Plan Review Details - Permit 06080391
| Plan Review Stops For Permit 06080391 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-02-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-02-06 |
Time |
14:50 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2007-02-06 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2007-02-06 14:53:15 | BUILDING PLAN REVIEW | | | PERMIT: 06080391 | | | ADD: 1701 S FLAGLER DR | | | CONT: MILLER ELECTRIC | | | TEL: (305)986-3669 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2NDREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | | THE COURT. | | | NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE | | | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: | | | 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT | | | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | NEW COMMENTS | | | | | | 3) SHEET S-1 DESIGN CRITERIA: | | | CORRECT (B) TO BUILDING CATEGORYIV | | | DESIGNATED EMERGENCY PREPARDNESS, COMMUNICATION, | | | REQUIRED FOR EMERGENCY RESPONSE. | | | IV= 1.15 | | | | | | 4) A W SOLUTIONS STRUCTURAL ANALYSIS AND CALCULATIONS | | | TO BE REVIEWED USING THE | | | CRITERIA LISTED ABOVE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-09-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-09-01 |
Time |
14:47 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2006-09-01 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2006-09-01 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 06080391 | | | ADD: 1701 S FLAGLER DR | | | CONT: MILLER ELEC | | | TEL: (305)986-3669 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 3) 106.1.2* ADDITIONAL INFORMATION | | | REQUIRED, E2 INDICATES A 60KW NATURAL | | | GASS GENERATOR, E3 A 30 KW GENERATOR, | | | AND CUT SHEET FOR A 4 CYCLE DIESEL? | | | | | | 4) PLANS DO NOT INDICATE WHERE NEW | | | CONDUITS WILL BE RUN: | | | 1019.1.2 PENETRATIONS . | | | PENETRATIONS INTO AND OPENINGS THROUGH | | | AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT | | | FOR REQUIRED EXIT DOORS, EQUIPMENT AND | | | DUCTWORK NECESSARY FOR INDEPENDENT | | | PRESSURIZATION, SPRINKLER PIPING, | | | STANDPIPES, ELECTRICAL RACEWAY FOR FIRE | | | DEPARTMENT COMMUNICATION AND ELECTRICAL | | | RACEWAY SERVING THE EXIT ENCLOSURE AND | | | TERMINATING AT A STEEL BOX NOT EXCEEDING | | | 16 SQUARE INCHES (0.010 M 2 ). SUCH | | | PENETRATIONS SHALL BE PROTECTED IN | | | ACCORDANCE WITH SECTION 712 . THERE | | | SHALL BE NO PENETRATIONS OR | | | COMMUNICATION OPENINGS, WHETHER | | | PROTECTED OR NOT, BETWEEN ADJACENT EXIT | | | ENCLOSURES. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-01-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-01-29 |
Time |
12:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-01-29 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2007-01-29 12:07:52 | ***** UNSAT 2ND REVIEW ******* | | | | | | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL | | | IN NEED OF ADDRESSING. | | | PLEASE SEE COMMENTS BELOW WHICH ARE TAKEN DIRECTLY FROM | | | PREVIOUS REVIEW WITH A *NO* OR *OK* IN FRONT OF | | | PREVIOUS NOTE. | | | | | | **IMPORTANT** | | | *PLEASE SEE NEW NOTES NOW ADDED FOR THESE PLANS NOW | | | SUBMITTED. | | | | | | | | | | | | 1) NOTE:NO, PLEASE SEE PERMIT APPLICATION AND SCOPE | | | OF WORK