| 2006-08-25 00:00:00 | REVIEW IN PROGRESS |
| | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE OWNER AND PERMITTING |
| | OF UNIT MAY NOT BE ASSIGNED OR ADRESSED |
| | TO THE OWNER OF ONE OF THE FEE SIMPLE |
| | UNITS. PLEASE SEE PERMIT APPLICATION HAS |
| | THE GENERATOR BEING PERMITTED TO UNIT |
| | H1713, AND OWNER BEING CAROL WEBSTER |
| | WHICH IS THE OWNER OF UNTI #1013. IT WAS |
| | LOCATED ON THE PAPERWORK THAT SHE IS THE |
| | PRESIDENT OF THE ASSOCIATION HOWEVER THE |
| | GEN CAN NOT PERMITTED TO HER ADDRESS. |
| | PLEASE ADJUST PERMIT APPLICATION, AND |
| | PAPERWORK. |
| | |
| | 2) NOTE: PLEASE CORRELATE GENERATOR |
| | SPECS, PLANS AND PERMIT APPLICATION. |
| | PLEASE SEE SPECS FOR NATURAL GAS, AND |
| | PLANS FOR DIESEL. ? |
| | 106.1.2 FBC |
| | |
| | 3) NOTE: PLEASE SEE PLANS STILL SHOW |
| | LEAVING THE MTS DEVICE IN LOCATION, IF |
| | THIS ISLEGALLY REQUIRED BACK UP |
| | SYSTEM, AN AUTOMATIC MEANS OF TRANSFER |
| | OF POWER MUST BE IN PLACE. THE |
| | RECEPT/MTS MAY REMAIN, HOWEVER THIS |
| | SHOULD BE WIRED IN THE EVENT OF FAILURE |
| | OF THE GEN, THEN A PORTABLE CAN BE USED. |
| | |
| | 4) NOTE: PLEASE SEE IF ELEVATION IS 6.5' |
| | AND BFE IS 7.0, THE 8" SLAB IS ONLY 2" |
| | ABOVE BFE, WHERE IT WOULD BE REQUIRED TO |
| | BE 6" ABOVE BFE, PLEASE ADJUST. |
| | NFPA-110 7.2 |
| | |
| | 5) NOTE: PLEASE PROVIDE LOAD |
| | CALCULATIONS FOR SAID LOADS WHICH WILL |
| | BE IMPOSED ON UNIT. THIS IS NO LONGER A |
| | MTS SYSTEM. |
| | 220,701.6 |
| | |
| | 6) NOTE: PLEASE INDICATE THE LOCATION OF |
| | THE EXISTING MAINS AND DISCONNECTS AND |
| | GROUPING. 225.34, 225.72 |
| | PLEASE ALSO SEE 230.2E, 701.9 |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |