Plan Review Details - Permit 06080391
Plan Review Stops For Permit 06080391
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-06 Cont ID  
Sent By jwitmer Date 2007-02-06 Time 14:50 Rev Time 0.77
Received By jwitmer Date 2007-02-06 Time 14:49 Sent To  
Notes
2007-02-06 14:53:15BUILDING PLAN REVIEW
 PERMIT: 06080391
 ADD: 1701 S FLAGLER DR
 CONT: MILLER ELECTRIC
 TEL: (305)986-3669
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 NEW COMMENTS
  
 3) SHEET S-1 DESIGN CRITERIA:
 CORRECT (B) TO BUILDING CATEGORYIV
 DESIGNATED EMERGENCY PREPARDNESS, COMMUNICATION,
 REQUIRED FOR EMERGENCY RESPONSE.
 IV= 1.15
  
 4) A W SOLUTIONS STRUCTURAL ANALYSIS AND CALCULATIONS
 TO BE REVIEWED USING THE
 CRITERIA LISTED ABOVE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-01 Cont ID  
Sent By jwitmer Date 2006-09-01 Time 14:47 Rev Time 1.33
Received By jwitmer Date 2006-09-01 Time 14:47 Sent To  
Notes
2006-09-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06080391
 ADD: 1701 S FLAGLER DR
 CONT: MILLER ELEC
 TEL: (305)986-3669
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) 106.1.2* ADDITIONAL INFORMATION
 REQUIRED, E2 INDICATES A 60KW NATURAL
 GASS GENERATOR, E3 A 30 KW GENERATOR,
 AND CUT SHEET FOR A 4 CYCLE DIESEL?
  
 4) PLANS DO NOT INDICATE WHERE NEW
 CONDUITS WILL BE RUN:
 1019.1.2 PENETRATIONS .
 PENETRATIONS INTO AND OPENINGS THROUGH
 AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT
 FOR REQUIRED EXIT DOORS, EQUIPMENT AND
 DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE
 DEPARTMENT COMMUNICATION AND ELECTRICAL
 RACEWAY SERVING THE EXIT ENCLOSURE AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M 2 ). SUCH
 PENETRATIONS SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 712 . THERE
 SHALL BE NO PENETRATIONS OR
 COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT
 ENCLOSURES.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-29 Cont ID  
Sent By dpalmer Date 2007-01-29 Time 12:07 Rev Time 0.00
Received By dpalmer Date 2007-01-29 Time 10:29 Sent To  
Notes
2007-01-29 12:07:52***** UNSAT 2ND REVIEW *******
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
 PLEASE SEE COMMENTS BELOW WHICH ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A *NO* OR *OK* IN FRONT OF
 PREVIOUS NOTE.
  
 **IMPORTANT**
 *PLEASE SEE NEW NOTES NOW ADDED FOR THESE PLANS NOW
 SUBMITTED.
  
  
  
 1) NOTE:NO, PLEASE SEE PERMIT APPLICATION AND SCOPE
 OF WORK STILL DOES NOT CORRELATE.
  
 A) PLEASE SEE SUBMITTALS ARE STILL BEING SUBMITTED
 (ATTACHED TO OLD PLANS) AS DIESEL AND NATURAL GAS?
  
 B) PLEASE SEE TWO DIFFERENT SIZE GENERATOR UNITS ARE
 BEING SHOWN.
  
 C) PLEASE SEE AS STATED PREVIOUSLY ON SITE FUEL IS
 REQUIRED FOR LEGALLY REQUIRED STAND-BY SYSTEMS. MAY NOT
 RELY SOLELY ON THE UTILITIES.
 PLEASE KNOW BASED ON THIS ALONE THIS WILL AFFECT PLANS,
 AND LOCATION OF TANK REQUIRED. PLEASE ALSO KNOW THAT
 BASED ON WHETHER OR NOT THE GENERATOR IS NATURAL GAS OR
 DIESEL, THE FUEL CONSUMPTION SHALL BE STATED FOR
 MINIMUM TIMES.
  
