Plan Review Details - Permit 06080566
Plan Review Stops For Permit 06080566
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-09-23 Cont ID  
Sent By rnuquist Date 2006-09-23 Time 13:25 Rev Time 0.00
Received By rnuquist Date 2006-09-23 Time 13:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-31 Cont ID  
Sent By btrobaug Date 2006-08-31 Time 16:30 Rev Time 0.50
Received By btrobaug Date 2006-08-31 Time 15:48 Sent To M
Notes
2006-08-31 00:00:00 
  
  
  
  
  
  
 THE VALUE ON THE APPLICATION MUST
 INCLUDE THE COST OF LABOR AND MATERIAL
 FOR THE INSTALLATION OF ALL COMPONENTS
 UNDER THE SCOPE OF THIS PERMIT. FBC
 108.3.
  
 1} PROVIDE A RISER DIAGRAM SHOWING
 ELECTRICAL CONNECTION OF ALL SERVICE AND
 GENERATOR EQUIPMENT.
  
 2} THE SITE PLAN SUBMITTED DOES NOT
 CLARIFY THE PHYSICAL LOCATION OF THE
 EQUIPMENT. COMPLIANCE WITH ARTICLE 225
 CANNOT BE DETERMINED. PLEASE REDRAW AND
 LABEL IF SEPARATE LOCATIONS.
  
 3} THE LOAD CALCULATION EXCEEDS THE
 GENERATOR OUTPUT. SEE 702.5, CAPACITY
 AND RATING.
 AN OPTIONAL STANDBY SYSTEM SHALL HAVE
 ADEQUATE CAPACITY AND RATING FOR THE
 SUPPLY OF ALL EQUIPMENT INTENDED TO BE
 OPERATED AT ONE TIME. OPTIONAL STANDBY
 SYSTEM EQUIPMENT SHALL BE SUITABLE FOR
 THE MAXIMUM AVAILABLE FAULT CURRENT AT
 ITS TERMINALS. THE USER OF THE OPTIONAL
 STANDBY SYSTEM SHALL BE PERMITTED TO
 SELECT THE LOAD CONNECTED TO THE SYSTEM.
  
 4} THERE MUST BE A DISCONNECT FROM THE
 GENERATOR WHERE THE CONDUCTORS ENTER THE
 BUILDING. IF ALL DISCONNECTS CANNOT BE
 GROUPED PER 230.72, SEE THAT ALL
 ARTICLES FROM 225.31 THROUGH 225.39, ARE
 COMPLIED WITH.
  
 5} PROVIDE MANUFACTURERS
 SPECIFICATIONS/RECOMMENDATION, REGARDING
 CLEARANCES.
  
 6} PROVIDE SPECIFICATIONS FOR THE
 TRANSFER SWITCH.
  
 7} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN/DRAWINGS, SHALL PRINT AND SIGN
 THEIR NAME ON THE SHEETS THEY DRAW.
 PLEASE DO THIS PRIOR TO RESUBMITTING.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
  
  
  
  

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-09-06 Cont ID  
Sent By mperson Date 2006-09-06 Time 09:45 Rev Time 0.00
Received By mperson Date 2006-09-06 Time 09:45 Sent To B
Notes
2006-09-06 00:00:00CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.
  
 IMPORTANT INFORMATION
 AS OF 8/25/06 GENERATOR (GEN/RES AND
 GEN/ COM) PERMIT APPLICATIONS SHALL NOT
 BE ACCEPTED UNLESS THE ELECTRICAL
 INFORMATION AND GAS (OR DIESEL)
 INFORMATION IS ALL SUBMITTED AT THE SAME
 TIME. THE GENERATOR, ELECTRICAL AND
 GAS/DIESEL INFORMATION WILL BE ROUTED
 TOGETHER. THIS WILL ENSURE THAT ALL OF
 THE INFORMATION (PARTICULARLY THE
 MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS) ARE AVAILABLE
 TO ALL PLAN REVIEWERS.
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-24 Cont ID  
Sent By adarroug Date 2006-08-24 Time 14:43 Rev Time 0.00
Received By adarroug Date 2006-08-24 Time 14:43 Sent To E
Notes
2006-08-24 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2006-08-12 Time 13:25 Sent To  
Notes
2006-08-12 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-09-05 Cont ID  
Sent By tgordon Date 2006-09-05 Time 15:18 Rev Time 0.15
Received By tgordon Date 2006-09-05 Time 15:18 Sent To G
Notes
2006-09-05 00:00:00*** DENIED ***
 1) SEE ZONING REVIEW NOTES.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-18 Cont ID  
Sent By mmclean Date 2006-08-18 Time 09:33 Rev Time 0.00
Received By mmclean Date 2006-08-18 Time 09:34 Sent To I
Notes
2006-08-23 00:00:00DENIED,
 1. PLEASE SUBMIT TWO COPY OF CURRENT
 SURVEY SHOWING THE LOCATION OF THE
 PROPOSED GENERATOR.
  
 MICHELEL MCLEAN
 ZONING TECHNICIAN
 805-6720