Plan Review Details - Permit 06080337
Plan Review Stops For Permit 06080337
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-06-15 Cont ID  
Sent By mjacobs Date 2007-06-15 Time 13:14 Rev Time 0.00
Received By mjacobs Date 2007-06-15 Time 12:46 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-03-03 Cont ID  
Sent By mjacobs Date 2007-03-03 Time 16:56 Rev Time 0.00
Received By mjacobs Date 2007-03-03 Time 14:22 Sent To  
Notes
2007-03-03 14:50:22BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*.PLEASE
 REVIEW THE PRODUCT REPORT AND CIRCLE WHICH ITEM WILL BE
 USED. EXAMPLE: FL 6350, ON SHEET 1 OF 8 WHICH DOOR WILL
 BE USED ETC. EACH PRODUCT APPROVAL SHALL BE APPROVED IN
 WRITING BY THE ARCHITECT. IF A LETTER IS
  
 3)A ROOFING CONTRACTOR WILL HAVE TO APPLY FOR A
 PERMIT TO DO THE ROOFING WORK ON THE PROJECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-13 Cont ID  
Sent By mjacobs Date 2007-01-13 Time 10:35 Rev Time 0.00
Received By mjacobs Date 2007-01-13 Time 06:58 Sent To PC
Notes
2007-01-13 08:33:24BUILDING PLAN REVIEW
 PERMIT:06080337
 ADD:1805TAMARIND AVE
 CONT:
 TEL: (561)822-1252
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)106.1 IF THE DESIGN PPOFISSIONAL IS AN ARCHITECT OR
 ENGINEER LEGALLY REGISTERED UNDER THE LAWS OF THIS
 STATE REGULATING THE PRACTICE OF ARCHITECTURE AS
 PROVIDED FOR IN CHAPTER 481 OR 471 OF THE FLORIDA
 STATUTES,THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA AS REQUIRED BY
 FLORIDA STATUTE.
  
 2)ROOFING PERMIT; ONLY CHECKED ITEMS APPLY
  
 ____1.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13.
  
 _XX___2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING
 INFORMATION ON THE APPLICATION, SEE ATTACHED
 POLICY:MEAN ROOF HEIGHT/ ROOF PITCH / ROOF DECK TYPE /
 AREA OF EACH ROOF TYPE
  
 ____3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED IN ADDITION TO THE EVALUATION REPORT
 SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG
  
 _XX___4.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 IF THE OPTIONS HAVE DIFFERENT PRESSURE LIMITATIONS.
  
 _XX___5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
  
 _XX__ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH
 METHOD OF ATTACHMENT YOU ARE USING.
  
 _XX___ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS
 PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF
 CONSULTANT REQUIRED FOR ENHANCED FASTENING. BUILDING
 PLAN REVIEW
  
  
 NOTE: FBC 1609.6.6.2THE SYSTEM SELECTED
 FROM THE SUBMITTED FLAT ROOF PRODUCT
 APPROVAL NOA HAS A MAXIMUM DESIGN
 PRESSURE OF LESS THAN -89 PSF AND CITES
 GENERAL LIMITATION #9.GENERAL LIMITATION #9
 PROHIBITS
 RATIONAL ANALYSIS OR EXTRAPOLATION TO
 ENHANCE THE UPLIFT PRESSURE AT PERIMETER
 AND CORNER AREAS BY REDUCING THE
 FASTENER SPACING IN THESE AREAS.EITHER
 SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT
 APPROVAL) THAT DOES NOT CITE GENERAL
 LIMITATION #9.ALTERNATIVELY IF THE
 SELECTED SYSTEM DOES CITE GENERAL
 LIMITATION #9, IT MUST HAVE A MAXIMUM
 DESIGN PRESSURE THAT EXCEEDS THE
 PRESSURE IN ROOF ZONE 3 (TYPICALLY -89
 PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR
 LESS).
  
 3)THE PRODUCT APPROVALS ARE MISSING THE FLORIDA STATE
 APPROVAL COVER SHEETS.
  
 4)SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS
 APPLY
  
 ____1.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY
 AN ENGINEER. DOCUMENTS PREPARED BY AN ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED
 ORIGINALS FAC61G15-23.002.
  
 ____2.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.
  
 ____3.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____4.ON THE PRODUCT APPROVAL, MARK WHICH DETAILS
 APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A
 HIGHLIGHTER.
  
 ____5.SHOW THE EMERGENCY MEANS OF ESCAPE,
  
 ____ 6.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 4
 ABOVE.
  
 5)INDICATE THE OCCUPANT LOAD OFF THE BUILDING ON THE
 DRAWINGS. SEE FBC 1004.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-16 Cont ID  
Sent By amorse Date 2006-08-16 Time 13:49 Rev Time 0.00
Received By amorse Date 2006-08-16 Time 13:44 Sent To PC
Notes
2006-08-16 00:00:00 
  
 DENIED
  
 1) A CERTIFICATE OF AUTHORIZATION SHALL
 BE REQUIRED FOR A CORPORATION, LIMITED
 LIABILITY COMPANY, OR PARTNERSHIP,
 OFFERING ARCHITECTURAL SERVICES TO THE
 PUBLIC JOINTLY OR SEPARATELY.
 PER 481.219(2) F.S.
  
