Plan Review Details - Permit 06080332
Plan Review Stops For Permit 06080332
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-10-16 Cont ID  
Sent By amorse Date 2007-10-16 Time 19:00 Rev Time 0.00
Received By amorse Date 2007-10-16 Time 19:00 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-09-15 Cont ID  
Sent By amorse Date 2007-09-15 Time 16:12 Rev Time 0.00
Received By amorse Date 2007-09-15 Time 16:12 Sent To PC
Notes
2007-09-15 16:31:55 
  
 DENIED
  
 THE FOLLOWING COMMENTS ALL PERTAIN TO PRODUCT
 APPROVALS
  
 1)PROVIDE NEW UPDATED FLORIDA STATE SHEETS (FL#
 251-R7) AND THE REVISEDMIAMI-DADE REPORT # 06-0523.03
 USED FOR CERTIFICATION AS THE SERIESSGD-70 IS NO
 LONGER AVAILABLE AND THE SUBMITTED MIAMI-DADE REPORT
 HAS BEEN SUPERSEDED
  
 2)PROVIDE NEW UPDATED FLORIDA STATEWIDE SHEETS
 (242-R6) AND THE REVISED MIAMI-DADE REPORT # 06-0405.06
 USED FOR CERTIFICATION
  
 3)PROVIDE THE FLORIDA STATEWIDE PRODUCT APPROVALS FOR
 THE FRENCH DOORS (235-R6) AND THE MIAMI-DADE REPORT #
 06-0807.07 (IMPACT) OR # 07-0309.09 (NON-IMPACT) THAT
 IS USED FOR CERTIFICATION. PLEASE BE AWARE THAT THE
 PRODUCT THAT YOU SUBMITTED IS NON IMPACT AND SHUTTER
 PRODUCT APPROVALS WILL BE REQUIRED.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-06-23 Cont ID  
Sent By amorse Date 2007-06-23 Time 17:21 Rev Time 0.00
Received By amorse Date 2007-06-23 Time 17:21 Sent To PC
Notes
2007-06-23 17:41:51 
  
 DENIED
  
 PRODUCT APPROVALS ARE INCOMPLETE
  
 1)THERMA-TRU "BENCHMARK" SERIES DOOR NOA HAS EXPIRED
 ALSO IT IS FOR DOORS WITH SIDELITES OF WHICH THEIR ARE
 NONE PRESENT ON THE DRAWINGS. PROVIDE PRODUCT APPROVAL
 FOR THE HOLLOW METAL ENTRY DOOR.
  
 2)PROVIDE PRODUCT APPROVAL FOR THE FRENCH DOORS SHOWN
 ON THE ELEVATION DRAWINGS (STATED AS PGT) THE FLORIDA
 APPROVAL SUBMITTED FOR THERMA-TRU (FL# 5262) IS NOT FOR
 THE ABOVE DOOR AND CANNOT BE USED FOR GLAZED DOORS SUCH
 AS THE FRENCH DOORS.
  
 3)PROVIDE PRODUCT APPROVALS FOR THE CASTCRETE
 LINTELS.
  
 4)PROVIDE PRODUCT APPROVALS FOR THE HURRICANE
 STRAPS/ANCHORS/TIES OR PROVIDE AN INDEX WITH ALL STRAPS
 TO BE USED AND THERE FL#'S
  
 5)PROVIDE THE FLORIDA STATEWIDE PRODUCT APPROVAL FOR
 THE HANSON ROOF TILE ( FL# 3506)
  
 6)THE FEES FOR THE INCREASED VALUE AND RADON WHERE
 NOT PAID IN THE AMOUNT OF $581.75 ,THIS IS REQUIRED TO
 BE PAID IN FULL BEFORE FURTHER PLAN REVIEW IS
 PERFORMED.
  
 7)THIS WAS THE 2ND RESUB AND IS NOT FREE CHARGES FOR
 THIS AND FUTURE RESUBS WILL BE CHARGED.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-04-21 Cont ID  
Sent By amorse Date 2007-04-21 Time 06:15 Rev Time 0.00
Received By amorse Date 2007-04-21 Time 06:15 Sent To PC
Notes
2007-04-19 19:07:23 
  
 DENIED
  
 THE FOLLOWING PLAN REVIEW NOTES WERE NOT ADDRESSED:
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL (561)
 233-5025 FOR MORE
 INFORMATION.
  
