Plan Review Details - Permit 06080583
Plan Review Stops For Permit 06080583
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-08-18 Cont ID  
Sent By lursu Date 2006-08-18 Time 09:15 Rev Time 0.00
Received By lursu Date 2006-08-18 Time 09:15 Sent To  
Notes
2006-08-18 00:00:00EXT #0002 WAS CREATED FOR THIS UNIT 400

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-26 Cont ID  
Sent By rmcdouga Date 2006-09-26 Time 10:23 Rev Time 0.00
Received By rmcdouga Date 2006-09-26 Time 10:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-18 Cont ID  
Sent By rmcdouga Date 2006-08-18 Time 09:36 Rev Time 0.00
Received By rmcdouga Date 2006-08-18 Time 07:18 Sent To  
Notes
2006-08-18 00:00:00BUILDING DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PLEASE SPECIFY THAT THE SOLID
 BLOCKING CALLED OUT IN GENERAL NOTE 11
 ON SHEET T IS REQUIRED TO BE NON
 COMBUSTIBLE OR FIRE-RETARDANT-TREATED
 WOOD. SEE FBC 717.5 AND 603.1.
  
 3) IN THE DOOR SCHEDULE ON A3.1 DOOR #
 EX3 IS LISTED AS ENTRY DOUBLE DOOR AND
 IS SHOWN ON PLANS AS A SINGLE DOOR.
 PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-06 Cont ID  
Sent By dpalmer Date 2006-10-06 Time 15:27 Rev Time 0.00
Received By dpalmer Date 2006-10-06 Time 15:21 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-24 Cont ID  
Sent By dpalmer Date 2006-09-24 Time 16:45 Rev Time 0.00
Received By dpalmer Date 2006-09-24 Time 16:43 Sent To  
Notes
2006-09-24 00:00:00** UNSAT 2ND REVIEW **
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW WHICH ARE STILL IN NEEDOF
 ADDRESSING.
 NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW.
  
 1) NOTE: OK.
  
 2) NOTE: NO, ANY SYSTEM IS NOT SHOWN,
 PLEASE SEE LIGHTING PLANS REMAINED
 UNCHANGED. PLEASE INDICATE ALL DEVICES
 AND ,LOCATIONS.PLEASE SEE SEPARATE
 SPACES.
 PLEASE SEE NO LPD SUBMITTED, OR SHOWN ON
 PLANS.
 PLEASE INDICATE SYMBOLS ON PLANS AND
 CORRELATE WITH SYMBOL LIST FOR DEVICES.
  
 ** PEVIOUS REVIEW NOTE **
 PLEASE SEE FBC 2004 CHAPTER 13.
 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR
 LIGHTING CONTROLS REQUIRED.
 PLEASE PROVIDE INFORMATION FOR DEVICES.
 IF OVER RIDES ARE TIMER (4HRSMAX) IF
 SENSOR TYPE (30MINS MAX) PLEASE
 INDICATE.
 PLEASE SEE LIGHTING POWER DENSITIES.
 13-415.2.ABC.1, TABLES 415.2.C.1.
 415.2.B.1
  
 3) NOTE: OK.
  
 ** NEW NOTE **
  
 4) NOTE: PLEASE SEE PLANS INDICATE AN
 "IT" ROOM, THIS WAS NOT NOTED ON
 PREVIOUS REVIEW. IF INDEED THIS IS A
 TRUE "IT" ROOMS, PLEASE INDICATE ALL
 REQUIREMENTS FOR SHUTTING DOWN
 POWER/EPO, CONSTRUCTION FOR
 ARCHITECTURAL FOR MIN 1HR TO ROOF DECL
 NFPA-75 2002.
 NEC 645, 2002
  
 5) NOTE: NOTICE GIVEN TO FS 553.80(2)(B)
 WITH RESPECT TO REPEAT COMMENTS FOR CODE
 COMPLIANCE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-17 Cont ID  
Sent By kstevens Date 2006-09-06 Time 15:08 Rev Time 0.00
Received By dpalmer Date 2006-08-17 Time 18:36 Sent To  
Notes
2006-08-17 00:00:00** UNSAT **
  
 1) NOTE: PLEASE CLARIFY IF THE CONTINOUS
 LOADS ARE SHOWN AT 125%.215.3,230.42 ETC
  
 2) NOTE: PLEASE SEE FBC 2004 CHAPTER 13.
 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR
 LIGHTING CONTROLS REQUIRED.
 PLEASE PROVIDE INFORMATION FOR DEVICES.
 IF OVER RIDES ARE TIMER (4HRSMAX) IF
 SENSOR TYPE (30MINS MAX) PLEASE
 INDICATE.
 PLEASE SEE LIGHTING POWER DENSITIES.
 13-415.2.ABC.1, TABLES 415.2.C.1.
 415.2.B.1
  
 3) NOTE: PLEASE BE SURE THE FOLLOWING
 CODES AT STATED ON PLANS AT A MIN.
 2002 NFPA-72, 2003 NFPA-101, 2004 FBC.
 2002 NEC IS ALREADY ON PLANS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-09-28 Cont ID  
Sent By mawillia Date 2006-09-28 Time 10:56 Rev Time 0.00
Received By mawillia Date 2006-09-28 Time 10:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-08-28 Cont ID  
Sent By mawillia Date 2006-08-28 Time 09:43 Rev Time 0.00
Received By mawillia Date 2006-08-28 Time 09:27 Sent To P
Notes
2006-08-28 00:00:00**PROVISO**
  
  
  
 1.) INTERIOR FINISH, WALLS, AND CEILING
 IN EXIT ACCESS CORRIDOR TO BE CLASS A OR
 CLASS B.
  
 2.) CONSTRUCTION, ALTERATION, AND
 DEMOLITION OPERATIONS TO COMPLY WITH
 NFPA 241.
  
 3.) COMBUSTIBLE WASTE AND(OR) DEBRIS
 SHALL BE REMOVED DAILY ANDALL EXIT
 COMPONENTS SHALL BE MAINTAINED.
  
 4.) IF THE SCOPE OF THE INTERIOR
 BUILDOUT REQUIRES MODIFICATION OF FIRE
 SPRINKLER OR FIRE ALARM SYSTEM, PROVIDE
 SEPARATE PERMIT AND SHOP DRAWING/PLANS.
  
  
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-17 Cont ID  
Sent By adarroug Date 2006-11-17 Time 11:36 Rev Time 0.00
Received By adarroug Date 2006-11-17 Time 11:36 Sent To M
Notes
2006-11-17 11:37:07TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-20 Cont ID  
Sent By adarroug Date 2006-09-20 Time 16:17 Rev Time 0.00
Received By adarroug Date 2006-09-20 Time 16:17 Sent To  
Notes
2006-09-23 00:00:00TO "BOB"#12
2006-09-20 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-06 Cont ID  
Sent By mmiller Date 2006-09-06 Time 15:08 Rev Time 0.00
Received By kstevens Date 2006-08-11 Time 10:02 Sent To E
Notes
2006-08-17 00:00:00TO "BOB"#12
2006-08-11 00:00:00WAITING FOR BILBOARD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-11-21 Cont ID  
Sent By tgordon Date 2006-11-21 Time 12:01 Rev Time 1.00
Received By tgordon Date 2006-11-21 Time 12:01 Sent To  
Notes
2006-11-21 12:19:00MECHANICAL REVISION PAGE M-1
 *** PROVISO ***
 1) SEE HIGH LIGHTS ON MECHANICAL PLAN.
  
 2) SEE HEAT DUCT TO OPEN OFFICE #414 MUST BE
 CONSTRUCTED OF 0.0217" OF STEEL OR GREATER, SHELL NOT
 BE EXCEED 100 SQUARE INCHES, AND MEET THE EXCEPTION
 UNDER 2004 FBC/M 607.53, OR IT WILL REQUIRE A FIRE
 DAMPER BE INSTALLED).
  
 3) SEE EXISTING ELECT. ROOM #415 WALLS SHELL NOT BE
 RATED, IF SO PROVIDE FIRE DAMPERS, PER 2004 FBC/M
 607.5.2 AND 607.5.3.
  
 4) SEE 7" AND 10"DUCTS ENTERING OFFICE STORAGE ROOM
 #406, MUST BE CONSTRUCTED OF 0.0217" OF STEEL OR
 GREATER, AND MEET THE EXCEPTION UNDER 2004 FBC/M
 607.53, OR THEY WILL REQUIRE A FIRE DAMPER BE
 INSTALLED.
  
 5) SEE HEAT DUCT 12X6 TO OFFICE #407, MUST BE
 CONSTRUCTED OF 0.0217" OF STEEL OR GREATER, AND MEET
 THE EXCEPTION UNDER 2004 FBC/M 607.53, OR IT WILL
 REQUIRE A FIRE DAMPER BE INSTALLED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-10-03 Cont ID  
Sent By tgordon Date 2006-10-03 Time 09:22 Rev Time 0.20
Received By tgordon Date 2006-10-03 Time 09:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-08-18 Cont ID  
Sent By tgordon Date 2006-08-18 Time 12:10 Rev Time 0.45
Received By tgordon Date 2006-08-18 Time 12:10 Sent To  
Notes
2006-08-18 00:00:00*** PROVISO ***
 1) PROVIDE RETURN AIR FOR CONF. ROOM
 #410.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-09-06 Cont ID  
Sent By kstevens Date 2006-09-06 Time 15:08 Rev Time 0.00
Received By kstevens Date 2006-09-06 Time 15:08 Sent To  
Notes
***NONE***