 2) PROVIDE OCCUPANCY AND CONSTRUCTION
 TYPE PER 106.3.5 FBC*
  
 3) PROVIDE WIND DESIGN DATA ON DRAWINGS
 PER 1603.1.4 FBC PLEASE INCLUDE THE
 COMPONENT AND CLADDING PRESSURES FOR THE
 OPENINGS
  
 4) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 ***NOTE PRODUCT APPROVALS ARE REQUIRED
 FOR DOORS, WINDOWS, BAHAMA SHUTTERS AND
 ROOF COVERING
  
 5) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 6) WINDOWS AND DOORS UP TO 30 FT ABOVE
 GRADE REQUIRED TO BE LARGE MISSILE
 IMPACT RESISTANT OR REQUIRE SHUTTERS
 (PLEASE SEE CITY THAT IS ENCLOSED AS
 THEIR ARE MORE REQUIREMENTS IF SHUTTERS
 ARE USED)
  
 7) PROVIDE SIZES FOR WINDOWS AND DOORS
 TO BE REPLACED TO CONFIRM DESIGN
 PRESSURES WITH PRODUCT APPROVAL
 PRESSURES
  
 8) PROVIDE INFORMATION ON WINDOW AND
 DOOR BUCK ATTACHMENT AS THIS INFORMATION
 IS ALWAYS STATED AS BY OTHERS ON PRODUCT
 APPROVALS
  
 9) A SEPERATE PERMIT IS REQUIRED FOR
 SIGNS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-12-20 Cont ID  
Sent By btrobaug Date 2006-12-20 Time 10:20 Rev Time 0.33
Received By btrobaug Date 2006-12-20 Time 10:18 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-15 Cont ID  
Sent By btrobaug Date 2006-08-15 Time 07:07 Rev Time 0.33
Received By btrobaug Date 2006-08-15 Time 07:06 Sent To B
Notes
2006-08-15 00:00:00 
  
  
  
 NONCOMPLIANT
  
 THE ARCHITECTURAL FIRM MUST DISPLAY THE
 CERTIFICATE OF AUTHORIZATION ON THE
 TITLE BLOCK PER 481.221 (8).
  
 THERE IS NO ELECTRICAL PLAN FOR THE
 SCOPE OF THIS PROJECT. IF ELECTRICAL
 WORK IS INTENDED PLEASE SUBMIT PLANS PER
 2002 NEC AND ALL REFERENCED DOCUMENTS.
  
 WILLIAM R TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/561) 805-6731

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-06-14 Cont ID  
Sent By adarroug Date 2007-06-14 Time 10:29 Rev Time 0.00
Received By adarroug Date 2007-06-14 Time 10:29 Sent To B
Notes
2007-06-14 10:30:07TO "MJACOBS" DESK/PROJECT TO PERMIT

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-02 Cont ID  
Sent By adarroug Date 2007-03-02 Time 11:03 Rev Time 0.00
Received By adarroug Date 2007-03-02 Time 11:02 Sent To B
Notes
2007-03-02 11:03:17TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-06 Cont ID  
Sent By adarroug Date 2006-12-06 Time 15:00 Rev Time 0.00
Received By adarroug Date 2006-12-06 Time 15:00 Sent To Z
Notes
2006-12-06 15:01:12TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-14 Cont ID  
Sent By adarroug Date 2006-08-14 Time 11:45 Rev Time 0.00
Received By adarroug Date 2006-08-14 Time 11:45 Sent To E
Notes
2006-08-14 00:00:00TO "BTROBAUG" DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-04 Cont ID  
Sent By mmiller Date 2006-08-04 Time 15:02 Rev Time 0.00
Received By mmiller Date 2006-08-04 Time 15:02 Sent To Z
Notes
2006-08-04 00:00:00WAITING FOR COMMERCIAL BOARD

Review Stop Z ZONING
Rev No 2 Status P Date 2006-12-18 Cont ID  
Sent By astelly Date 2006-12-18 Time 09:43 Rev Time 0.00
Received By astelly Date 2006-12-18 Time 09:43 Sent To  
Notes
2006-12-18 09:45:48A SEPARATE PERMIT IS REQUIRED FOR SIGNAGE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-10 Cont ID  
Sent By astelly Date 2006-08-10 Time 13:13 Rev Time 0.00
Received By astelly Date 2006-08-10 Time 13:13 Sent To  
Notes
2006-08-10 00:00:00PLEASE PROVIDE A SURVEY. PROPOSED PAVING
 CANNOTENCROACH UPON RIGHT-OF-WAY.