| 2006-08-04 00:00:00 | 1) THIS ROOF IS MISSING OR NOT IN |
| | COMPLIANCE WITH THE FOLLOW ITEMS: |
| | |
| | _XX__ THE SYSTEM PROVIDED HAS A LOW |
| | PRESSURE FOR ZONE 2/_3__ . |
| | |
| | ___ THE SYSTEM PROVIDED STATES |
| | LIMITATION# 7, SHOULD THE FASTENER |
| | RESISTANCE BE LESS THAN THAT |
| | REQUIRED, AS DETERMINED BY THE |
| | BUILDING OFFICIAL, A REVISED |
| | FASTENER SPACING, PREPARED , SIGNED |
| | AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER, REGISTERED |
| | ARCHITECT OR REGISTERED ROOF |
| | CONSULTANT MAY BE SUBMITTED. |
| | |
| | _XX__THE SYSTEM PROVIDED INDICATES |
| | LIMITATION# 9, NO ENHANCED |
| | FASTENING ALLOWED. |
| | |
| | 2) FBC 1609THE SYSTEM SELECTED FROM |
| | THE SUBMITTED FLAT ROOF PRODUCT APPROVAL |
| | NOA HAS A MAXIMUM DESIGN PRESSURE OF |
| | LESS THAN -89 PSF AND CITES GENERAL |
| | LIMITATION #9 (SEE PAGE 39_ OF _45_). |
| | GENERAL LIMITATION #9 PROHIBITS RATIONAL |
| | ANALYSIS OR EXTRAPOLATION TO ENHANCE THE |
| | UPLIFT PRESSURE AT PERIMETER AND CORNER |
| | AREAS BY REDUCING THE FASTENER SPACING |
| | IN THESE AREAS.EITHER SELECT AN |
| | ALTERNATIVE SYSTEM (OR PRODUCT APPROVAL) |
| | THAT DOES NOT CITE GENERAL LIMITATION |
| | #9.ALTERNATIVELY IF THE SELECTED |
| | SYSTEM DOES CITE GENERAL LIMITATION #9, |
| | IT MUST HAVE A MAXIMUM DESIGN PRESSURE |
| | THAT EXCEEDS THE PRESSURE IN ROOF ZONE 3 |
| | (TYPICALLY -89 PSF FOR MEAN ROOF HEIGHT |
| | OF 30 FEET OR LESS). |
| | |
| | 3) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | TEL:(561)805-6726 |
| | |
| | |