Plan Review Details - Permit 06080501
Plan Review Stops For Permit 06080501
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-08-22 Cont ID  
Sent By lursu Date 2006-08-22 Time 14:50 Rev Time 0.00
Received By lursu Date 2006-08-22 Time 14:50 Sent To  
Notes
2006-08-22 00:00:00ATTACH PERMIT TO EXT #0001 FOR THE UNIT
 2, UNDER THE MAIN PCN

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-08-17 Cont ID  
Sent By alange Date 2006-08-17 Time 15:01 Rev Time 0.00
Received By alange Date 2006-08-17 Time 15:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-13 Cont ID  
Sent By dpalmer Date 2006-10-13 Time 16:10 Rev Time 0.00
Received By dpalmer Date 2006-10-13 Time 15:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-09 Cont ID  
Sent By dpalmer Date 2006-09-09 Time 15:04 Rev Time 0.00
Received By dpalmer Date 2006-09-09 Time 14:52 Sent To  
Notes
2006-09-09 00:00:00****UNSAT 2ND REVIEW ****
  
 1) NOTE: NO, PLEASE SEE REPSONE LETTER
 MENTIONS DESIGN WERE DESIGNED TO THE
 MOST RECENT ADOPTED CODES, HOWEVER
 PLEASE KNOW, THE CODES WHICH ARE
 RELEVANT TO DESIGN ARE REQUIRED ON PLANS
 FOR SCOPE OF WORK SHOWN ON PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE PLANS REFLECT
 THE FOLLOWING CODES.
 2004 FBC , 2002 NFPA-70, 2002 NFPA-72,
 AND 2003 NFPA-101.
  
 2) NOTE: OK.
  
 3) NOTE: NO?? PLEASE KNOW IT IS UNCLEAR
 WHAT IS BEING DONE WITH THE SERVICE AS
 SHOWN ON PLANS. IT WAS ORIGINAL THOUGHT
 THAT THE SERVICE SHOWN ON PREVIOUS PLANS
 WAS "EXISTING", HOWEVER PLANS INDICATE
 THIS SERVICE IS PROPOSED. PLEASE SEE
 RESPONSE LETTER MENTIONS THIS WAS
 ALREADY DONE UNDER OTHER PLANSAND
 PERMITS AND THE LTR MENTIONS THIS
 INFORMATION AND DOCUMENTATION WAS
 SUBMITTED, HOWEVER COULD NOT LCOATE ANY
 OF THIS IN PACKAGE.?
 IF THIS SERVICE IS NEW ON THE PERMIT AND
 SCOPE, PLEASE COMPLETE RISER WITH ALL
 CONDUIT SIZES FOR RISER AND CONDUIT FROM
 MAIN TO GUTTER, GUTTER TO METERS AND
 OTHER MAINS, ALONG WITH SIZES OF ALL NEW
 MAINS, METERS, AND CONDUCTOR SIZES.
 ALSO IF PERMIT IS NEW UNDER THIS SCOPE,
 PLEASE PROVIDE A LAYOUT OF THE ENTIRE
 BUILDING WHICH NEW SERVICE IS BEING
 INSTALLED. DOES THIS "BUILDING " CONTAIN
 ANY OTHER SERVICES? IF THE NEW SERVICE
 IS TAKING PLACE OF A PREVIOUS SERVICE,
 PLEASE INDICATE.
 NEED TO SHOW SERVICE ON A PLAN "OVER
 VIEW" INDICATING ALL CLEARENCES AS
 REQUIRED. 110.26
 PLEASE KNOW, IF THIS SERVICE AS SHOWN
 BACKS UP TO THE ALLEEY IN THE REAR OF
 THIS BUILDING, BOLLARDS WILL BE REQUIRED
 TO PROTECT THE SERVICE EQUIPMENT.
  
