Plan Review Details - Permit 06080331
Plan Review Stops For Permit 06080331
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-16 Cont ID  
Sent By amorse Date 2006-08-16 Time 12:46 Rev Time 0.00
Received By amorse Date 2006-08-16 Time 12:15 Sent To PC
Notes
2006-08-16 00:00:00 
  
 DENIED
  
 1) A CERTIFICATE OF AUTHORIZATION SHALL
 BE REQUIRED FOR A CORPORATION, LIMITED
 LIABILITY COMPANY, OR PARTNERSHIP,
 OFFERING ARCHITECTURAL SERVICES TO THE
 PUBLIC JOINTLY OR SEPARATELY.
 PER 481.219(2) F.S.
  
 2) PROVIDE OCCUPANCY AND CONSTRUCTION
 TYPE PER 106.3.5 FBC*
  
 3) PROVIDE WIND DESIGN DATA ON DRAWINGS
 PER 1603.1.4 FBC PLEASE INCLUDE THE
 COMPONENT AND CLADDING PRESSURES FOR THE
 OPENINGS
  
 4) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
  
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 ***NOTE PRODUCT APPROVALS ARE REQUIRED
 FOR DOORS, WINDOWS AND BAHAMA SHUTTER
  
 5) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 6) WINDOWS AND DOORS UP TO 30 FT ABOVE
 GRADE REQUIRED TO BE LARGE MISSILE
 IMPACT RESISTANT OR REQUIRE SHUTTERS
 (PLEASE SEE CITY THAT IS ENCLOSED AS
 THEIR ARE MORE REQUIREMENTS IF SHUTTERS
 ARE USED)
  
 7) PROVIDE SIZES FOR WINDOWS AND DOORS
 TO BE REPLACED TO CONFIRM DESIGN
 PRESSURES WITH PRODUCT APPROVAL
 PRESSURES
  
 8) PROVIDE INFORMATION ON THE TYPE OF
 WALL CONSTRUCTION, BUCK DESIGN, ETC.
  
 9) SIGNAGE WILL REQUIRE SEPERATE PERMITS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2006-08-15 Cont ID  
Sent By btrobaug Date 2006-08-15 Time 07:00 Rev Time 0.50
Received By btrobaug Date 2006-08-15 Time 06:31 Sent To B
Notes
2006-08-15 00:00:00 
  
 NONCOMPLIANT
  
 THE ARCHITECTURAL FIRM MUST DISPLAY THE
 CERTIFICATE OF AUTHORIZATION ON THE
 TITLE BLOCK PER 481.221 (8).
  
 THERE IS NO ELECTRICAL PLAN FOR THE
 SCOPE OF THIS PROJECT. IF ELECTRICAL
 WORK IS INTENDED PLEASE SUBMIT PLANS PER
 2002 NEC AND ALL REFERENCED DOCUMENTS.
  
 WILLIAM R TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/561) 805-6731

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-14 Cont ID  
Sent By adarroug Date 2006-08-14 Time 11:44 Rev Time 0.00
Received By adarroug Date 2006-08-14 Time 11:44 Sent To E
Notes
2006-08-14 00:00:00TO "BTROBAUG" DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-04 Cont ID  
Sent By mmiller Date 2006-08-04 Time 14:52 Rev Time 0.00
Received By mmiller Date 2006-08-04 Time 14:52 Sent To Z
Notes
2006-08-04 00:00:00WAITING FOR COMMERICAL BOARD

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-10 Cont ID  
Sent By astelly Date 2006-08-10 Time 12:54 Rev Time 0.00
Received By astelly Date 2006-08-10 Time 12:54 Sent To  
Notes
2006-08-10 00:00:001. ALL WINDOWS ON EAST AND SOUTH
 ELEVATIONS MUST MATCH.
  
 2. PROVIDE AWNINGS WHICH EITHER SPAN
 BOTH THE WINDOWS AND DOORS OR AWNINGS
 WHICH ARE APPROPRIATELY SIZED FOR EACH
 ELEMENT.
  
 3. PROVIDE DIMENSIONS FOR BOTH LENGTH
 AND HEIGHT OF PROPOSED BUILDING SIGNAGE.
 SIGNAGE CANNOT EXCEED 60% OF THE
 BUILDING WIDTH AS PER THE SIGNAGE CODE
 FOR THE DOWNTOWN MASTER PLAN (DMP).
  
 4. PLEASE PROVIDE A SURVEY. DOORS CANNOT
 SWING INTO THE RIGHT-OF-WAY.