STILL DOES NOT CORRELATE. | | | | | | A) PLEASE SEE SUBMITTALS ARE STILL BEING SUBMITTED | | | (ATTACHED TO OLD PLANS) AS DIESEL AND NATURAL GAS? | | | | | | B) PLEASE SEE TWO DIFFERENT SIZE GENERATOR UNITS ARE | | | BEING SHOWN. | | | | | | C) PLEASE SEE AS STATED PREVIOUSLY ON SITE FUEL IS | | | REQUIRED FOR LEGALLY REQUIRED STAND-BY SYSTEMS. MAY NOT | | | RELY SOLELY ON THE UTILITIES. | | | PLEASE KNOW BASED ON THIS ALONE THIS WILL AFFECT PLANS, | | | AND LOCATION OF TANK REQUIRED. PLEASE ALSO KNOW THAT | | | BASED ON WHETHER OR NOT THE GENERATOR IS NATURAL GAS OR | | | DIESEL, THE FUEL CONSUMPTION SHALL BE STATED FOR | | | MINIMUM TIMES. | | | | | | D) PLEASE KNOW BASED ON *C* ABOVE, THE ON SITE FUEL | | | WILL BE REQUIRED TO BE LOCATED AT THE GROUND FLOOR | | | LEVEL WHICH WILL REQUIRE SITE PLANS, AND PLANS FOR THIS | | | PART OF THE INSTALLATION. | | | NFPA-110 CHAPTER 7 WHICH REQUIRES MORE INFORMATION FOR | | | THE ENTIRE INSTALLATION. ISOLATION FROM STRUCTURE, | | | LOCATION OF FUEL SOURCE ETC. | | | PLEASE SEE 701.11(B)(3) FOR ON-SITE FUEL. | | | PLEASE SEE 110.3, 90.7, 215.5, 240.4 ETC AS THE REVIEW | | | FOR CODE COMPLIANCE CAN NOT BE FULLY ACCOMPLISHED BASED | | | ON THE PERMIT APPLICATION SHOWING ONE SYSTEM, AND THE | | | PLANS AND THE SPECS SHOWING TWO OTHER SYSTEMS. | | | | | | E) PLEASE MEANS OF DISCONNECT AND SHUTTING DOWN POWER | | | ETC CAN NOT BE VERIFIED. 230.70, 230.72 ETC | | | | | | ** PREVIOUS REVIEW NOTE FROM REVIEW #1** | | | PLEASE CORRELATE PLANS, PERMIT APPLICATION AND | | | SUBMITTALS. | | | PLEASE SEE PLANS INDICATE A DIESEL GEN, AND NATURAL GAS | | | GEN. | | | PLEASE KNOW A DIESEL GEN WILL NOT BE PERMITTED ON THE | | | ROOF TOP. PLEASE ALSO KNOW ANY PERMISSION FOR OTHER GEN | | | ON ROOF IS NOT APPROVED AT THIS TIME. PLEASE KNOW A | | | CONFERENCE WITH THE FIRE MARSHAL AND PLAN REVIEW FOR | | | POSSIBILITIES OF THE PERMITTING A NAT GAS GEN MUST BE | | | HELD BEFORE PERMISSION WILL BE GRANTED. SHUT DOWN OF | | | FUEL, GEN , MOTOR AND SHUNT OF FEEDERS MAY ALL BE | | | REQUIRED ON THE GROUND FLOOR OF BLDG. | | | PLEASE KNOW AS MORE THAN ONE SIZE OF GEN AND TYPE FOR | | | PRIME MOVER IS BEING SUBMITTED, A COMPLETE REVIEW CAN | | | NOT BE DONE AT THIS TIME. | | | PLEASE SEE NFPA-110 PLEASE SEE ALL OF CHAPTER 7. PLEASE | | | KNOW, GAS FUEL LINE SHALL NOT BE GALVANIZED 7.9.3.1. | | | PLEASE ALSO SEE 701.11(B)(3) FOR DUEL FUEL SUPPLIES | | | REQUIRED. MAY NOT RELY ONLY ON THE UTILITY. | | | | | | 2) NOTE: OK. | | | | | | 3) NOTE: NO, PLEASE SEE THE VALUE AS SHOWN ON | | | APPLICATION BASED ON THE SCOPE OF WORK IS EXTREMELY LOW | | | AND A VALUE WILL BE ADJUSTED. THIS NEEDS TO INCLUDE ALL | | | STRUCTURAL WORK, GAS/FUEL, TANKS ETC. | | | PLEASE SEE 108.3 | | | | | | **PLEASE KNOW, VALUE FOR COMPLETE | | | SCOPE OF WORK SHALL INCLUDE ALL LABOR | | | AND MATERIALS. AN INSTALLATION OF GAS | | | LINE/ TO ROOF TOP, GEM, ATS ETC. | | | FBC 108.3 | | | | | | 4) NOTE: OK. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-08-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-08-24 |
Time |
18:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-08-24 |
Time |
18:25 |
Sent To |
|
|
| Notes |