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE COMPLETE LOAD
 CALCULATIONSFOR EXISTING SERVICE AND
 NEW LOADS BEING ADDED.
 NOTE ON PLANS MENTIONS THIS, HOWEVER
 CALCULATIONS COULD NOT BE LOCTAED.
 220,215.5,
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE NOTE BELOW WHICH
 MENTIONS"IMPORTANT" ETC.
 PLEASE SEE THAT TWO COMPLETE SETS WERE
 NOT SUBMITTED IN THE ORDER AS PREVIOUSLY
 REQUESTED IN NOTE BELOW.
 ***************************************
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
 ***************************************
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-18 Cont ID  
Sent By dpalmer Date 2006-08-18 Time 11:07 Rev Time 0.00
Received By dpalmer Date 2006-08-18 Time 08:34 Sent To  
Notes
2006-08-18 00:00:00****UNSAT ****
  
 1) NOTE: PLEASE BE SURE PLANS REFLECT
 THE FOLLOWING CODES.
 2004 FBC , 2002 NFPA-70, 2002 NFPA-72,
 AND 2003 NFPA-101.
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13, FOR
 LIGHTING CONTROLS REQUIRED.
 13-415.1.ABC.1.1, .1.2, AND .1.3
 THIS SPACE IS PART OF A BUILDING LARGER
 THAN 5000 SQ FT,
  