 5)THE MIN SOIL BEARING CAPACITY THAT IS REQUIRED BY
 THE DESIGNER (2500 PSF) AND THE SOIL BEARING CAPACITY
 IN THE SOIL REPORT (2000 PSF) DO NOT MATCH *****PER
 106.1.3 FBC* THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS "NO WHITE OUT, PENCIL OR INK" ***
  
 7 & 9) THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES
 OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD INCLUDE THE FLORIDA
 STATE APPROVAL COVER PAGES, AND THE PRODUCT NOA THAT
 LISTS THE SYSTEM COMPONENTS/ FASTENER LIST PAGES, THE
 PAGES WITH THE CHOSEN ASSEMBLY/ SYSTEM TO BE USED AND
 THE GENERAL LIMITATIONS PAGE. ALL CAN BE FOUND ON
 WWW.FLORIDABUILDING.ORG
 ********THE CITY OF WEST PALM BEACH REQUIRES THE
 FLORIDA STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED******* PLEASE SEE
 EXAMPLE FOR YOUR PGT HORIZONTAL SLIDERS ENCLOSED.
 FLORIDA PRODUCT APPROVAL NUMBERS ARE MARKED ON THE
 NOA'S SOME OF THE NOA'S ARE OUTDATED ALSO
  
 11)THE FOLLOWING PRODUCT APPROVALS ARE MISSING FROM
 THE PACKAGE
 ***** STILL REQUIRE PRE CAST LINTELS AND HURRICANE
 ANCHORS/TIESAND ALSO REQUIRED FOR PGT FRENCH
 DOORS*****
  
 12)SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
 ****THE TRUSS DRAWINGS MUST BE SUBMITTED PRIOR TO
 SETTING OF TRUSSES*****
  
 15)PROVIDE ATTIC ACCESS ON DRAWINGS TO ALL AREAS AS
 REQUIRED PER R807.1 FBC RES.
 *****PLEASE NOTE THAT ALL ROOF AREAS MUST BE ACCESSED
 LEAVE OPENING IN PLYWOOD WHERE ROOF TRUSSES
 INTERSECT*****
  
 16)PROVIDE MIN ROOF SHEATHING ATTACHMENT
 PER TABLE 2304.9.1 FBC
 *****SECTION R803.2.3.1 FBC RES. BETTER STATES THE
 PATTERN THAT IS REQUIRED ( 8D RING SHANK NAILS SPACED
 AT 6" EDGE & 6" IN THE FIELD EXCEPT ZONE 3 IN WIND
 ZONES OF 130 MPH OR GREATER WHERE 4" EDGES & 6" FIELD
 IS REQUIRED)******
  
 17)PROVIDE ENGINEERED SUBSTRATE ATTACHMENT FOR WOOD
 BUCKS PER 1714.5.4.1 FBC
 *****PLEASE NOTE THAT NOA'S SHOW "APPROVED BUCKS" WHICH
 MEANS DESIGNED BY OTHERS, WE TYPICALLY SEE 1X4 AND 2X4
 APPLICATIONS IN THE FIELD THEREFORE REQUIRE BOTH
 DETAILS WITH ATTACHMENT METHODS SHOWN ON THE DRAWINGS
  
 NEW COMMENTS
  
 1)PROVIDE LINTEL LENGTHS THAT WILL BE USED FOR EACH
 OPENING FOR COMPLIANCE WITH2104.1.5 FBC MIN 4"
 BEARING
  
 2)SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL. PLEASE SUBMIT ON CORRECT FORM, SEE
 MECHANICAL REVIEW
  
 3)BEFORE FURTHER REVIEW ALL FEES MUST BE PAID IN
 FULL
  
 NOTE:
 FBC = FLORIDA BUILDING CODE 2004
 FBC* = WEST PALM BEACH ADMINISTATIVE AMMENDMENTS TO
 FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE RESIDENTIAL 2004
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-09-14 Cont ID  
Sent By amorse Date 2006-09-14 Time 14:33 Rev Time 0.00
Received By amorse Date 2006-09-14 Time 14:33 Sent To  
Notes
2006-09-14 00:00:00 
  
 DENIED
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 2) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC. THESE FEES
 WILL BE ADDED TO THE PERMIT APPLICATION
 FEES
  
 3) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
  
 4) INDEX SHEET REQUIES UPDATED
 INFORMATION ON THE FRONT AND SIDE
 SETBACKS THAT ARE PROVIDED
  
 5) THE MIN SOIL BEARING CAPACITY THAT IS
 REQUIRED BY THE DESIGNER (2500 PSF) AND
 THE SOIL BEARING CAPACITY IN THE SOIL
 REPORT (2000) DO NOT MATCH
  
 6) PLEASE SUBMIT 2 COPIES OF ALL
 CONSTRUTION DOCUMENTS THIS INCLUDES SOIL
 REPORTS, SURVEYS, ENERGY CALC'S, PRODUCT
 APPROVALS, ETC.
  
 7) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 8) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 9) PRODUCT APPROVALS THAT WERE SUBMITTED
 SHALL BE SUBMITTED WITH THE STATE COVER
 SHEETS WHERE APPLICABLE
  
 10) PRODUCT APPROVALS WERE SUBMITTED FOR
 HORIZONTAL SLIDING WINDOWS AND NONE ARE
 PRESNT ON THE DRAWINGS
  
 11) THE FOLLOWING PRODUCT APPROVALS ARE
 MISSING FROM THE PACKAGE (SH WINDOWS,
 MULLIONS FOR WINDOWS THAT ARE JIONED
 TOGETHER, FRENCH DOORS,SLIDING GLASS
 DOORS,WOOD ANCHORS AND TIES
  
 12) SUBMIT ENGINEERED TRUSS DRAWINGS
 THAT COMPLY WITH R802.10.1 FBC WITH
 PERMIT APPLICATION OR BEFORE
 INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
  
 13) PROVIDE AT MINIMUM 1 ACCESSIBLE
 BATHROOM PER R322.1.1 FBC
  
 14) THE SH24 WINDOWS SPECIFIED ON THE
 DRAWINGS DO NOT MEET THE REQUIREMENTS
 FOR EMERGENCY EGRESS AS STIPULATED PER
 R310.1 - R310.1.4 FBC
  
 15) PROVIDE ATTIC ACCESS ON DRAWINGS PER
 R807.1
  
 16) PROVIDE MIN ROOF SHEATHING
 ATTACHMENT PER TABLE 2304.9.1 FBC
  
 17) PROVIDE BUCK ATTACHMENT DETAIL FOR
 2X BUCKS AS MANY INSTALLATIONS USE 2X
 INSTEAD OF 1X, ALSO NOTE THAT BUCK FOR
 GARAGE DOOR AS PER NOA
  
 18) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-08-15 Cont ID  
Sent By btrobaug Date 2006-08-15 Time 17:54 Rev Time 0.50
Received By btrobaug Date 2006-08-15 Time 17:27 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-01-31 Cont ID  
Sent By adarroug Date 2008-01-31 Time 09:31 Rev Time 0.00
Received By adarroug Date 2008-01-31 Time 09:31 Sent To M
Notes
2008-01-31 09:31:21TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-10-12 Cont ID  
Sent By adarroug Date 2007-10-12 Time 10:25 Rev Time 0.00
Received By adarroug Date 2007-10-12 Time 10:25 Sent To B
Notes
2007-10-12 10:26:05TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-09-05 Cont ID  
Sent By adarroug Date 2007-09-05 Time 14:33 Rev Time 0.00
Received By adarroug Date 2007-09-05 Time 14:33 Sent To M
Notes
2007-09-05 14:34:29TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-06-19 Cont ID  
Sent By adarroug Date 2007-06-19 Time 11:11 Rev Time 0.00
Received By adarroug Date 2007-06-19 Time 11:11 Sent To M
Notes
2007-06-19 11:11:57TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-06-13 Cont ID  
Sent By adarroug Date 2007-06-13 Time 10:14 Rev Time 0.00
Received By adarroug Date 2007-06-13 Time 10:14 Sent To Z
Notes
2007-06-13 10:14:43TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-27 Cont ID  
Sent By spalmer Date 2007-03-27 Time 17:35 Rev Time 0.00
Received By spalmer Date 2007-03-27 Time 17:35 Sent To M
Notes
2007-03-27 17:35:43TO TOM GORDON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-22 Cont ID  
Sent By adarroug Date 2007-03-22 Time 11:12 Rev Time 0.00
Received By adarroug Date 2007-03-22 Time 11:12 Sent To Z
Notes
2007-03-22 11:13:08TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-12 Cont ID  
Sent By adarroug Date 2006-08-12 Time 16:06 Rev Time 0.00
Received By adarroug Date 2006-08-12 Time 16:06 Sent To E
Notes
2006-08-12 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-09-14 Time   Rev Time 0.00
Received By adarroug Date 2006-08-08 Time 10:09 Sent To  
Notes
2006-08-08 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-01-31 Cont ID  
Sent By tgordon Date 2008-01-31 Time 14:09 Rev Time 0.30
Received By tgordon Date 2008-01-31 Time 14:09 Sent To  
Notes
2008-01-31 14:10:07REVISION TO MECH. PLAN M-1.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-09-10 Cont ID  
Sent By tgordon Date 2007-09-10 Time 11:22 Rev Time 0.30
Received By tgordon Date 2007-09-10 Time 11:22 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-06-19 Cont ID  
Sent By tgordon Date 2007-06-19 Time 14:55 Rev Time 0.25
Received By tgordon Date 2007-06-19 Time 14:54 Sent To B
Notes
2007-06-19 15:00:14*** DENIED ***
 1) THE MECHANICAL PLANS PAGE M-2 IN ONE SET OF PLANS IS
 SEALED BY THE ENGINEER BUT NOT SIGNED OR DATED, SEE FAC
 61G15-23.002. PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-03-28 Cont ID  
Sent By tgordon Date 2007-03-28 Time 09:23 Rev Time 0.25
Received By tgordon Date 2007-03-28 Time 09:23 Sent To B
Notes
2007-03-28 09:26:12*** DENIED ***
 1) AS NOTED IN LAST REVIEW 8-16-06.ENERGY
 CALCULATIONS NEED TO BE ON
 FORM 600A-04 (2004) PER FBC 13-600.3.A .
  
 2) SEE ATTACHED NOTICE FS 553.80(2)(B)
 REGARDING FOUR TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-16 Cont ID  
Sent By tgordon Date 2006-08-16 Time 10:02 Rev Time 0.25
Received By tgordon Date 2006-08-16 Time 10:02 Sent To P
Notes
2006-08-16 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON
 FORM 600A-04 (2004) PER FBC 13-600.3.A .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-09-12 Cont ID  
Sent By jleech Date 2006-09-12 Time 07:23 Rev Time 0.00
Received By jleech Date 2006-09-12 Time 07:23 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2007-06-15 Cont ID  
Sent By adavila Date 2007-06-15 Time 12:03 Rev Time 0.00
Received By adavila Date 2007-06-14 Time 17:01 Sent To I
Notes
2007-06-15 12:03:03PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  
 ***NOTE***
  
 1.FENCE AND GATES, DEMOLITION OF CARPORT AND UTILITY
 ROOM, AND THE DRIVEWAY SHALL ALL BE APPROVED UNDER
 SEPARATE PERMITS.
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2007-03-26 Cont ID  
Sent By adavila Date 2007-03-26 Time 16:22 Rev Time 0.00
Received By adavila Date 2007-03-26 Time 16:16 Sent To I
Notes
2007-03-26 16:36:55PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.FRONT SETBACK AREA AND LANDSCAPE AREA DATA ON THE
 SITE PLAN SHALL BE CORRECTED TO REFLECT ACTUAL
 CONDITIONS.ON A 75 FOOT WIDE LOT, THE FRONT SETBACK
 AREA IS 1,875 SQUARE FEET.PER SECTION 94-482(A) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS, THE LESSER
 OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT YARD
 AREA MUST BE LANDSCAPED.
  
 2.PROVIDE SQUARE FOOTAGE OF THE PROPOSED
 DRIVEWAY/WALKWAY AREA.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-12 Cont ID  
Sent By mmclean Date 2006-08-12 Time 09:29 Rev Time 0.00
Received By mmclean Date 2006-08-12 Time 09:29 Sent To I
Notes
2006-08-12 00:00:00DENIED,
 1. PLEASE PROVIDE THE DIMENSION OF THE
 LOT ON THE SITEPLAN (2 COPIES)
 2. MUST PROVIDE THE DIMENSION OF THE
 PROPOSED DRIVEWAY/WALKWAY, ALSO THE
 EXISTING DRIVEWAY/WALKWAY (LENGTH &
 WIDTH)
  
 NOTE: MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
  
 3. MUST PULL A SEPARATE PERMIT FOR THE
 GATE/FENCE WITH CITY OF WEST PALM
 UTILITY EASEMENT APPROVAL.
  
 4. PLEASE SHOW THE LOCATION OF THE A/C &
 POOL EQUIPMENT ON TH TWO COPY OF
 SITEPLAN.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720