Plan Review Details - Permit 06080143
Plan Review Stops For Permit 06080143
Review Stop AD ADDRESSING
Rev No 4 Status P Date 2006-11-15 Cont ID  
Sent By lursu Date 2006-11-15 Time 16:22 Rev Time 0.00
Received By lursu Date 2006-11-15 Time 16:22 Sent To  
Notes
2006-11-15 16:23:08PERMIT ATTACHED TO PCN = 74424302090003360

Review Stop AD ADDRESSING
Rev No 3 Status P Date 2006-11-02 Cont ID  
Sent By lursu Date 2006-11-02 Time 11:13 Rev Time 0.00
Received By lursu Date 2006-11-02 Time 11:13 Sent To  
Notes
2006-11-02 11:14:27UNITY OF TITLE WAS RECEIVED , PERMIT ATTACHED TO THE
 TEMPORARY RECORD.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2006-11-01 Cont ID  
Sent By lursu Date 2006-11-01 Time 16:49 Rev Time 0.00
Received By lursu Date 2006-11-01 Time 16:49 Sent To  
Notes
2006-11-01 16:50:20UNITY OF TITLE IS REQUIRED BEFORE ASSIGNING THE PERMIT
 TO THE TEMPORARY PCN CREATED.

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-08-04 Cont ID  
Sent By lursu Date 2006-08-04 Time 08:35 Rev Time 0.00
Received By lursu Date 2006-08-04 Time 08:35 Sent To  
Notes
2006-08-04 00:00:00TEMPORARY PCN WAS CREATED FOR THESE
 UNITS 336,337,338.PERMIT MUST BE
 ATTACHED TO PCN = TEMP7442430208336
 ON THE APPLICATION THE ADDRESS MUST READ
 : 5407 N HAVERHILL RD # 336INSTEAD OF
 5405.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-05-09 Cont ID  
Sent By jwitmer Date 2007-05-09 Time 13:58 Rev Time 0.77
Received By jwitmer Date 2007-05-09 Time 13:58 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-03-06 Cont ID  
Sent By jwitmer Date 2007-03-06 Time 13:25 Rev Time 0.78
Received By jwitmer Date 2007-03-06 Time 13:25 Sent To  
Notes
2007-03-06 13:25:59REVISIONS 2& 3.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-01-05 Cont ID  
Sent By jwitmer Date 2007-01-05 Time 11:46 Rev Time 0.77
Received By jwitmer Date 2007-01-05 Time 11:46 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-11-02 Cont ID  
Sent By jwitmer Date 2006-11-02 Time 10:00 Rev Time 1.11
Received By jwitmer Date 2006-11-02 Time 10:00 Sent To PC
Notes
2006-11-02 10:01:27PERMIT:06080143
 ADD: 5405 N. HAVERHILL RD.
 CONT: G. W. PURUCKER HOMES INC.
 TEL: (561)775-1170
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: REVIEWED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 11-02 -06 UNITY OF TITLE FAXED THIS MORNING- OK!
 COMMENT FROM PREVIOUS REVIEWS:
 4) THESE UNITS ARE CONDOMINIMUM
 REQUIRING A UNITY OF TITLE BETWEEN
 UNITS. THE PROPOSED BUILDING (UNIT)
 STRUCTURE TRANSGRESSES LEGAL BOUNDARY
 LINES BETWEEN THE LOTS WHICH COMBINE TO
 FORM 'THE SITE'.A 'UNITY OF TITLE'
 SHALL BE RECORDED AT THE COUNTY
 COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF OF TITLE' DOCUMENT SO
 THAT FBC TABLE 601 BOUNDARY LINE
 REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
  
