| 2006-08-15 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED TO APPLY FOR SEPARATE BUILDING |
| | PERMIT FOR STRUCTURAL ROOF FRAMING. |
| | |
| | 2- ROOF FRAMING PLAN DOESN'T SPECIFY |
| | RAFTER SPACING. ENGINEER TO SPECIFY AS |
| | REQUIRED. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | 3- ENGINEER TO PROVIDE CALCULATED UPLIFT |
| | LOADS TO VERIFY COMPLIANCE WITH THE |
| | SPECIFIED CONNECTORS. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 4- PROVIDE GABLE END DETAIL. SHOWING HOW |
| | IS THE GABLE END WALL STRUCTURALLY |
| | CONTINUOUS BETWEEN POINTS OF LATERAL |
| | SUPPORT. SEC. 2115.1.FBC 2004. |
| | |
| | 5- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL AS REQUIRED BY DCA RULE 9B-72 |
| | FOR: |
| | A) SIMPSON STRUCTURAL CONNECTORS |
| | SPECIFIED ON PLANS. |
| | |
| | B) ROOF SHINGLES. GO TO THE DCA WEBSITE |
| | WWW.FLORIDABUILDING.ORG AND LOOK FOR |
| | FLORIDA PRODUCT APPROVAL #183 TO |
| | DOWNLOAD CURRRENT DADE COUNTY NOA THAT |
| | WAS SUBMITTED FOR APPROVAL. NEED NOA |
| | #04-0820.01 NOT 03-0219.04. |
| | |
| | 6- ENGINEER OF RECORD TO REVIEW AND |
| | APPROVE IN WRITTING ALL PRODUCT |
| | APPROVALS AS REQUIRED BY SEC. 106.3.3 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 7- ENGINEER TO PROVIDE THE CERTIFICATE |
| | OF AUTHORIZATION NUMBER FOR BUCK |
| | ENGINEERING, INC. AS REQUIRED BY F.A.C. |
| | SEC. 61G15-23.002. |
| | |
| | 8- NEED RECORDED NOTICE OF |
| | COMMENCEMENT. |
| | |
| | 9- VALUE DECLARED IN THE PERMIT |
| | APPLICATION IS TOO LOW. PROVIDE COMPLETE |
| | VALUE FOR LABOR AND MATERIALS. OR |
| | VALUATION WILL BE UPDATED AS REQUIRED BY |
| | SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 10- TYPICAL WALL SECTION: |
| | A) SPECIFY SIZE OF CONTINUOUS VENT. |
| | |
| | B) REVISE ROOF SHEATHING INSTALLATION. |
| | SEE TABLE 2304.9.1 FBC 2004. |
| | |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |