Plan Review Details - Permit 06080582
Plan Review Stops For Permit 06080582
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-08-25 Cont ID  
Sent By lursu Date 2006-08-25 Time 08:10 Rev Time 0.00
Received By lursu Date 2006-08-25 Time 08:10 Sent To  
Notes
2006-08-25 00:00:00EXT #0010 FOR THE UNIT 501 ( AIG) WAS
 ADDED

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-25 Cont ID  
Sent By rmcdouga Date 2006-09-25 Time 16:56 Rev Time 0.00
Received By rmcdouga Date 2006-09-25 Time 16:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-24 Cont ID  
Sent By rmcdouga Date 2006-08-24 Time 07:47 Rev Time 0.00
Received By rmcdouga Date 2006-08-24 Time 07:11 Sent To  
Notes
2006-08-24 00:00:00DENIED
  
 1) THE ARCHITECT DID NOT SIGN AND SEAL
 ALL OF THE ARCHITECTURAL SHEETS ON ONE
 SET OF DRAWINGS.
  
 2)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-03 Cont ID  
Sent By dpalmer Date 2006-10-03 Time 20:06 Rev Time 0.00
Received By dpalmer Date 2006-10-03 Time 20:06 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-24 Cont ID  
Sent By dpalmer Date 2006-09-24 Time 16:59 Rev Time 0.00
Received By dpalmer Date 2006-09-24 Time 16:57 Sent To  
Notes
2006-09-24 00:00:00** UNSAT 2ND REVIEW **
  
  
 1) NOTE: OK.
  
 2) NOTE: NO, PLEASE INDICATE ALL DEVICES
 AND ,LOCATIONS.PLEASE SEE SEPARATE
 SPACES.
 PLEASE INDICATE SYMBOLS ON PLANS AND
 CORRELATE WITH SYMBOL LIST FOR DEVICES.
  
 ** PEVIOUS REVIEW NOTE **
 PLEASE SEE FBC 2004 CHAPTER 13.
 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR
 LIGHTING CONTROLS REQUIRED.
 PLEASE PROVIDE INFORMATION FOR DEVICES.
 IF OVER RIDES ARE TIMER (4HRSMAX) IF
 SENSOR TYPE (30MINS MAX) PLEASE
 INDICATE.
 PLEASE SEE LIGHTING POWER DENSITIES.
 13-415.2.ABC.1, TABLES 415.2.C.1.
 415.2.B.1
  
 3) NOTE: OK.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-24 Cont ID  
Sent By dpalmer Date 2006-08-24 Time 10:11 Rev Time 0.00
Received By dpalmer Date 2006-08-24 Time 10:11 Sent To  
Notes
2006-08-24 00:00:00** UNSAT **
  
 1) NOTE: PLEASE CLARIFY IF THE CONTINOUS
 LOADS ARE SHOWN AT 125%.215.3,230.42 ETC
  
 2) NOTE: PLEASE SEE FBC 2004 CHAPTER 13.
 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR
 LIGHTING CONTROLS REQUIRED.
 PLEASE PROVIDE INFORMATION FOR DEVICES.
 IF OVER RIDES ARE TIMER TYPE (4HRS MAX)
 IF SENSOR TYPE (30MINS MAX) PLEASE
 INDICATE.
 PLEASE SEE LIGHTING POWER DENSITIES.
 13-415.2.ABC.1, TABLES 415.2.C.1.
 415.2.B.1
  
  
 3) NOTE: PLEASE BE SURE THE FOLLOWING
 CODES AT STATED ON PLANS AT A MIN.
 2002 NFPA-72, 2003 NFPA-101, 2004 FBC.
 2002 NEC IS ALREADY ON PLANS.
  
 4) NOTE: PLEASE VERIFY THE PANEL 5LL
 CONTAINING A MCB TO MEET 240.21 AND
 408.16. PLEASE KNOW, IF ONE IS NOT
 EXISTING, ONE WILL BE REQUIRED TO BE
 INSTALLED.
 PLEASE VERIFY.
  
 5) NOTE: PLEASE SEEPLANS IN ONE SET OF
 THE TWO ARE NOT SIGNED, DATED OR SEAL
 FOR BOTH ELECTRICAL SHEETS, ONE
 MECHANICAL AND THREE OF THE
 ARCHITECTURALS.
 PLEASE KNOW, SIGNING AND SEALING OF
 PLANS IS REQUIRED FOR ALL TRADES AND FOR
 ALL REVIEWER(S) WHETHER OR NOT COMMENT
 IS MADE BY THE OTHER REVIEWER(S).
 PLEASE SEE FS 481.221, 471.025
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-09-28 Cont ID  
Sent By mawillia Date 2006-09-28 Time 10:29 Rev Time 0.00
Received By mawillia Date 2006-09-28 Time 10:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-08-28 Cont ID  
Sent By mawillia Date 2006-08-28 Time 11:15 Rev Time 0.00
Received By mawillia Date 2006-08-28 Time 11:14 Sent To  
Notes
2006-08-28 00:00:00**PROVISO**
  
  
  
  
 1.) INTERIOR FINISH, WALLS, AND CEILING
 IN EXIT ACCESS AREAS TO BE CLASS A OR
 CLASS B.
  
 2.) CONSTRUCTION, ALTERATION, AND
 DEMOLITION OPERATIONS TO COMPLY WITH
 NFPA 241.
  
 3.) COMBUSTIBLE WASTE AND(OR) DEBRIS
 SHALL BE REMOVED DAILY AND ALL EXIT
 COMPONENTS SHALL BE MAINTAINED.
  
 4.) IF THE SCOPE OF THE INTERIOR
 BUILDOUT REQUIRES MODIFICATION OF FIRE
 SPRINKLER OR FIRE ALARM SYSTEM, PROVIDE
 SEPARATE PERMIT AND SHOP DRAWINGS/PLANS.
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-804-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-20 Cont ID  
Sent By adarroug Date 2006-09-20 Time 16:08 Rev Time 0.00
Received By adarroug Date 2006-09-20 Time 16:08 Sent To  
Notes
2006-09-23 00:00:00TO "BOB"#7
2006-09-20 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-28 Cont ID  
Sent By mawillia Date 2006-08-28 Time 11:13 Rev Time 0.00
Received By mawillia Date 2006-08-11 Time 09:50 Sent To  
Notes
2006-08-22 00:00:00TO "BOB"#5
2006-08-11 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-09-28 Cont ID  
Sent By tgordon Date 2006-09-28 Time 09:46 Rev Time 0.30
Received By tgordon Date 2006-09-28 Time 09:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-24 Cont ID  
Sent By tgordon Date 2006-08-24 Time 11:35 Rev Time 0.30
Received By tgordon Date 2006-08-24 Time 11:35 Sent To  
Notes
2006-08-24 00:00:00*** DENIED ***
 1) ONLY ONE SET OF MECHANICAL PLANS HAVE
 THE ENGINEER'S SEAL ON THEM, PLEASE
 CORRECT.
  
 2) PLEASE BE ADVISED THE DOORS TO PH.
 CLOSET 505 WILL NEED TO BE LOUVERED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-08-28 Cont ID  
Sent By jleech Date 2006-08-28 Time 09:27 Rev Time 0.00
Received By jleech Date 2006-08-28 Time 09:27 Sent To  
Notes
***NONE***