 AMP. 120/240VOLT,MLO PANEL | | | MARKED "B". LOCATE THE REQUIRED DISCONNECTING MEANS FOR | | | THAT PANEL PER 230.70(A)(1). THE PANEL SHOWN ON THE | | | PLAN IS RATED 120/208. PLEASE CORRELATE PER ARTICLE | | | 408.16. | | | | | | 4} THERE ARE 5 #12 CONDUCTORS FEEDING THE "BOOTH | | | CONTROLLER" THE PANEL SCHEDULE SHOWS 6 CIRCUITS BEING | | | USED. | | | | | | 5} LOCATE THE BOOTH CONTROLLER ON THE BOOTH THIS WAS | | | NOTE #1 ON THE PREVIOUS REVIEW, AND WAS STATED- 1} THE | | | ELECTRICAL CONNECTION TO THE | | | BOOTH IS NOT SHOWN. PLEASE SHOW THE | | | LOCATION OF CONNECTIONS AND COMPLIANCE | | | WITH 516 NEC AND NFPA-33, CHAPTER 6. | | | | | | 6} THE BRANCH CIRCUITS IN THE PANEL SCHEDULE ARE ALL | | | LISTED ON "A" PHASE, PLEASE CORRECT. | | | | | | 7} SHEET 1 OF 4 HAS THE LOCATION OF THE PROJECT ON THE | | | WRONG PROPERTY. | | | | | | 8} THE DESIGNER OF RECORD MUST COMPLY WITH FS 471.025, | | | ALL SHEETS. ALSO NOTE THE DATE THE PLANS WERE SEALED IS | | | NOT CLEAR, ALL SHEETS. | | | | | | 9} SHEET #1 LISTS "LIGHTS ON ELECTRIC INC." AS THE | | | ELECTRICAL CONTRACTOR. THE CONTRACTOR THAT APPLIED FOR | | | AN ELECTRICALPERMITFOR THIS WORK IS "VAL ELECTRIC". | | | THERE SEEMS TO BE ALOT OF CONFUSION WITH THIS PROJECT. | | | PLEASE CONSULT THE GENERAL CONTRACTOR TO CLEAR THESE | | | ISSUES UP. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-01-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-01-09 |
Time |
08:59 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2007-01-05 |
Time |
12:32 |
Sent To |
|
|
| Notes |
| 2007-01-09 08:33:02 | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. THIS IS THE SECOND REQUEST FOR THESE COMMENTS. | | | THE CHANGES TO THE PLAN MUST BE DONE BY THE DESIGNER OF | | | RECORD PER 471 FS. | | | | | | 1} THE ELECTRICAL CONNECTION TO THE | | | BOOTH IS NOT SHOWN. PLEASE SHOW THE | | | LOCATION OF CONNECTIONS AND COMPLIANCE | | | WITH 516 NEC AND NFPA-33, CHAPTER 6. | | | | | | 2} PLEASE INDICATE PANEL LOCATION, | | | DESIGNATION, AND BRANCH CIRCUIT NUMBERS | | | FEEDING THE BOOTH. | | | | | | 3} THE REFERENCE TO THE 2003 NEC IN THE | | | NOTES IS INCORRECT AND SHOULD READ 2002, | | | WHICH IS THE ONE ADOPTED BY STATUTE. | | | | | | 4} THE REFERENCE TO SBCCI FL FIRE | | | PREVENTION CODE, IS ALSO OUTDATED AND NO | | | LONGER IN USE. | | | PLEASE ELIMINATE ALL REFERENCES THAT DO | | | NOT APPLY, AND USE THE CORRECT CODE | | | REFERENCED BY THE 2004 FBC, IN THE | | | NOTES. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-09-06 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-09-06 |
Time |
11:41 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2006-09-06 |
Time |
06:49 |
Sent To |
|
|
| Notes |
| 2006-09-06 00:00:00 | | | | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} THE ELECTRICAL CONNECTION TO THE | | | BOOTH IS NOT SHOWN. PLEASE SHOW THE | | | LOCATION OF CONNECTIONS AND COMPLIANCE | | | WITH 516 NEC AND NFPA-33, CHAPTER 6. | | | | | | 2} PLEASE INDICATE PANEL LOCATION, | | | DESIGNATION, AND BRANCH CIRCUIT NUMBERS | | | FEEDING THE BOOTH. | | | | | | 3} THE REFERENCE TO THE 2003 NEC IN THE | | | NOTES IS INCORRECT AND SHOULD READ 2002, | | | WHICH IS THE ONE ADOPTED BY STATUTE. | | | | | | 4} THE REFERENCE TO SBCCI FL FIRE | | | PREVENTION CODE, IS ALSO OUTDATED AND NO | | | LONGER IN USE. | | | PLEASE ELIMINATE ALL REFERENCES THAT DO | | | NOT APPLY, AND USE THE CORRECT CODE | | | REFERENCED BY THE 2004 FBC, IN THE | | | NOTES. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-02-26 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-02-26 |
Time |
18:47 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-02-26 |
Time |
18:47 |
Sent To |
|
|
| Notes |
| 2007-02-26 18:56:01 | ***PROVISO***** | | | | | | | | | TO BE STAMPED APPROVED WHEN ALL OTHER PLAN REVIEWS HAVE | | | BEEN SATISFIED |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-01-09 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-01-09 |
Time |
17:56 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-01-09 |
Time |
17:56 |
Sent To |
|
|
| Notes |
| 2007-01-09 18:00:06 | ****DENIED***** | | | | | | | | | COMMENTS FROM PREVIOUS FIRE PLAN REVIEW OF 09/08/2006 | | | STILL HAVE NOT BEEN ADDRESSED.TO EXPEDITE THE PLAN | | | REVIEW PROCESS WHEN RESUBMITTING, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-09-08 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-09-08 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-09-08 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2006-09-08 00:00:00 | ***DENIED*** | | | | | | 1) PLEASE PROVIDE NOTE TO PLANS | | | INDICATING HOW THE PREVENTION OF STATIC | | | ELECTRICITY WILL OCCUR. | | | | | | 2) OCCUPANT NOTIFICATION APPLIANCE IS | | | REQUIRED. IF BUILDING IS PROTECTED BY | | | FIRE ALARM SYSTEM, THE SPRAY BOOTH SHALL | | | BE CONNECTED TO THE FIRE ALARM SYSTEM. | | | | | | 3) PLEASE PROVIDE INFORMATION REGARDING | | | WHAT TYPE OF FIRE PROTECTION SYSTEM TO | | | BE USED, SPRINKLER OR DRY CHEMICAL. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-01-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-24 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-24 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2007-01-24 13:48:40 | TO "BOB"#3 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-12-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-12-15 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-12-15 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2007-01-03 07:43:09 | TO BOB SPACE #11 | | 2006-12-15 14:45:30 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-09-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-09-11 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-08-15 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2006-09-05 00:00:00 | TO "BOB"#13 | | 2006-08-15 00:00:00 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2006-09-07 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-09-07 |
Time |
16:26 |
Rev Time |
0.40 |
| Received By |
tgordon |
Date |
2006-09-07 |
Time |
16:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-03-03 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-03-03 |
Time |
07:11 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-03-03 |
Time |
07:11 |
Sent To |
|
|
| Notes |
| 2007-03-03 07:17:18 | DENIED; | | | AN EYE WASH STATION IS REQUIRED. SEE MATERIAL SAFETY | | | DATA SHEET SECTION 4 "SKIN OR EYE CONTACT". EYE WASH | | | SHOULD BE LOCATED CLOSE TO PAINT BOTH DOOR FOR EASY | | | ACCESS. | | | | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|