Plan Review Details - Permit 06080911
Plan Review Stops For Permit 06080911
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-02-15 Cont ID  
Sent By rmcdouga Date 2007-02-15 Time 10:42 Rev Time 0.00
Received By rmcdouga Date 2007-02-15 Time 10:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-08 Cont ID  
Sent By rmcdouga Date 2007-02-08 Time 16:40 Rev Time 0.00
Received By rmcdouga Date 2007-02-08 Time 16:32 Sent To  
Notes
2007-02-08 16:39:52DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) G2447.1 (623.1) COOKING APPLIANCES.
 COOKING APPLIANCES THAT ARE DESIGNED FOR PERMANENT
 INSTALLATION, INCLUDING RANGES, OVENS, STOVES,
 BROILERS, GRILLS , FRYERS, GRIDDLES, HOT PLATES AND
 BARBECUES, SHALL BE TESTED IN ACCORDANCE WITH ANSI
 Z21.1 OR ANSI Z21.58 AND SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS. SEE MECHANICAL COMMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-22 Cont ID  
Sent By rmcdouga Date 2006-08-22 Time 11:45 Rev Time 0.00
Received By rmcdouga Date 2006-08-22 Time 11:44 Sent To  
Notes
2006-08-22 00:00:00DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) 106.1.1* INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL.CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE
 BUILDING OFFICIAL (SEE ALSO SECTION
 106.3.5 ).
  
 3) 106.1.3* QUALITY OF PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8
 INCH SCALE UPON SUBSTANTIAL PAPER, CLOTH
 OR OTHER ACCEPTABLE MEDIUM.
  
 4) PROVIDE A FLOOR PLAN OF THE STRUCTURE
 INDICATING THE EXISTING AND PROPOSED
 LOCATIONS OF THE WASHER AND GAS CLOTHES
 DRYER. INDICATE THE LOCATION OF THE
 TANKLESS GAS WATER HEATER. SPECIFY THE
 ROOM TYPES ON THE FLOOR PLAN
 (BEDROOMS,ETC.).
  
 5) SPECIFY THE LOCATION OF THE DRYER
 EXHAUST AND GAS VENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-01-31 Cont ID  
Sent By btrobaug Date 2007-01-31 Time 14:40 Rev Time 0.50
Received By btrobaug Date 2007-01-31 Time 14:21 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-16 Cont ID  
Sent By btrobaug Date 2006-08-16 Time 18:14 Rev Time 0.33
Received By btrobaug Date 2006-08-16 Time 18:11 Sent To G
Notes
2006-08-16 00:00:00 
 NO ELECTRICAL PLANS SUBMITTED FOR
 REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-05-04 Cont ID  
Sent By mperson Date 2007-05-04 Time 15:59 Rev Time 0.45
Received By mperson Date 2007-05-04 Time 15:58 Sent To PC
Notes
2007-05-04 16:02:10REVISION: CHANGED PIPE MATERIAL, BTU LOAD AND LONGEST
 LENGTH.
  
 ****************PROVISO****************
 A} PER THE INDICATED FBC-2004 FUEL GAS, TABLES
 402.4(2) AND 402.4(20) GAS SYSTEM IS NATURAL GAS.
  
 B} PER FBC-2004 FUEL GAS, SECTION 408.4 A SEDIMENT
 TRAP IS REQUIRED FOR THE TANKLESS WATER HEATER.
  