 D) PLEASE KNOW BASED ON *C* ABOVE, THE ON SITE FUEL
 WILL BE REQUIRED TO BE LOCATED AT THE GROUND FLOOR
 LEVEL WHICH WILL REQUIRE SITE PLANS, AND PLANS FOR THIS
 PART OF THE INSTALLATION.
 NFPA-110 CHAPTER 7 WHICH REQUIRES MORE INFORMATION FOR
 THE ENTIRE INSTALLATION. ISOLATION FROM STRUCTURE,
 LOCATION OF FUEL SOURCE ETC.
 PLEASE SEE 701.11(B)(3) FOR ON-SITE FUEL.
 PLEASE SEE 110.3, 90.7, 215.5, 240.4 ETC AS THE REVIEW
 FOR CODE COMPLIANCE CAN NOT BE FULLY ACCOMPLISHED BASED
 ON THE PERMIT APPLICATION SHOWING ONE SYSTEM, AND THE
 PLANS AND THE SPECS SHOWING TWO OTHER SYSTEMS.
  
 E) PLEASE MEANS OF DISCONNECT AND SHUTTING DOWN POWER
 ETC CAN NOT BE VERIFIED. 230.70, 230.72 ETC
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1**
 PLEASE CORRELATE PLANS, PERMIT APPLICATION AND
 SUBMITTALS.
 PLEASE SEE PLANS INDICATE A DIESEL GEN, AND NATURAL GAS
 GEN.
 PLEASE KNOW A DIESEL GEN WILL NOT BE PERMITTED ON THE
 ROOF TOP. PLEASE ALSO KNOW ANY PERMISSION FOR OTHER GEN
 ON ROOF IS NOT APPROVED AT THIS TIME. PLEASE KNOW A
 CONFERENCE WITH THE FIRE MARSHAL AND PLAN REVIEW FOR
 POSSIBILITIES OF THE PERMITTING A NAT GAS GEN MUST BE
 HELD BEFORE PERMISSION WILL BE GRANTED. SHUT DOWN OF
 FUEL, GEN , MOTOR AND SHUNT OF FEEDERS MAY ALL BE
 REQUIRED ON THE GROUND FLOOR OF BLDG.
 PLEASE KNOW AS MORE THAN ONE SIZE OF GEN AND TYPE FOR
 PRIME MOVER IS BEING SUBMITTED, A COMPLETE REVIEW CAN
 NOT BE DONE AT THIS TIME.
 PLEASE SEE NFPA-110 PLEASE SEE ALL OF CHAPTER 7. PLEASE
 KNOW, GAS FUEL LINE SHALL NOT BE GALVANIZED 7.9.3.1.
 PLEASE ALSO SEE 701.11(B)(3) FOR DUEL FUEL SUPPLIES
 REQUIRED. MAY NOT RELY ONLY ON THE UTILITY.
  
 2) NOTE: OK.
  
 3) NOTE: NO, PLEASE SEE THE VALUE AS SHOWN ON
 APPLICATION BASED ON THE SCOPE OF WORK IS EXTREMELY LOW
 AND A VALUE WILL BE ADJUSTED. THIS NEEDS TO INCLUDE ALL
 STRUCTURAL WORK, GAS/FUEL, TANKS ETC.
 PLEASE SEE 108.3
  
 **PLEASE KNOW, VALUE FOR COMPLETE
 SCOPE OF WORK SHALL INCLUDE ALL LABOR
 AND MATERIALS. AN INSTALLATION OF GAS
 LINE/ TO ROOF TOP, GEM, ATS ETC.
 FBC 108.3
  
 4) NOTE: OK.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-24 Cont ID  
Sent By dpalmer Date 2006-08-24 Time 18:42 Rev Time 0.00
Received By dpalmer Date 2006-08-24 Time 18:25 Sent To  
Notes
2006-08-24 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE CORRELATE PLANS, PERMIT APPLICATION AND
 SUBMITTIALS.
 PLEASE SEE PLANS INDICATE A DIESEL GEN,
 AND NATURAL GAS GEN.
 PLEASE KNOW, A DIESEL GEN WILL NOT BE
 PERMITTED ON THE ROOF TOP. PLEASE ALSO
 KNOW ANY PERMISSION FOR OTHER GEN ON
 ROOF IS NOT APROVED AT THIS TIME. PLEASE
 KNOW A CONFERENCE WITH THE FIRE MARSHAL
 AND PLAN REVIEW FOR POSSIBILITIES OF THE PERMITTING A
 NAT GAS GEN MUST BE HELD
 BEFORE PERMISSION WILL BE GRANTED. SHUT
 DOWN OF FUEL, GEN , MOTOR AND SHUNT OF
 FEEDERS AMY ALL BE REQUIRED ON THE
 GROUND FLOOR OF BLDG.
 PLEASE KNOW AS MORE THAN ONE SIZE OF GEN
 AND TYPE FOR PRIME MOVER IS BEING
 SUBMITTED, A COMPLETE REVIEW CAN NOT BE
 DONE AT THIS TIME.
 PLEASE SEE NFPA-110 PLEASE SEE ALL OF
 CHAPTER 7.
 PLEASE KNOW, GAS FUEL LINE SHALL NOT BE
 GALVANIZED 7.9.3.1.
 PLEASE ALSO SEE 701.11(B)(3) FOR DUEL
 FUEL SUPPLIES REQUIRED. MAY NOT RELY
 ONLY ON THE UTILITY.
  
 2) NOTE: PLEASE BE SURE ALL CURRENT
 CODES ARE REFLECTED ON PLANS.
 2002 NFPA-72, NFPA-70 2002, NFPA-101
 2003, NFPA-110 2002
  
 3) NOTE: PLEASE KNOW, VALUE FOR COMPLETE
 SCOPE OF WORK SHALL INCLUDE ALL LABOUR
 AND MATERIALS. AN INSTALLATION OF GAS
 LINE/ TO ROOF TOP, GEM, ATS ETC.
 FBC 108.3
  
 4) NOTE: PLEASE SUPPLY LOAD CALCULATIONS
 FOR INENDED LOADS.
 701.6
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-02-23 Cont ID  
Sent By mawillia Date 2007-02-23 Time 17:15 Rev Time 0.00
Received By mawillia Date 2007-02-23 Time 17:15 Sent To  
Notes
2007-02-23 17:18:59*****DENIED*****
  
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
  
 2.)THE LOCATION OF EQUIPMENT SHALL NOT HINDER,
 IMPEDE, OR OBSTRUCT ENTRANCE AND/OR EXITING TO ROOF.
  
 3.)HOW WILL THE UTILITY LINES AS WELL AS FUEL
 (DIESEL) BE SUPPLIED TO THE GENERATOR.PLEASE BE
 ADVISED THAT PENETRATIONS INTO, AND OPENINGS THROUGH,
 AN EXIT ENCLOSURE (FIRE RATED STAIRWELL) SHALL BE
 LIMITED AS PER NFPA 101, CH. 7, SECTION 7.1.3.2.1 (6).
  
 4.)WHAT IS THE FIRE RATING OF THE ROOF?
  
 5.)IN RELATION TO EXHAUST FUMES, WHAT ARE THE
 DISTANCES TO SURROUNDING ROOF TOP UNIT (RTU) INTAKE
 AIR?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-10-13 Cont ID  
Sent By mawillia Date 2006-10-13 Time 14:48 Rev Time 0.00
Received By mawillia Date 2006-10-13 Time 14:48 Sent To  
Notes
2006-10-13 15:25:51*****DENIED*****
  
  
  
  
 1.)NFPA 101, 2003 EDITION SHALL BE REFERENCED.
  
 2.)LOCATION OF STRUCTURE SHALL NOT HINDER, IMPEDE, OR
 OBSTRUCT ENTRANCE AND/OR EXITING TO ROOF.
  
 3.)HOW WILL THE UTILITY LINES AS WELL AS FUEL
 (DIESEL) BE SUPPLIED TO THE GENERATOR.PLEASE BE
 ADVISED THAT PENETRATIONS INTO, AND OPENINGS THROUGH,
 AN EXIT ENCLOSURE (FIRE RATED STAIRWELL) SHALL BE
 LIMITED AS PER NFPA 101, CH. 7, SECTION 7.1.3.2.1 (6).
  
