Plan Review Details - Permit 06080678
Plan Review Stops For Permit 06080678
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-10-23 Cont ID  
Sent By dpalmer Date 2006-10-23 Time 18:38 Rev Time 0.00
Received By dpalmer Date 2006-10-23 Time 18:28 Sent To E
Notes
2006-10-23 18:38:19**** UNSAT ****
 AS REVISIONS WERE SUBMITTED UDNER THE WRONG PERMIT
 NUMBER, PLANS FROM FRONT COUNTER SUPERVISOR ON
 10/23/06
  
  
 1) NOTE: PLEASE SEE A PREMIT WAS ISSUED TO REMOVE AND
 REPLACE ELECTRICAL RECEPTS/DEVICES ONLY. PLEASE KNOW AS
 SHOWN THE SCOPE HAS COMPLETELY CHANGED.
 PLEASE PROVIDE INFORMATION ON PLANS FOR COMPLIANCE WITH
 225.31-225.39.
 PLEASE PROVIDE GROUNDING PER 250.32
 PLEASE SEE MISSING DEDICATED BATH CIRCUIT PER
 250.52D,210.11C3
 PLEASE SEE ALL DEDICATE DAND CIRCUITS SHALL BE SHOWN ON
 PANEL SCHEDULE. 240.4,310.16, ETC.
  
 FBC 106.1.2, 106.3.5.4
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717