 C} PER FBC-2004 FUEL GAS, SECTION 404.13.3AN
 INSULATED COPPER TRACER WIRE SHALL BE INSTALLED
 ADJACENT TO UNDERGROUND NONMETALLIC GAS PIPING. THE
 TRACER WIRE SIZE SHALL NOT BE LESS THAN 18 AWG AND THE
 INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2007-02-07 Cont ID  
Sent By mperson Date 2007-02-07 Time 15:51 Rev Time 0.45
Received By mperson Date 2007-02-07 Time 15:51 Sent To M
Notes
2007-02-07 16:00:46 
 ****************PROVISO****************
 A} PER FBC-2004 FUEL GAS SECTION 404.4: ALL METALLIC
 PIPING TO BE ABOVE GROUND AND PROTECTED AGAINST
 CORROSION BY PAINTING PIPE.
 B} PER FBC-2004 FUEL GAS SECTION 407.2: PIPING SHALL
 BE PROVIDED WITH SUPPORT BY STRAPPING TO WALL.
 C} PER FBC-2004 FUEL GAS SECTION 408.4: SEDIMENT TRAP
 REQUIRED FOR TANKLESS WATER HEATER.
 D} PER INDICATED TABLE 402.4(2) GAS SYSTEM IS NATURAL
 GAS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-27 Cont ID  
Sent By adarroug Date 2007-04-27 Time 11:19 Rev Time 0.00
Received By adarroug Date 2007-04-27 Time 11:19 Sent To G
Notes
2007-04-27 11:19:28TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-30 Cont ID  
Sent By adarroug Date 2007-01-30 Time 11:23 Rev Time 0.00
Received By adarroug Date 2007-01-30 Time 11:23 Sent To E
Notes
2007-01-30 11:24:20TO "BTROBAUGH" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-22 Cont ID  
Sent By rmcdouga Date 2006-08-22 Time 15:40 Rev Time 0.00
Received By rmcdouga Date 2006-08-12 Time 14:43 Sent To  
Notes
2006-08-12 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-02-15 Cont ID  
Sent By tgordon Date 2007-02-15 Time 10:57 Rev Time 0.30
Received By tgordon Date 2007-02-15 Time 10:57 Sent To  
Notes
2007-02-15 10:59:37*** PROVISO ***
 1) GAS GRILL MUST BE A PORTABLE GRILL.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-02-08 Cont ID  
Sent By tgordon Date 2007-02-08 Time 10:38 Rev Time 0.25
Received By tgordon Date 2007-02-08 Time 10:38 Sent To B
Notes
2007-02-08 10:44:03*** DENIED ***
 1) NEW GAS GRILL UNDER EXISTING CANVAS COVERED PATIO
 WILL REQUIRE AN APPROVED EXHAUST HOOD, PER 2004 FBC/M
 505.3.
  
 2) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR GAS
 GRILL AND EXHAUST HOOD.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-21 Cont ID  
Sent By tgordon Date 2006-08-21 Time 09:49 Rev Time 0.30
Received By tgordon Date 2006-08-21 Time 09:49 Sent To B
Notes
2006-08-21 00:00:00*** DENIED ***
 1) CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
 .
  
 2) PLEASE SUBMIT COMBUSTION AIR
 CALCULATIONS, OR PROVIDE COMBUSTION AIR
 FOR GAS CLOTHES DRYER, PER 2004 FBC/M
 702.1 .
  
 3) PLEASE SHOW IN DETAIL WHERE GAS BBQ
 GRILL IS BEING INSTALLED (ROOM OR OUT
 DOORS).
  
 4) STATE ON PLANS IF GAS TANKLESS WATER
 HEATER IS BEING INSTALLED OUT DOORS OR
 NOT.
  
 5) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-02-07 Cont ID  
Sent By mperson Date 2007-02-07 Time 15:41 Rev Time 0.33
Received By mperson Date 2007-02-07 Time 15:41 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-08-18 Cont ID  
Sent By btrobaug Date 2006-08-16 Time 18:17 Rev Time 0.33
Received By mperson Date 2006-08-18 Time 15:37 Sent To M
Notes
2006-08-18 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING AND GAS PLAN REVIEW. PLEASE
 REFERENCE CORRECTED DRAWING IN RED INK
 FOR RESUBMITTAL :
  
 1. PER CHAPTER 1, SECTION 106, PLEASE
 SUBMIT A DRAWING INDICATING EXISTING
 FLOOR PLAN LAY-OUT OF WASHING MACHINE
 AND A SEPERATE DRAWING INDICATING THE
 NEW PROPOSED WASHING MACHINE LAY-OUT.
 2. PER FBC-2004 PLUMBING THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE WASHING
 MACHINE.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER. ( NOTE: THE DRAINAGE STACK IS
 SIZED WRONG.)
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE
 INDIVIDUALLY TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE STANDPIPE
 ON THE CORRECTED DRAWING.
 3. PER FBC-2004 PLUMBING THE FOLLOWING
 INFORMATION ON CLEANOUTS NEEDS TO BE
 INDICATED ON THE CORRECTED DRAWING FOR
 RESUBMITTAL.
 (A) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 (B) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS. CLEANOUTS FOR
 WASHING MACHINES SHALL BE LOCATED 4'
 ABOVE FINNISH FLOOR (AFF). PLEASE NOTE
 THIS ON DRAWING.
 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
  
 NOTE: A SEPERATE PERMIT IS REQUIRED FOR
 THE GAS SYSTEM WITH THE FOLLOWING
 INFORMATION:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. NOTE: THE DRAWING
 SUBMITTED FOR THE GAS PIPE IS NOT AN
 ISOMETRIC.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 10. FBC-2004 CHAPTER 1,SECTION
 106.3.4.2: THE PERSON RESPONSIBLE FOR
 THE DESIGN OF THE DRAWING SHALL CLEARLY
 PRINT AND SIGN NAME, AND ALSO DATE
 DRAWING. PLEASE DO THIS PRIOR TO
 RESUBMITTING.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  