 4.)WHAT IS THE FIRE RATING OF THE ROOF?
  
 5.)IN RELATION TO EXHAUST FUMES, WHAT ARE THE
 DISTANCES TO SURROUNDING ROOF TOP UNIT (RTU) INTAKE
 AIR?
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2006-10-17 Cont ID  
Sent By pkrauss Date 2006-10-17 Time 13:45 Rev Time 0.00
Received By pkrauss Date 2006-10-17 Time 13:45 Sent To  
Notes
2006-10-17 13:48:47DENIED:
 PLANS INDICATE NATURAL GAS GENERATOR WHEREAS THE
 MANUFACTURE SUBMITTAL ON THE GENERATOR IS FOR A DIESEL
 GENERATOR.
  
 PLEASE NOTE, SHOULD THE NATURAL GAS GENERATOR BE
 INSTALLED A GAS PERMIT WILL BE REQUIRED INSTEAD OF A
 FUEL PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-02-14 Cont ID  
Sent By kstevens Date 2007-02-14 Time 17:44 Rev Time 0.00
Received By kstevens Date 2007-02-14 Time 17:44 Sent To  
Notes
2007-02-14 17:51:04DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 FROM PREVIOUS REVIEW:
  
 A. PLANS INDICATE NATURAL GAS FUEL, BUT
 MANUF. SHEETS INDICATE DIESEL FUEL.
 PLEASE CLARIFY. SECTION 106.1.1.
 ****CONDITION NOW CHANGED. IS THIS A NATURAL GAS
 GENERATOR, A DIESEL GENERATOR, OR A BI-FUEL GENERATOR??
 PLEASE INDICATE ON PLANS.
  
 B. IF NATURAL GAS FUEL, PLEASE SUBMIT
 THE FOLLOWING INFORMATION:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****CONDITION CHANGED. NOW THE GAS IS CONNECTED TO THE
 EXISTING GAS PIPING INSIDE THE BUILDING. THE ISOMETRIC
 SHALL SHOW ALL PIPING FROM THE METER TO THE GENERATOR.
 INDICATE THE TOTAL DEVELOPED LENGTH, TOTAL BTU LOAD ON
 THE SYSTEM, AND INDICATE ALL PIPE SIZES.
  
 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 INSTALLATION INSTRUCTION REQUIRED TO
 INDICATE CLEARANCES REQUIRED FOR
 SERVICING ETC.
 ****THE MAXIMUM BTU LOAD SHALL BE INDICATED ON THE
 MANUF SPECIFICATION SHEETS. THIS IS NOT INDICATED .
  
 3. SUBMIT MANUF. SPECIFICATION SHEETS
 FOR 2PSI TO 1/2PSI REGULATOR. INDICATE
 MODEL NUMBER.
 ****NOT ADDRESSED. NO RESPONSE.
  
 4. 2 PSI TABLE 402.4(3) ONLY GIVES
 INFORMATION UP TO 200'. SEE ATTACHED
 FORMULA, (WEYMOUTH). SUBMIT CALCULATIONS
 SHOWING BTU'S ALLOWED FOR 375' TO
 COMFIRM PIPE SIZE FOR GENERATOR.
 ****NOT ADDRESSED. NO RESPONSE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-09-01 Cont ID  
Sent By kstevens Date 2006-09-01 Time 08:19 Rev Time 0.00
Received By kstevens Date 2006-08-31 Time 16:50 Sent To  
Notes
2006-09-01 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 A. PLANS INDICATE NATURAL GAS FUEL, BUT
 MANUF. SHEETS INDICATE DIESEL FUEL.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 B. IF NATURAL GAS FUEL, PLEASE SUBMIT
 THE FOLLOWING INFORMATION:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 INSTALLATION INSTRUCTION REQUIRED TO
 INDICATE CLEARANCES REQUIRED FOR
 SERVICING ETC.
  
