Plan Review Details - Permit 06080602
Plan Review Stops For Permit 06080602
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-12-26 Cont ID  
Sent By shill Date 2006-12-26 Time 16:23 Rev Time 0.00
Received By shill Date 2006-12-26 Time 16:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-12-07 Cont ID  
Sent By shill Date 2006-12-07 Time 10:11 Rev Time 0.00
Received By shill Date 2006-12-07 Time 10:11 Sent To  
Notes
2006-12-07 10:36:43****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED:
  
 1.)DECLARE GOVERNING CODE, INCLUDING
 FBC EB, AND LEVEL OF ALTERATION FBC EB3.NOTE THAT IT
 IS ACCEPTABLE FOR THIS TO BE HANDWRITTEN ON THE PLAN BY
 THE ARCHITECT BUT ALSO MUST BE INITIALLED AND DATED.
 ALSO NOTE THAT ON THE RESPONSE LETTER, "BUILDING" IS
 BLANK (NO STATUS, NO COMMENTS) AS IT WAS PRINTED BEFORE
 THE BUILDING REVIEW WAS COMPLETED.
  
 NEW COMMENTS:
  
 2.)THE TITLE BLOCK FOR FEDERATED SPACE IS TO HAVE
 THEIR CERTIFICATE OF AUTHORIZATION NUMBERS FOR
 ARCHITECTURE AND ENGINEERING, FAC61G15-23.002,
 FAC61G16.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-10-04 Cont ID  
Sent By shill Date 2006-10-04 Time 09:47 Rev Time 0.00
Received By shill Date 2006-09-29 Time 17:06 Sent To  
Notes
2006-10-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)DECLARE GOVERNING CODE, INCLUDING
 FBC EB, AND LEVEL OF ALTERATION FBC EB3.
  
 2.)CITY PLACE STAMP REQUIRED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-10-28 Cont ID  
Sent By dpalmer Date 2006-10-28 Time 15:35 Rev Time 0.00
Received By dpalmer Date 2006-10-28 Time 15:31 Sent To  
Notes
2006-10-28 15:35:46OK, STAMPED 2 SETS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-09-05 Cont ID  
Sent By dpalmer Date 2006-09-05 Time 09:55 Rev Time 0.00
Received By dpalmer Date 2006-08-31 Time 12:08 Sent To  
Notes
2006-09-05 00:00:00****UNSAT ****
  
 *** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" AND AHVE NOT
 BEEN SUBMITTED FOR PERMITTING.
  
  
  
 1) NOTE: PLEASE BE SURE PLANS REFLECT
 THE FOLLOWING CODES AT A MINIMUM.
 2004 FBC , 2002 NFPA-70, 2003 NFPA-101
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY REQUEST OTHER CODES.
  
 2) NOTE: PLEASE KNOW THAT ALL PLANS
 SUBMITTED FOR WORK DONE IN CITY PLACE
 WHETHER INTERIOR OR EXITERIOR, MUST
 CONTAIN THE REVIEW AND STAMP BY THE CITY
 PLACE MANAGMENT OFFICE. PLEASE BE SURE
 TO HAVE ALL PLANS STAMPED BY THEIR
 OFFICE BEFORE SUBMITTING FOR PERMIT.
  
 3) NOTE: PLEASE VERIFY THE PANEL
 MANUFACTURE AS SHOWN. PLEASE SEE PANEL
 IS SHOWN AS "FPE" AND IT IS KNOWN TO
 THIS OFFICE THIS PARTICULAR MACY'IS A
 NEWER STORE AND FPE WAS OUT OF
 MANUFACTURING WHEN THIS STORE BUILT.
 PLEASE VERIFY.
 110.3, 90.7
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
2006-08-31 00:00:00TAKEN OFF "HOLD" AND APPLIED DATE
 CHANGED TO 8/31
2006-08-24 00:00:00** PROJECT ON "HOLD" AS FEES FOR PLAN
 REVIEW WERE NOT PAID.
 CALLED, PERMIT EXPEDITOR SONIA GONZALES,
  
 TO BE PAID BY TUESADAY 8/29, OR PLANS
 WILL BE REMOVED FROM BOARD AND PLACED
 OUT FRONT FOR PU.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-19 Cont ID  
Sent By mwennerg Date 2006-12-19 Time 14:37 Rev Time 0.00
Received By mwennerg Date 2006-12-19 Time 14:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-15 Cont ID  
Sent By mwennerg Date 2006-09-15 Time 11:56 Rev Time 0.00
Received By mwennerg Date 2006-09-15 Time 11:56 Sent To  
Notes
2006-09-15 00:00:00***DENIED***
  
 PLAN REVIEW ONLY
  
 1) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 2) WILL THIS WORK HAVE ANY DIRECT IMPACT
 ON EXISTING BUILDING FIRE PROTECTION
 EQUIPMENT AND REQUIRED MEANS OF EGRESS?
  
 3) PLEASE SHOW ALL EXISTING OR NEW EXIT
 AND EMERGENCY LIGHTING IN AREAS WITHIN
 THE SCOPE OF THIS WORK.
  
 4) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 5) WILL ANY RELOCATION OF FIRE
 EXTINGUISHERS OCCUR DUE TO THIS WORK?
  
 6) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-26 Cont ID  
Sent By adarroug Date 2006-10-26 Time 16:34 Rev Time 0.00
Received By adarroug Date 2006-10-26 Time 16:34 Sent To  
Notes
2006-10-28 15:28:32TO "COMM" BD#19
2006-10-26 16:35:16WAITING FOR "COMM" BD--PROJECT TO PERMIT

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-04 Cont ID  
Sent By shill Date 2006-10-04 Time 09:50 Rev Time 0.00
Received By shill Date 2006-08-31 Time 12:16 Sent To  
Notes
2006-08-23 00:00:00TO "COMM" BD#6
2006-08-12 00:00:00WAITING FOR COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-10-31 Cont ID  
Sent By tgordon Date 2006-10-31 Time 09:30 Rev Time 0.20
Received By tgordon Date 2006-10-31 Time 09:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-19 Cont ID  
Sent By tgordon Date 2006-09-19 Time 14:31 Rev Time 0.20
Received By tgordon Date 2006-09-19 Time 14:31 Sent To  
Notes
2006-09-19 00:00:00** FOR PLAN REVIEW ONLY NOT FOR PERMIT**
  
 1) SEE ELECTRICAL REVIEW NOTES #1 AND 2,
 PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-09-09 Cont ID  
Sent By kstevens Date 2006-09-09 Time 14:10 Rev Time 0.00
Received By kstevens Date 2006-09-09 Time 13:57 Sent To  
Notes
2006-09-09 00:00:00NO PLUMBING WORK SHOWN ON PLANS

Review Stop Z ZONING
Rev No 1 Status N Date 2006-09-05 Cont ID  
Sent By eschneid Date 2006-09-05 Time 11:16 Rev Time 0.00
Received By eschneid Date 2006-09-05 Time 11:15 Sent To  
Notes
***NONE***