Plan Review Details - Permit 06080393
Plan Review Stops For Permit 06080393
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2006-08-25 Cont ID  
Sent By swurafti Date 2006-08-25 Time 10:29 Rev Time 0.00
Received By swurafti Date 2006-08-25 Time 10:11 Sent To  
Notes
2006-08-25 00:00:00DISREGARD ADDRESSING IN/OUT DONE IN
 ERROR

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-01 Cont ID  
Sent By jwitmer Date 2006-09-01 Time 13:26 Rev Time 2.22
Received By jwitmer Date 2006-09-01 Time 13:25 Sent To  
Notes
2006-09-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06080393
 ADD: 3901 S. FLAGLER DR
 CONT: MILLER ELECTRIC
 TEL: (305)986-3669
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) PERMIT APPLICATION INDICATES THE
 OWNER OF RECORD TO BE THE PRESIDENT OF
 ASSOCIATION BUT THE PRESIDENTS OWN UNIT
 IS NOT TO BE DESIGNATED AS PART OF
 ADDRESS (LOCATION) ON PERMIT
 APPLICATION.
  
 4) THIS ADDRESS IS LOCATED IN A "A-5"
 FLOOD ZONE. THE BASE FLOOD ELEVATION IS
 7'-0" FROM FEMA, BUT THE CITY IS MORE
 RESTRICTIVE WITH NEW WORK NOT TO BE BE
 BELOW THE ELEVATION OF 7'-6".
 PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6" BEFORE A CERTIFICATE OF
 COMPLETIONWILL BE ISSUED.
  
 5) SHEET E2 INDICATES THAT GRADE IS
 6'-6", SHEET S3 INDICATES THAT THE SLAB
 IS TO BE SET WITH 3" ABOVE GRADE OR A
 FINISHED HEIGTH OF 6'-9". HOW WILL THE
 DIFFERENCE TO 7'-6" BE ACCOMPLISHED WITH
 A PRECAST CONCRETE PAD? THIS IS A
 MINIMUM THAT MUST BE MET!!!!
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-25 Cont ID  
Sent By dpalmer Date 2006-08-25 Time 07:39 Rev Time 0.00
Received By dpalmer Date 2006-08-24 Time 18:47 Sent To  
Notes
2006-08-25 00:00:00REVIEW IN PROGRESS
 *** UNSAT ***
  
 1) NOTE: PLEASE SEE OWNER AND PERMITTING
 OF UNIT MAY NOT BE ASSIGNED OR ADRESSED
 TO THE OWNER OF ONE OF THE FEE SIMPLE
 UNITS. PLEASE SEE PERMIT APPLICATION HAS
 THE GENERATOR BEING PERMITTED TO UNIT
 H1713, AND OWNER BEING CAROL WEBSTER
 WHICH IS THE OWNER OF UNTI #1013. IT WAS
 LOCATED ON THE PAPERWORK THAT SHE IS THE
 PRESIDENT OF THE ASSOCIATION HOWEVER THE
 GEN CAN NOT PERMITTED TO HER ADDRESS.
 PLEASE ADJUST PERMIT APPLICATION, AND
 PAPERWORK.
  
 2) NOTE: PLEASE CORRELATE GENERATOR
 SPECS, PLANS AND PERMIT APPLICATION.
 PLEASE SEE SPECS FOR NATURAL GAS, AND
 PLANS FOR DIESEL. ?
 106.1.2 FBC
  
 3) NOTE: PLEASE SEE PLANS STILL SHOW
 LEAVING THE MTS DEVICE IN LOCATION, IF
 THIS ISLEGALLY REQUIRED BACK UP
 SYSTEM, AN AUTOMATIC MEANS OF TRANSFER
 OF POWER MUST BE IN PLACE. THE
 RECEPT/MTS MAY REMAIN, HOWEVER THIS
 SHOULD BE WIRED IN THE EVENT OF FAILURE
 OF THE GEN, THEN A PORTABLE CAN BE USED.
  
 4) NOTE: PLEASE SEE IF ELEVATION IS 6.5'
 AND BFE IS 7.0, THE 8" SLAB IS ONLY 2"
 ABOVE BFE, WHERE IT WOULD BE REQUIRED TO
 BE 6" ABOVE BFE, PLEASE ADJUST.
 NFPA-110 7.2
  
 5) NOTE: PLEASE PROVIDE LOAD
 CALCULATIONS FOR SAID LOADS WHICH WILL
 BE IMPOSED ON UNIT. THIS IS NO LONGER A
 MTS SYSTEM.
 220,701.6
  
 6) NOTE: PLEASE INDICATE THE LOCATION OF
 THE EXISTING MAINS AND DISCONNECTS AND
 GROUPING. 225.34, 225.72
 PLEASE ALSO SEE 230.2E, 701.9
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-08-24 00:00:00IN ELEC FOR REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-13 Cont ID  
Sent By mawillia Date 2006-10-13 Time 15:46 Rev Time 0.00
Received By mawillia Date 2006-10-13 Time 15:46 Sent To  
Notes
2006-10-13 15:45:39*****DENIED*****
  
  
  
 1.)IN THE EVENT OF A FUEL LEAK, HOW WILL THE RUNOFF
 BE CONTAINED TO NOT COMPROMISE LIFE SAFETY AND/OR THE
 ENVIRONMENT?
  
  
 2.)LOCATION OF STRUCTURE SHALL NOT HINDER, IMPEDE, OR
 OBSTRUCT ENTRANCE AND/OR EXITING TO ROOF.
  
