| 2006-09-09 00:00:00 | ****UNSAT 2ND REVIEW **** |
| | |
| | 1) NOTE: NO, PLEASE SEE REPSONE LETTER |
| | MENTIONS DESIGN WERE DESIGNED TO THE |
| | MOST RECENT ADOPTED CODES, HOWEVER |
| | PLEASE KNOW, THE CODES WHICH ARE |
| | RELEVANT TO DESIGN ARE REQUIRED ON PLANS |
| | FOR SCOPE OF WORK SHOWN ON PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE BE SURE PLANS REFLECT |
| | THE FOLLOWING CODES. |
| | 2004 FBC , 2002 NFPA-70, 2002 NFPA-72, |
| | AND 2003 NFPA-101. |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE: NO?? PLEASE KNOW IT IS UNCLEAR |
| | WHAT IS BEING DONE WITH THE SERVICE AS |
| | SHOWN ON PLANS. IT WAS ORIGINAL THOUGHT |
| | THAT THE SERVICE SHOWN ON PREVIOUS PLANS |
| | WAS "EXISTING", HOWEVER PLANS INDICATE |
| | THIS SERVICE IS PROPOSED. PLEASE SEE |
| | RESPONSE LETTER MENTIONS THIS WAS |
| | ALREADY DONE UNDER OTHER PLANSAND |
| | PERMITS AND THE LTR MENTIONS THIS |
| | INFORMATION AND DOCUMENTATION WAS |
| | SUBMITTED, HOWEVER COULD NOT LCOATE ANY |
| | OF THIS IN PACKAGE.? |
| | IF THIS SERVICE IS NEW ON THE PERMIT AND |
| | SCOPE, PLEASE COMPLETE RISER WITH ALL |
| | CONDUIT SIZES FOR RISER AND CONDUIT FROM |
| | MAIN TO GUTTER, GUTTER TO METERS AND |
| | OTHER MAINS, ALONG WITH SIZES OF ALL NEW |
| | MAINS, METERS, AND CONDUCTOR SIZES. |
| | ALSO IF PERMIT IS NEW UNDER THIS SCOPE, |
| | PLEASE PROVIDE A LAYOUT OF THE ENTIRE |
| | BUILDING WHICH NEW SERVICE IS BEING |
| | INSTALLED. DOES THIS "BUILDING " CONTAIN |
| | ANY OTHER SERVICES? IF THE NEW SERVICE |
| | IS TAKING PLACE OF A PREVIOUS SERVICE, |
| | PLEASE INDICATE. |
| | NEED TO SHOW SERVICE ON A PLAN "OVER |
| | VIEW" INDICATING ALL CLEARENCES AS |
| | REQUIRED. 110.26 |
| | PLEASE KNOW, IF THIS SERVICE AS SHOWN |
| | BACKS UP TO THE ALLEEY IN THE REAR OF |
| | THIS BUILDING, BOLLARDS WILL BE REQUIRED |
| | TO PROTECT THE SERVICE EQUIPMENT. |
| | |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE COMPLETE LOAD |
| | CALCULATIONSFOR EXISTING SERVICE AND |
| | NEW LOADS BEING ADDED. |
| | NOTE ON PLANS MENTIONS THIS, HOWEVER |
| | CALCULATIONS COULD NOT BE LOCTAED. |
| | 220,215.5, |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE SEE NOTE BELOW WHICH |
| | MENTIONS"IMPORTANT" ETC. |
| | PLEASE SEE THAT TWO COMPLETE SETS WERE |
| | NOT SUBMITTED IN THE ORDER AS PREVIOUSLY |
| | REQUESTED IN NOTE BELOW. |
| | *************************************** |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | *************************************** |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |