| Plan Review Stops For Permit 06080559 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2006-08-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-08-11 |
Time |
15:16 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-08-11 |
Time |
15:16 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-08-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-08-10 |
Time |
16:31 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-08-10 |
Time |
16:20 |
Sent To |
PC |
|
| Notes |
| 2006-08-10 00:00:00 | | | | NONCOMPLIANT | | | | | | 1} PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. | | | | | | | | | 2} INDICATE THE AMPERE RATING OF THE | | | MAIN BREAKER IN THE NEW PANEL, VOLTAGE | | | RATING, AND NUMBER OF CIRCUITS | | | AVAILABLE. | | | | | | 3} INDICATE THE SIZE OF THE GROUNDING | | | ELECTRODE CONDUCTOR PER 250.66, AND THE | | | GROUNDING SYSTEM( WHAT IS BONDEED) PER | | | 250.52. | | | | | | 4} INDICATE THE SERVICE CONDUCTOR SIZE, | | | AND INDICATE OVERHEAD OR UNDERGROUND. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-08-10 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-08-10 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2006-08-10 |
Time |
16:20 |
Sent To |
E |
|
| Notes |
|
|
|