| 2006-08-24 00:00:00 | **** UNSAT **** | | | | | | 1) NOTE: PLEASE CORRELATE PLANS, PERMIT APPLICATION AND | | | SUBMITTIALS. | | | PLEASE SEE PLANS INDICATE A DIESEL GEN, | | | AND NATURAL GAS GEN. | | | PLEASE KNOW, A DIESEL GEN WILL NOT BE | | | PERMITTED ON THE ROOF TOP. PLEASE ALSO | | | KNOW ANY PERMISSION FOR OTHER GEN ON | | | ROOF IS NOT APROVED AT THIS TIME. PLEASE | | | KNOW A CONFERENCE WITH THE FIRE MARSHAL | | | AND PLAN REVIEW FOR POSSIBILITIES OF THE PERMITTING A | | | NAT GAS GEN MUST BE HELD | | | BEFORE PERMISSION WILL BE GRANTED. SHUT | | | DOWN OF FUEL, GEN , MOTOR AND SHUNT OF | | | FEEDERS AMY ALL BE REQUIRED ON THE | | | GROUND FLOOR OF BLDG. | | | PLEASE KNOW AS MORE THAN ONE SIZE OF GEN | | | AND TYPE FOR PRIME MOVER IS BEING | | | SUBMITTED, A COMPLETE REVIEW CAN NOT BE | | | DONE AT THIS TIME. | | | PLEASE SEE NFPA-110 PLEASE SEE ALL OF | | | CHAPTER 7. | | | PLEASE KNOW, GAS FUEL LINE SHALL NOT BE | | | GALVANIZED 7.9.3.1. | | | PLEASE ALSO SEE 701.11(B)(3) FOR DUEL | | | FUEL SUPPLIES REQUIRED. MAY NOT RELY | | | ONLY ON THE UTILITY. | | | | | | 2) NOTE: PLEASE BE SURE ALL CURRENT | | | CODES ARE REFLECTED ON PLANS. | | | 2002 NFPA-72, NFPA-70 2002, NFPA-101 | | | 2003, NFPA-110 2002 | | | | | | 3) NOTE: PLEASE KNOW, VALUE FOR COMPLETE | | | SCOPE OF WORK SHALL INCLUDE ALL LABOUR | | | AND MATERIALS. AN INSTALLATION OF GAS | | | LINE/ TO ROOF TOP, GEM, ATS ETC. | | | FBC 108.3 | | | | | | 4) NOTE: PLEASE SUPPLY LOAD CALCULATIONS | | | FOR INENDED LOADS. | | | 701.6 | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-02-23 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-02-23 |
Time |
17:15 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-02-23 |
Time |
17:15 |
Sent To |
|
|
| Notes |
| 2007-02-23 17:18:59 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | | REVIEW STILL NEED TO BE ADDRESSED: | | | | | | | | | 2.)THE LOCATION OF EQUIPMENT SHALL NOT HINDER, | | | IMPEDE, OR OBSTRUCT ENTRANCE AND/OR EXITING TO ROOF. | | | | | | 3.)HOW WILL THE UTILITY LINES AS WELL AS FUEL | | | (DIESEL) BE SUPPLIED TO THE GENERATOR.PLEASE BE | | | ADVISED THAT PENETRATIONS INTO, AND OPENINGS THROUGH, | | | AN EXIT ENCLOSURE (FIRE RATED STAIRWELL) SHALL BE | | | LIMITED AS PER NFPA 101, CH. 7, SECTION 7.1.3.2.1 (6). | | | | | | 4.)WHAT IS THE FIRE RATING OF THE ROOF? | | | | | | 5.)IN RELATION TO EXHAUST FUMES, WHAT ARE THE | | | DISTANCES TO SURROUNDING ROOF TOP UNIT (RTU) INTAKE | | | AIR? | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-10-13 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2006-10-13 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2006-10-13 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2006-10-13 15:25:51 | *****DENIED***** | | | | | | | | | | | | | | | 1.)NFPA 101, 2003 EDITION SHALL BE REFERENCED. | | | | | | 2.)LOCATION OF STRUCTURE SHALL NOT HINDER, IMPEDE, OR | | | OBSTRUCT ENTRANCE AND/OR EXITING TO ROOF. | | | | | | 3.)HOW WILL THE UTILITY LINES AS WELL AS FUEL | | | (DIESEL) BE SUPPLIED TO THE GENERATOR.PLEASE BE | | | ADVISED THAT PENETRATIONS INTO, AND OPENINGS THROUGH, | | | AN EXIT ENCLOSURE (FIRE RATED STAIRWELL) SHALL BE | | | LIMITED AS PER NFPA 101, CH. 7, SECTION 7.1.3.2.1 (6). | | | | | | 4.)WHAT IS THE FIRE RATING OF THE ROOF? | | | | | | 5.)IN RELATION TO EXHAUST FUMES, WHAT ARE THE | | | DISTANCES TO SURROUNDING ROOF TOP UNIT (RTU) INTAKE | | | AIR? | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FUEL |
