Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-24 Cont ID  
Sent By rmcdouga Date 2006-08-24 Time 10:18 Rev Time 0.00
Received By rmcdouga Date 2006-08-24 Time 09:02 Sent To  
Notes
2006-08-24 00:00:00BUILDING DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PLANS WITH ARCHITECT'S TITLE BLOCK
 ARE REQUIRED TO BE SIGNED, SEALED AND
 DATED. FS 481.221
  
 3) HANDWRITTEN NOTES ON THE PLANS CAN
 ONLY BE DONE BY THE DESIGNER OF RECORD
 AND ARE REQUIRED TO BE INITIALED AND
 DATED BY THEM.
  
 4) THE PLANS DO NOT IDENTIFY THE ITEMS
 THAT ARE TO BE REMOVED OR DEMOLISHED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-23 Cont ID  
Sent By dpalmer Date 2006-08-23 Time 18:29 Rev Time 0.00
Received By dpalmer Date 2006-08-23 Time 18:29 Sent To  
Notes
2006-08-23 00:00:00** UNSAT **
  
 1) NOTE: PLANS SUBMITTED FO INTERIOR
 DEMO WORK , NOT SIGNED DATED OR SEALED
 BY SAID ARCHITECT ON PLANS/TITLE BLOCK.
 FS 481.221
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-15 Cont ID  
Sent By mawillia Date 2006-09-15 Time 12:23 Rev Time 0.00
Received By mawillia Date 2006-09-15 Time 12:11 Sent To AD
Notes
2006-09-15 00:00:00*****DENIED*****
  
  
  
  
 1.) STRUCTURES UNDERGOING CONSTRUCTION,
 ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 2.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIALS AND DUST DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH
 SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATIONS.
  
 3.)CONSTRUCTION AND/OR DEMOLITION
 OPERATIONS SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONDERS ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF.
  
 4.) EXITS SHALL REMAIN CLEAR AND
 UNOBSTRUCTED.
  
 5.) NFPA 101, 2003 EDITION AND FLORIDA
 FIRE PREVENTION CODE, 2004 EDITION SHALL
 BE REFERENCED.
  
 6.) SINCE THE SCOPE OF THE PROPOSED WORK
 IS FOR BUILDING 2, PLEASE INDICATE THE
 LOCATION OF THIS BUILDING IN
 RELATIONSHIP TO OTHER BUILDING(S) ON THE
 PROPERTY.
  
 7.) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR SPRINKLER AND FIRE
 ALARM SYSTEM INSATLLATION OR REMODEL.
  
 8.) PLEASE INDICATE INTERIOR FINISH FOR
 WALLS AND CEILINGS.CLASS A OR B IS
 REQUIRED IN THE MEANS OF EGRESS AREAS.
  
 9.)PANIC HARDWARE IS REQUIRED ON EXIT
 DOORS SERVING AN OCCUPANT LOAD GREATER
 THAN ONE HUNDRED.
  
 10.) PLEASE INDICATE/DISPLAY/SHOW
 LOCATION OF EXIT LIGHTS, EMERGENCY
 LIGHTS, PULL STATIONS, FIRE EXTINGUISHER
 FOR THE PROPOSED.
  
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-15 Cont ID  
Sent By mawillia Date 2006-09-15 Time 12:11 Rev Time 0.00
Received By mawillia Date 2006-08-11 Time 16:41 Sent To  
Notes
2006-08-23 00:00:00TO "COMM" BD#5
2006-08-11 00:00:00WAITING FOR COMMERICAL BOARD