 3. SUBMIT MANUF. SPECIFICATION SHEETS
 FOR 2PSI TO 1/2PSI REGULATOR. INDICATE
 MODEL NUMBER.
  
 4. 2 PSI TABLE 402.4(3) ONLY GIVES
 INFORMATION UP TO 200'. SEE ATTACHED
 FORMULA, (WEYMOUTH). SUBMIT CALCULATIONS
 SHOWING BTU'S ALLOWED FOR 375' TO
 COMFIRM PIPE SIZE FOR GENERATOR.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-01-17 Cont ID  
Sent By adarroug Date 2007-01-17 Time 16:50 Rev Time 0.00
Received By adarroug Date 2007-01-17 Time 16:50 Sent To  
Notes
2007-01-24 09:08:49TO "COMM" BD#24
2007-01-17 16:50:58WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-10-17 Cont ID  
Sent By pkrauss Date 2006-10-17 Time 14:20 Rev Time 0.00
Received By pkrauss Date 2006-08-08 Time 16:15 Sent To  
Notes
2006-08-22 00:00:00TO "COMM" BD#64
2006-08-08 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-02-21 Cont ID  
Sent By tgordon Date 2007-02-21 Time 16:45 Rev Time 0.30
Received By tgordon Date 2007-02-21 Time 16:45 Sent To  
Notes
2007-02-21 16:47:07*** DENIED ***
 1) SEE REVIEW NOTES BY OTHER REVIEWERS, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-10-17 Cont ID  
Sent By pkrauss Date 2006-10-17 Time 13:53 Rev Time 0.00
Received By pkrauss Date 2006-10-17 Time 13:49 Sent To  
Notes
2006-10-17 14:19:52DENIED:
 1.PLANS INDICATE GAS GENERATOR.THE MANUFACTURE
 SUBMITTAL DATA ALSO INCLUDES SUBMITTAL FOR A NATURAL
 GAS OR LP GENERATOR.PLEASE CORRELATE AND REMOVE
 SUBMITTAL THAT DOES NOT APPLY TO THIS PROJECT.
  
 2.PLEASE COMPLETE THE "STANDARD FEATURES AND
 ACCESSORIES" SHEET IN THE SUBMITTAL PACKAGE THAT WILL
 PERTAIN TO THIS INSTALLATION.
  
 3.PLAN SHEET E2 INDICATES NEW GENERATOR TO BE
 INSTALLED ON "EXISTING EQUIPMENT PLATFORM".PLEASE
 PROVIDE ELEVATION FROM GRADE.
  
 4.PLAN SHEET S3 INDICATES NEW GENERATOR LOCATED ON
 ROOF.PLEASE INDICATE THE FOLLOWING:
 A) HEIGHT OF PARAPET WALL
 B) INDICATE ACCESS TO ROOF
 C) CLEARANCES FROM FRESH AIR INTAKES, WINDOWS,
 DOORS OR COMBUSTIBLE CONSTRUCTION.
  
 5.PLEASE CLARIFY WHAT "EXISTING CABINET" REPRESENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop Z ZONING
Rev No 2 Status F Date 2007-01-29 Cont ID  
Sent By mmclean Date 2007-01-29 Time 09:11 Rev Time 0.00
Received By mmclean Date 2007-01-29 Time 09:11 Sent To E
Notes
2007-01-29 09:13:00DENIED,
 1. SEE ELECTRICAL COMMENTS REGARDING THE TYPE OF
 GENERATOR AND LOCATION OF TANK.
 2. BASE ON THE TYPE OF GENERATOR, THE TANK AND
 GENERATOR WILL NEED TO BE LOCATED ON GROUND FLOOR.
 3. PLEASE PROVIDE A COMPLETE SITEPLAN SHOWING THE
 LOCATION OF THE PROPOSED GENERATOR AND FUEL TANK.
 4. PLEASE SHOW ON THE TWO COPIES OF SITEPLAN/SURVEYS
 THE LOCATION WITH SETBACKS.
  
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status P Date 2006-09-19 Cont ID  
Sent By mmclean Date 2006-09-19 Time 13:47 Rev Time 0.00
Received By mmclean Date 2006-09-19 Time 13:47 Sent To  
Notes
***NONE***