| Plan Review Stops For Permit 06080602 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2006-12-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-12-26 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-12-26 |
Time |
16:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-12-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-12-07 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-12-07 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2006-12-07 10:36:43 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC RFLORIDA BUILDING CODE 2004 | | | RESIDENTIAL | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED: | | | | | | 1.)DECLARE GOVERNING CODE, INCLUDING | | | FBC EB, AND LEVEL OF ALTERATION FBC EB3.NOTE THAT IT | | | IS ACCEPTABLE FOR THIS TO BE HANDWRITTEN ON THE PLAN BY | | | THE ARCHITECT BUT ALSO MUST BE INITIALLED AND DATED. | | | ALSO NOTE THAT ON THE RESPONSE LETTER, "BUILDING" IS | | | BLANK (NO STATUS, NO COMMENTS) AS IT WAS PRINTED BEFORE | | | THE BUILDING REVIEW WAS COMPLETED. | | | | | | NEW COMMENTS: | | | | | | 2.)THE TITLE BLOCK FOR FEDERATED SPACE IS TO HAVE | | | THEIR CERTIFICATE OF AUTHORIZATION NUMBERS FOR | | | ARCHITECTURE AND ENGINEERING, FAC61G15-23.002, | | | FAC61G16. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-10-04 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-09-29 |
Time |
17:06 |
Sent To |
|
|
| Notes |
| 2006-10-04 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC RFLORIDA BUILDING CODE 2004 | | | RESIDENTIAL | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)DECLARE GOVERNING CODE, INCLUDING | | | FBC EB, AND LEVEL OF ALTERATION FBC EB3. | | | | | | 2.)CITY PLACE STAMP REQUIRED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2006-10-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-28 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-28 |
Time |
15:31 |
Sent To |
|
|
| Notes |
| 2006-10-28 15:35:46 | OK, STAMPED 2 SETS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-09-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-05 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-31 |
Time |
12:08 |
Sent To |
|
|
| Notes |
| 2006-09-05 00:00:00 | ****UNSAT **** | | | | | | *** PLEASE KNOW, PLANS HAVE ONLY BEEN | | | SUBMITTED FOR "PLAN REVIEW" AND AHVE NOT | | | BEEN SUBMITTED FOR PERMITTING. | | | | | | | | | | | | 1) NOTE: PLEASE BE SURE PLANS REFLECT | | | THE FOLLOWING CODES AT A MINIMUM. | | | 2004 FBC , 2002 NFPA-70, 2003 NFPA-101 | | | PLEASE SEE ANY COMMENTS FROM OTHER | | | TRADES WHICH MAY REQUEST OTHER CODES. | | | | | | 2) NOTE: PLEASE KNOW THAT ALL PLANS | | | SUBMITTED FOR WORK DONE IN CITY PLACE | | | WHETHER INTERIOR OR EXITERIOR, MUST | | | CONTAIN THE REVIEW AND STAMP BY THE CITY | | | PLACE MANAGMENT OFFICE. PLEASE BE SURE | | | TO HAVE ALL PLANS STAMPED BY THEIR | | | OFFICE BEFORE SUBMITTING FOR PERMIT. | | | | | | 3) NOTE: PLEASE VERIFY THE PANEL | | | MANUFACTURE AS SHOWN. PLEASE SEE PANEL | | | IS SHOWN AS "FPE" AND IT IS KNOWN TO | | | THIS OFFICE THIS PARTICULAR MACY'IS A | | | NEWER STORE AND FPE WAS OUT OF | | | MANUFACTURING WHEN THIS STORE BUILT. | | | PLEASE VERIFY. | | | 110.3, 90.7 | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | 2006-08-31 00:00:00 | TAKEN OFF "HOLD" AND APPLIED DATE | | | CHANGED TO 8/31 | | 2006-08-24 00:00:00 | ** PROJECT ON "HOLD" AS FEES FOR PLAN | | | REVIEW WERE NOT PAID. | | | CALLED, PERMIT EXPEDITOR SONIA GONZALES, | | | | | | TO BE PAID BY TUESADAY 8/29, OR PLANS | | | WILL BE REMOVED FROM BOARD AND PLACED | | | OUT FRONT FOR PU. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-12-19 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-12-19 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-12-19 |
Time |
14:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-09-15 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-09-15 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-09-15 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2006-09-15 00:00:00 | ***DENIED*** | | | | | | PLAN REVIEW ONLY | | | | | | 1) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL. | | | | | | 2) WILL THIS WORK HAVE ANY DIRECT IMPACT | | | ON EXISTING BUILDING FIRE PROTECTION | | | EQUIPMENT AND REQUIRED MEANS OF EGRESS? | | | | | | 3) PLEASE SHOW ALL EXISTING OR NEW EXIT | | | AND EMERGENCY LIGHTING IN AREAS WITHIN | | | THE SCOPE OF THIS WORK. | | | | | | 4) LIFE SAFETY SHALL COMPLY WITH NFPA | | | 101, 2003 EDITION. | | | | | | 5) WILL ANY RELOCATION OF FIRE | | | EXTINGUISHERS OCCUR DUE TO THIS WORK? | | | | | | 6) CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-10-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-26 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-26 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2006-10-28 15:28:32 | TO "COMM" BD#19 | | 2006-10-26 16:35:16 | WAITING FOR "COMM" BD--PROJECT TO PERMIT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-10-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-10-04 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-08-31 |
Time |
12:16 |
Sent To |
|
|
| Notes |
| 2006-08-23 00:00:00 | TO "COMM" BD#6 | | 2006-08-12 00:00:00 | WAITING FOR COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2006-10-31 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-10-31 |
Time |
09:30 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2006-10-31 |
Time |
09:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-09-19 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-09-19 |
Time |
14:31 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2006-09-19 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2006-09-19 00:00:00 | ** FOR PLAN REVIEW ONLY NOT FOR PERMIT** | | | | | | 1) SEE ELECTRICAL REVIEW NOTES #1 AND 2, | | | PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2006-09-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-09-09 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-09-09 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2006-09-09 00:00:00 | NO PLUMBING WORK SHOWN ON PLANS |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2006-09-05 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2006-09-05 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2006-09-05 |
Time |
11:15 |
Sent To |
|
|
| Notes |
|
|