DIESEL GENERATOR |
| Rev No |
1 |
Status |
F |
Date |
2006-10-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-10-17 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-10-17 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2006-10-17 13:48:47 | DENIED: | | | PLANS INDICATE NATURAL GAS GENERATOR WHEREAS THE | | | MANUFACTURE SUBMITTAL ON THE GENERATOR IS FOR A DIESEL | | | GENERATOR. | | | | | | PLEASE NOTE, SHOULD THE NATURAL GAS GENERATOR BE | | | INSTALLED A GAS PERMIT WILL BE REQUIRED INSTEAD OF A | | | FUEL PERMIT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (561)805-6719. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2007-02-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-02-14 |
Time |
17:44 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-02-14 |
Time |
17:44 |
Sent To |
|
|
| Notes |
| 2007-02-14 17:51:04 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | | | | FROM PREVIOUS REVIEW: | | | | | | A. PLANS INDICATE NATURAL GAS FUEL, BUT | | | MANUF. SHEETS INDICATE DIESEL FUEL. | | | PLEASE CLARIFY. SECTION 106.1.1. | | | ****CONDITION NOW CHANGED. IS THIS A NATURAL GAS | | | GENERATOR, A DIESEL GENERATOR, OR A BI-FUEL GENERATOR?? | | | PLEASE INDICATE ON PLANS. | | | | | | B. IF NATURAL GAS FUEL, PLEASE SUBMIT | | | THE FOLLOWING INFORMATION: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | ****CONDITION CHANGED. NOW THE GAS IS CONNECTED TO THE | | | EXISTING GAS PIPING INSIDE THE BUILDING. THE ISOMETRIC | | | SHALL SHOW ALL PIPING FROM THE METER TO THE GENERATOR. | | | INDICATE THE TOTAL DEVELOPED LENGTH, TOTAL BTU LOAD ON | | | THE SYSTEM, AND INDICATE ALL PIPE SIZES. | | | | | | 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | INSTALLATION INSTRUCTION REQUIRED TO | | | INDICATE CLEARANCES REQUIRED FOR | | | SERVICING ETC. | | | ****THE MAXIMUM BTU LOAD SHALL BE INDICATED ON THE | | | MANUF SPECIFICATION SHEETS. THIS IS NOT INDICATED . | | | | | | 3. SUBMIT MANUF. SPECIFICATION SHEETS | | | FOR 2PSI TO 1/2PSI REGULATOR. INDICATE | | | MODEL NUMBER. | | | ****NOT ADDRESSED. NO RESPONSE. | | | | | | 4. 2 PSI TABLE 402.4(3) ONLY GIVES | | | INFORMATION UP TO 200'. SEE ATTACHED | | | FORMULA, (WEYMOUTH). SUBMIT CALCULATIONS | | | SHOWING BTU'S ALLOWED FOR 375' TO | | | COMFIRM PIPE SIZE FOR GENERATOR. | | | ****NOT ADDRESSED. NO RESPONSE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6713 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2006-09-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-09-01 |
Time |
08:19 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-08-31 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2006-09-01 00:00:00 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | | | | A. PLANS INDICATE NATURAL GAS FUEL, BUT | | | MANUF. SHEETS INDICATE DIESEL FUEL. | | | PLEASE CLARIFY. SECTION 106.1.1. | | | | | | B. IF NATURAL GAS FUEL, PLEASE SUBMIT | | | THE FOLLOWING INFORMATION: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. | | | | | | 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | INSTALLATION INSTRUCTION REQUIRED TO | | | INDICATE CLEARANCES REQUIRED FOR | | | SERVICING ETC. | | | | | | 3. SUBMIT MANUF. SPECIFICATION SHEETS | | | FOR 2PSI TO 1/2PSI REGULATOR. INDICATE | | | MODEL NUMBER. | | | | | | 4. 2 PSI TABLE 402.4(3) ONLY GIVES | | | INFORMATION UP TO 200'. SEE ATTACHED | | | FORMULA, (WEYMOUTH). SUBMIT CALCULATIONS | | | SHOWING BTU'S ALLOWED FOR 375' TO | | | COMFIRM PIPE SIZE FOR GENERATOR. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6713 | | | E-MAIL [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-01-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-17 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-17 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2007-01-24 09:08:49 | TO "COMM" BD#24 | | 2007-01-17 16:50:58 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-10-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-10-17 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-08-08 |
Time |
16:15 |
Sent To |
|
|
| Notes |
| 2006-08-22 00:00:00 | TO "COMM" BD#64 | | 2006-08-08 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-02-21 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-02-21 |
Time |
16:45 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-02-21 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2007-02-21 16:47:07 | *** DENIED *** | | | 1) SEE REVIEW NOTES BY OTHER REVIEWERS, PLEASE | | | CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-10-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-10-17 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-10-17 |
Time |
13:49 |
Sent To |
|
|
| Notes |
| 2006-10-17 14:19:52 | DENIED: | | | 1.PLANS INDICATE GAS GENERATOR.THE MANUFACTURE | | | SUBMITTAL DATA ALSO INCLUDES SUBMITTAL FOR A NATURAL | | | GAS OR LP GENERATOR.PLEASE CORRELATE AND REMOVE | | | SUBMITTAL THAT DOES NOT APPLY TO THIS PROJECT. | | | | | | 2.PLEASE COMPLETE THE "STANDARD FEATURES AND | | | ACCESSORIES" SHEET IN THE SUBMITTAL PACKAGE THAT WILL | | | PERTAIN TO THIS INSTALLATION. | | | | | | 3.PLAN SHEET E2 INDICATES NEW GENERATOR TO BE | | | INSTALLED ON "EXISTING EQUIPMENT PLATFORM".PLEASE | | | PROVIDE ELEVATION FROM GRADE. | | | | | | 4.PLAN SHEET S3 INDICATES NEW GENERATOR LOCATED ON | | | ROOF.PLEASE INDICATE THE FOLLOWING: | | | A) HEIGHT OF PARAPET WALL | | | B) INDICATE ACCESS TO ROOF | | | C) CLEARANCES FROM FRESH AIR INTAKES, WINDOWS, | | | DOORS OR COMBUSTIBLE CONSTRUCTION. | | | | | | 5.PLEASE CLARIFY WHAT "EXISTING CABINET" REPRESENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (561)805-6719 OR E-MAIL [email protected]. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-01-29 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2007-01-29 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2007-01-29 |
Time |
09:11 |
Sent To |
E |
|
| Notes |
| 2007-01-29 09:13:00 | DENIED, | | | 1. SEE ELECTRICAL COMMENTS REGARDING THE TYPE OF | | | GENERATOR AND LOCATION OF TANK. | | | 2. BASE ON THE TYPE OF GENERATOR, THE TANK AND | | | GENERATOR WILL NEED TO BE LOCATED ON GROUND FLOOR. | | | 3. PLEASE PROVIDE A COMPLETE SITEPLAN SHOWING THE | | | LOCATION OF THE PROPOSED GENERATOR AND FUEL TANK. | | | 4. PLEASE SHOW ON THE TWO COPIES OF SITEPLAN/SURVEYS | | | THE LOCATION WITH SETBACKS. | | | | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2006-09-19 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-09-19 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-09-19 |
Time |
13:47 |
Sent To |
|
|
| Notes |
|
|
|