 3.)HOW WILL THE UTILITY LINES AS WELL AS FUEL
 (DIESEL) BE SUPPLIED TO THE GENERATOR.PLEASE BE
 ADVISED THAT PENETRATIONS INTO, AND OPENINGS THROUGH,
 AN EXIT ENCLOSURE (FIRE RATED STAIRWELL) SHALL BE
 LIMITED AS PER NFPA 101, CH. 7, SECTION 7.1.3.2.1 (6).
  
 4.)WHAT IS THE FIRE RATING OF THE ROOF?
  
 5.)IN RELATION TO EXHAUST FUMES, WHAT ARE THE
 DISTANCES TO SURROUNDING ROOF TOP UNIT (RTU) INTAKE
 AIR?
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2006-10-17 Cont ID  
Sent By pkrauss Date 2006-10-17 Time 13:08 Rev Time 0.00
Received By pkrauss Date 2006-10-17 Time 13:08 Sent To  
Notes
2006-10-17 13:39:28DENIED:
 PLEASE CLARIFY MANUFACTURE'SSUBMITTAL DATA, TWO
 DIFFERENT GENERATOR'S WERE SUBMITTED.ONE IS
 INDICATING NATURAL GAS OR LP AND THE SECOND GENERATOR
 IS A DIESEL GENERATOR.PLANS ALSO INDICATE DIESEL
 GENERATOR.
  
 1.FOR THE DIESEL GENERATOR PLEASE CLARIFY IF THIS
 WILL HAVE A SUB-BASE SELF CONTAINED FUEL TANK OR REMOTE
 FILL/ DAY TANK.
  
 2.PLEASE PROVIDE ANY FUEL PIPING, SIZE, MATERIAL OR
 LAYOUT IF APPLICABLE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-08-31 Cont ID  
Sent By kstevens Date 2006-08-31 Time 16:37 Rev Time 0.00
Received By kstevens Date 2006-08-31 Time 16:37 Sent To  
Notes
2006-08-31 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
  
 1. SUBMITTALS FOR TWO TYPES OF
 GENERATORS HAVE BEEN SUBMITTED. ONE IS
 FOR DIESEL AND THE OTHER IS FOR NATURAL
 OR LP GAS. PLANS SHOW DIESEL. PLEASE
 CLARIFY. - IF NATURAL OR LP GAS FUEL IS
 USED, SEE ATTACHED SHEET FOR FUEL GAS
 REQUIREMENTS FOR PERMIT FOR GAS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-17 Cont ID  
Sent By pkrauss Date 2006-10-17 Time 13:43 Rev Time 0.00
Received By pkrauss Date 2006-08-08 Time 16:15 Sent To  
Notes
2006-08-22 00:00:00TO "COMM" BD#64
2006-08-08 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-17 Cont ID  
Sent By pkrauss Date 2006-10-17 Time 10:34 Rev Time 0.00
Received By pkrauss Date 2006-10-17 Time 09:30 Sent To  
Notes
2006-10-17 10:22:49DENIED:
 1.PERMIT APPLICATION INDICATES DIESEL GENERATOR
 WHEREAS THE MANFUACTURER'S SUBMITTAL INDICATES NATURAL
 GAS OR LP WAS THIS SUBMITTED IN ERROR.SUBMITTAL
 PACKAGE ALSO INCLUDES A DIESEL GENERATOR.PLEASE
 CORRELATE.
  
 2.PLEASE COMPLETE THE "STANDARD FEATURES AND
 ACCESSORIES SHEET" AS TO WHAT IS TO BE INSTALLED.
  
 3.PLAN SHEET E2 INDICATES THE GENERATOR EXHAUST TO
 OPEN AIR AT THE ROOF OF COVERED PARKING.PLEASE
 PROVIDE THE FOLLOWING INFORMATION:
 A) WHAT TYPE OF MATERIAL IS THE ROOF, I.E.
 CONCRETE, CANVAS, ETC.
 B) IS THIS A PITCHED OR FLAT ROOF,COMBUSTIBLE OR
 NON-COMBUSTIBLE?
 C) WILL THE EXHAUST PIPING EXTEND ABOVE THE ROOF?
 HOW FAR?
 D) PLEASE SUBMIT MANUFACTURE DETAIL FOR EXTENDING
 THE MUFFLER EXHAUST.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2006-09-19 Cont ID  
Sent By mmclean Date 2006-09-19 Time 14:28 Rev Time 0.00
Received By mmclean Date 2006-09-19 Time 14:28 Sent To  
Notes
2006-09-19 00:00:00DENIED,
 1. PLEASE SUBMIT A COMPLETE
 SURVEY/SITEPLAN OF THE PROPERTY, SHOWING
 THE LOCATION OF THE PROPOSED GENERATOR.
 2. PLEASE PROVIDE THE APPROVED PARKING
 FROM THE CITY OF WEST PALM BEACH AND
 WHAT IS AT THE LOCATION.
 3. THE LOCATION OF THE PROPOSED
 GENERATOR WILL BE TAKING AWAY PARKING,
 NEED INFORMATION TO MAKE SURE THAT THE
 PARKING IS NOT NEEDED BASE ON WHAT HAS
 BEEN APPROVED BY THE CITY OF WEST PALM
 BEACH.
  
 NOTE: THE PROPOSED GENERATOR MUST BE
 SCREEN WITH A LANDSCAPE BUFFER (SEC
 94-444(B).
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720