 3) NOTE: PLEASE PROVIDE COMPLETE LOAD
 CALCULATIONSFOR EXISTING SERVICE AND
 NEW LOADS BEING ADDED.
 NOTE ON PLANS MENTIONS THIS, HOWEVER
 CALCULATIONS COULD NOT BE LOCTAED.
 220,215.5,
 FBC 106.1.2
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-08-24 Cont ID  
Sent By mwennerg Date 2006-08-24 Time 15:46 Rev Time 0.00
Received By mwennerg Date 2006-08-24 Time 15:46 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-09-18 Cont ID  
Sent By jleech Date 2006-09-18 Time 08:20 Rev Time 0.00
Received By jleech Date 2006-09-18 Time 08:20 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-08-26 Cont ID  
Sent By jleech Date 2006-08-26 Time 12:57 Rev Time 0.00
Received By jleech Date 2006-08-26 Time 12:57 Sent To  
Notes
2006-08-26 00:00:00DENIED;
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 2.A UNION IS REQUIRED BETWEEN THE
 SHUTOFF VALVE AND THE EMERGENCY SHUTOFF
 VALVE FOR REPLACEMENT OR REPAIR OF
 VALVE.
 3.ADD A DRIP LEG TO YOUR ISOMETRIC AT
 KITCHEN EQUIPMENT SECTION408.4.
 4.LIST ALL GAS EQUIPMENT AND THE BTU'S
 OF EACH.
 5.NATURAL GAS REQUIREMENT NOTES;
 3.FPU GAS CO.PRESSURE IS 12"W.C.
 6.DELETE (OR FBC APPROVED EQUAL)
 PIPE MUST BE SIZED BY THE APPRO-
 PRIATE CHARTS IN CHAPTER 4 OF THE
 FBC FUEL GAS CODE.
 9.GAS PIPE TO BE INSTALLED PER FBC
 2004 FUEL GAS CODE NOT NFPA 54.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-12-07 Cont ID  
Sent By adarroug Date 2006-12-07 Time 14:13 Rev Time 0.00
Received By adarroug Date 2006-12-07 Time 14:13 Sent To  
Notes
2006-12-28 10:23:27TO "BOB"#8
2006-12-07 14:13:25WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-06 Cont ID  
Sent By adarroug Date 2006-10-06 Time 08:40 Rev Time 0.00
Received By adarroug Date 2006-10-06 Time 08:40 Sent To  
Notes
2007-05-04 15:44:13TO LUIS'S DESK
2006-10-12 09:43:47TO "BOB"#8
2006-10-06 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 15:01 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 15:01 Sent To  
Notes
2006-09-08 00:00:00WAITING FOR "BOB"
 TO "BOB"#10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-10 Cont ID  
Sent By mmiller Date 2006-08-10 Time 15:25 Rev Time 0.00
Received By mmiller Date 2006-08-10 Time 15:25 Sent To E
Notes
2006-08-17 00:00:00TO "BOB"#15
2006-08-10 00:00:00WAITING " FOR BBOARD"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-08-17 Cont ID  
Sent By tgordon Date 2006-08-17 Time 15:59 Rev Time 0.30
Received By tgordon Date 2006-08-17 Time 15:59 Sent To  
Notes
2006-08-17 00:00:00*** PROVISO ***
 1) ADDITIONAL PERMITS REQUIRED FOR HOOD,
 AND FIRE SUPPESSION, SUBMIT PLANS WITH
 PERMIT APPLICATION.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-01-05 Cont ID  
Sent By jleech Date 2007-01-05 Time 10:25 Rev Time 0.00
Received By jleech Date 2007-01-05 Time 10:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-10-23 Cont ID  
Sent By jleech Date 2006-10-23 Time 15:26 Rev Time 0.00
Received By jleech Date 2006-10-23 Time 14:59 Sent To  
Notes
2006-10-23 15:25:27WASTE ORDINANCE # 3434; REQUIRES THE UTILITY DEPARTMENT
 TO REVIEW ALL RESTARUANTS TO DETERMINE
 IF A GREASE TRAP IS REQUIRED AND SIZE OFTRAP IF
 REQUIRED. PLEASE CONTACT;
 LYNN MASSON AT 822-2271
 E-MAIL [email protected]: TO RCO
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-09-18 Cont ID  
Sent By jleech Date 2006-09-18 Time 08:20 Rev Time 0.00
Received By jleech Date 2006-09-18 Time 08:20 Sent To  
Notes
2006-09-18 00:00:00DENIED;
 1.PLANS MUST BE REVIEWED BY THE DIVISION
 OF HOTELS AND RESTAURANTS. SEE WEB SITE,
 WWW.MYFLORIDA.COM/DBPR/HR/FORMS/INDEX.SH
 WW.MYFLORIDA.COM/DBPR/HR/FORMS/INDEX.SHT
 W.MYFLORIDA.COM/DBPR/HR/FORMS/INDEX.SHTM
 OR PHONE (850)487-1395.
 2.GREASE TRAP SIZE AND LOCATION MUST BE
 APPROVED BY HOTEL AND RESTAURANTS AND
 THE UTILITY DEPARTMENT BEFORE PLANS CAN
 BE APPROVED BY THE PLUN=MBING PLAN
 REVIEW DEPARTMENT.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-08-26 Cont ID  
Sent By jleech Date 2006-08-26 Time 13:34 Rev Time 0.00
Received By jleech Date 2006-08-26 Time 13:34 Sent To  
Notes
2006-08-26 00:00:00DENIED;
 1.GREASE TRAP SIZING WILL BE DONE BY THE
 UTILITY DEPARTMENT, WASTE ORDINANCE
 #3434. PLEASE CONTACT;
 LYNN MASSON
 PHONE # 822-2271
 FAX# 822-2279
 [email protected]
 2.WATER HEATER DETAIL; THERMAL EXPANTION
 TANK TO BE ON COLD WATER SIDE OF HEATER
 PER MANUFACTURE'S SPECIFICATIONS.
 3.PLUMBING NOTES; WATER HAMMER ARRESTORS
 TO BE USED IN PLACE OF AIR CHAMBERS. SEE
 FBC-2004 PLUMBING SEC604.9 FOR LOCATION
 REQUIRED.
 4.BATHROOM FLOOR DRAIN SHOULD BE PART OF
 BATHROOM SANITARY SYSTEM SEE SECTION
 909.1 WET VENT.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status N Date 2006-12-20 Cont ID  
Sent By mflis Date 2006-12-20 Time 13:56 Rev Time 0.00
Received By mflis Date 2006-12-20 Time 13:56 Sent To  
Notes
2006-12-20 13:57:18REVIEWED- APPROVED 9-05-06
 INTERIOR WORK ONLY.
  
 -MATT FLIS 822-1445

Review Stop Z ZONING
Rev No 1 Status P Date 2006-12-20 Cont ID  
Sent By mflis Date 2006-09-05 Time 10:11 Rev Time 0.00
Received By mflis Date 2006-12-20 Time 13:56 Sent To  
Notes
2006-09-05 00:00:00REVIEWED-
  
 *) PLEASE INCLUDE BUILDING PLAN/DIAGRAM
 INDICATING LEASE SPACE LOCATION IN PLAN.