| 2006-09-15 00:00:00 | *****DENIED***** |
| | |
| | |
| | |
| | |
| | 1.) STRUCTURES UNDERGOING CONSTRUCTION, |
| | ALTERATION, OR DEMOLITION OPERATIONS |
| | SHALL COMPLY WITH NFPA 241. |
| | |
| | 2.) ACCUMULATIONS OF COMBUSTIBLE WASTE |
| | MATERIALS AND DUST DEBRIS SHALL BE |
| | REMOVED FROM THE STRUCTURE AND ITS |
| | IMMEDIATE VICINITY AT THE END OF EACH |
| | SHIFT OR MORE FREQUENTLY AS NECESSARY |
| | FOR SAFE OPERATIONS. |
| | |
| | 3.)CONSTRUCTION AND/OR DEMOLITION |
| | OPERATIONS SHALL NOT INTERFERE OR HINDER |
| | EMERGENCY RESPONDERS ACCESS TO THE SAID |
| | PROPERTY OR VICINITY THEREOF. |
| | |
| | 4.) EXITS SHALL REMAIN CLEAR AND |
| | UNOBSTRUCTED. |
| | |
| | 5.) NFPA 101, 2003 EDITION AND FLORIDA |
| | FIRE PREVENTION CODE, 2004 EDITION SHALL |
| | BE REFERENCED. |
| | |
| | 6.) SINCE THE SCOPE OF THE PROPOSED WORK |
| | IS FOR BUILDING 2, PLEASE INDICATE THE |
| | LOCATION OF THIS BUILDING IN |
| | RELATIONSHIP TO OTHER BUILDING(S) ON THE |
| | PROPERTY. |
| | |
| | 7.) SEPARATE SHOP DRAWINGS AND PERMITS |
| | ARE REQUIRED FOR SPRINKLER AND FIRE |
| | ALARM SYSTEM INSATLLATION OR REMODEL. |
| | |
| | 8.) PLEASE INDICATE INTERIOR FINISH FOR |
| | WALLS AND CEILINGS.CLASS A OR B IS |
| | REQUIRED IN THE MEANS OF EGRESS AREAS. |
| | |
| | 9.)PANIC HARDWARE IS REQUIRED ON EXIT |
| | DOORS SERVING AN OCCUPANT LOAD GREATER |
| | THAN ONE HUNDRED. |
| | |
| | 10.) PLEASE INDICATE/DISPLAY/SHOW |
| | LOCATION OF EXIT LIGHTS, EMERGENCY |
| | LIGHTS, PULL STATIONS, FIRE EXTINGUISHER |
| | FOR THE PROPOSED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |