| Plan Review Stops For Permit 06080582 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2006-08-25 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-08-25 |
Time |
08:10 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-08-25 |
Time |
08:10 |
Sent To |
|
|
| Notes |
| 2006-08-25 00:00:00 | EXT #0010 FOR THE UNIT 501 ( AIG) WAS | | | ADDED |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-09-25 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-09-25 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-09-25 |
Time |
16:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-08-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-08-24 |
Time |
07:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-08-24 |
Time |
07:11 |
Sent To |
|
|
| Notes |
| 2006-08-24 00:00:00 | DENIED | | | | | | 1) THE ARCHITECT DID NOT SIGN AND SEAL | | | ALL OF THE ARCHITECTURAL SHEETS ON ONE | | | SET OF DRAWINGS. | | | | | | 2)A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-10-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-03 |
Time |
20:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-03 |
Time |
20:06 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-09-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-24 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-24 |
Time |
16:57 |
Sent To |
|
|
| Notes |
| 2006-09-24 00:00:00 | ** UNSAT 2ND REVIEW ** | | | | | | | | | 1) NOTE: OK. | | | | | | 2) NOTE: NO, PLEASE INDICATE ALL DEVICES | | | AND ,LOCATIONS.PLEASE SEE SEPARATE | | | SPACES. | | | PLEASE INDICATE SYMBOLS ON PLANS AND | | | CORRELATE WITH SYMBOL LIST FOR DEVICES. | | | | | | ** PEVIOUS REVIEW NOTE ** | | | PLEASE SEE FBC 2004 CHAPTER 13. | | | 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR | | | LIGHTING CONTROLS REQUIRED. | | | PLEASE PROVIDE INFORMATION FOR DEVICES. | | | IF OVER RIDES ARE TIMER (4HRSMAX) IF | | | SENSOR TYPE (30MINS MAX) PLEASE | | | INDICATE. | | | PLEASE SEE LIGHTING POWER DENSITIES. | | | 13-415.2.ABC.1, TABLES 415.2.C.1. | | | 415.2.B.1 | | | | | | 3) NOTE: OK. | | | | | | | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-08-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-24 |
Time |
10:11 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-24 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2006-08-24 00:00:00 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE CLARIFY IF THE CONTINOUS | | | LOADS ARE SHOWN AT 125%.215.3,230.42 ETC | | | | | | 2) NOTE: PLEASE SEE FBC 2004 CHAPTER 13. | | | 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR | | | LIGHTING CONTROLS REQUIRED. | | | PLEASE PROVIDE INFORMATION FOR DEVICES. | | | IF OVER RIDES ARE TIMER TYPE (4HRS MAX) | | | IF SENSOR TYPE (30MINS MAX) PLEASE | | | INDICATE. | | | PLEASE SEE LIGHTING POWER DENSITIES. | | | 13-415.2.ABC.1, TABLES 415.2.C.1. | | | 415.2.B.1 | | | | | | | | | 3) NOTE: PLEASE BE SURE THE FOLLOWING | | | CODES AT STATED ON PLANS AT A MIN. | | | 2002 NFPA-72, 2003 NFPA-101, 2004 FBC. | | | 2002 NEC IS ALREADY ON PLANS. | | | | | | 4) NOTE: PLEASE VERIFY THE PANEL 5LL | | | CONTAINING A MCB TO MEET 240.21 AND | | | 408.16. PLEASE KNOW, IF ONE IS NOT | | | EXISTING, ONE WILL BE REQUIRED TO BE | | | INSTALLED. | | | PLEASE VERIFY. | | | | | | 5) NOTE: PLEASE SEEPLANS IN ONE SET OF | | | THE TWO ARE NOT SIGNED, DATED OR SEAL | | | FOR BOTH ELECTRICAL SHEETS, ONE | | | MECHANICAL AND THREE OF THE | | | ARCHITECTURALS. | | | PLEASE KNOW, SIGNING AND SEALING OF | | | PLANS IS REQUIRED FOR ALL TRADES AND FOR | | | ALL REVIEWER(S) WHETHER OR NOT COMMENT | | | IS MADE BY THE OTHER REVIEWER(S). | | | PLEASE SEE FS 481.221, 471.025 | | | | | | | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-09-28 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-09-28 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-09-28 |
Time |
10:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2006-08-28 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-08-28 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-08-28 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2006-08-28 00:00:00 | **PROVISO** | | | | | | | | | | | | | | | 1.) INTERIOR FINISH, WALLS, AND CEILING | | | IN EXIT ACCESS AREAS TO BE CLASS A OR | | | CLASS B. | | | | | | 2.) CONSTRUCTION, ALTERATION, AND | | | DEMOLITION OPERATIONS TO COMPLY WITH | | | NFPA 241. | | | | | | 3.) COMBUSTIBLE WASTE AND(OR) DEBRIS | | | SHALL BE REMOVED DAILY AND ALL EXIT | | | COMPONENTS SHALL BE MAINTAINED. | | | | | | 4.) IF THE SCOPE OF THE INTERIOR | | | BUILDOUT REQUIRES MODIFICATION OF FIRE | | | SPRINKLER OR FIRE ALARM SYSTEM, PROVIDE | | | SEPARATE PERMIT AND SHOP DRAWINGS/PLANS. | | | | | | | | | | | | | | | LT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-804-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-09-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-20 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-20 |
Time |
16:08 |
Sent To |
|
|
| Notes |
| 2006-09-23 00:00:00 | TO "BOB"#7 | | 2006-09-20 00:00:00 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-08-28 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-08-28 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-08-11 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2006-08-22 00:00:00 | TO "BOB"#5 | | 2006-08-11 00:00:00 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2006-09-28 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-09-28 |
Time |
09:46 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-09-28 |
Time |
09:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-08-24 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-08-24 |
Time |
11:35 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-08-24 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2006-08-24 00:00:00 | *** DENIED *** | | | 1) ONLY ONE SET OF MECHANICAL PLANS HAVE | | | THE ENGINEER'S SEAL ON THEM, PLEASE | | | CORRECT. | | | | | | 2) PLEASE BE ADVISED THE DOORS TO PH. | | | CLOSET 505 WILL NEED TO BE LOUVERED. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2006-08-28 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-08-28 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-08-28 |
Time |
09:27 |
Sent To |
|
|
| Notes |
|
|