 ALSO SEE REVIEW NOTES FROM PLANNING/ ZONING
 AND ADDRESSING.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-13 Cont ID  
Sent By jwitmer Date 2006-10-13 Time 12:44 Rev Time 0.55
Received By jwitmer Date 2006-10-13 Time 12:44 Sent To  
Notes
2006-10-13 12:52:25BUILDING PLAN REVIEW
 PERMIT: 06080143
 ADD: 5407 N HAVERHILL RD, SUITE 336
 CONT: G. W. PURUCKER HOMES
 TEL: (561)775-1170
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 NEW COMMENT: PLEASE SEE THE ADDRESSING COMMENT, WOULD
 THE CONTRACTOR PLEASE
 CHANGE THE ADDRESS OF THE PROJECT ON HIS PERMIT
 APPLICATION. ADDRESSING HAS ESTABLISHED THE
 BULDING ADDRESS AS 5407 N HAVERHILL UNIT 336. PLEASE
 CORRECT THE PERMIT APPLICATION TO REFLECT THIS.
  
 PLEASE RECORD THE NOTICE OF COMMENCEMENT WITH THIS NEW
 ADDRESS. BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-31 Cont ID  
Sent By jwitmer Date 2006-08-31 Time 14:40 Rev Time 2.22
Received By jwitmer Date 2006-08-31 Time 14:32 Sent To  
Notes
2006-08-31 00:00:00BUILDING PLAN REVIEW
 PERMIT:06080143
 ADD: 5405 N. HAVERHILL RD.
 CONT: G. W. PURUCKER HOMES INC.
 TEL: (561)775-1170
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601, AND LEVEL OF ALTERATION
 UNDER 2004 FL EXISTING BLDG
 CODE.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 3) ADDITIONAL INFORMATION REQUIRED,
 106.1.2*. PLANS INDICATE THERE IS A
 MEZZANINE LEVEL, PROVIDE WHAT WALLS ARE
 EXISTING AND WHAT WALLS ARE NEW FIRST
 FLOOR AND MEZZANINE LEVEL.
 BOTH THE FIRST FLOOR AND MEZZANINE
 LEVELS CAN NOT BE TOTALY ENCLOSED.
 MEZZANINES BY DEFINTION NEED TO
 COMMUNICATE WITH THE ROOM THAT IT IS
 LOCATED. EITHER THE FLOORS CAN NOT BE
 ENCLOSED ONLY ONE. 505.2. EVEN IF THE
 EXCEPTION# 1 OF 505.4 THE AMOUNT OF
 OPENNESS REQUIRED THE OCCUPANT LOAD FOR
 THE MEZZANINE WOULD BE OVER 10
 OCCUPANTS. THE CONFERENCE ROOM ALONE
 148SQ FT @ 15 SQ FT / PERSON ALONE WOULD
 BE AN OCCUPANT LOAD OF 10 PLUS THE
 REMAINDER OF THE FLOOR. IF EXCEPTION# 3
 IS TAKEN ONLY 10% OF THE MEZZANINE FLOOR
 AREA CAN BE ENCLOSED.
  
 4) THESE UNITS ARE CONDOMINIMUM
 REQUIRING A UNITY OF TITLE BETWEEN
 UNITS. THE PROPOSED BUILDING (UNIT)
 STRUCTURE TRANSGRESSES LEGAL BOUNDARY
 LINES BETWEEN THE LOTS WHICH COMBINE TO
 FORM 'THE SITE'.A 'UNITY OF TITLE'
 SHALL BE RECORDED AT THE COUNTY
 COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF OF TITLE' DOCUMENT SO
 THAT FBC TABLE 600 BOUNDARY LINE
 REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
  
 5) DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY:11-4.1.6(1)(F)
 NOTHING IN THIS SECTION SHALL BE
 CONSTRUED TO RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY FROM THE
 DUTY TO PROVIDE VERTICAL ACCESSIBILITY
 TO ALL LEVELS ABOVE AND BELOW OCCUPIABLE
 GRADE LEVEL, REGARDLESS OF WHETHER THE
 CODE REQUIRES AN ELEVATOR TO BE
 INSTALLED IN SUCH BUILDING, STRUCTURE,
 OR FACILITY, EXCEPT FOR: (1) ELEVATOR
 PITS, ELEVATOR PENTHOUSES, MECHANICAL
 ROOMS, PIPING OR EQUIPMENT CATWALKS, AND AUTOMOBILE
 LUBRICATION AND MAINTENANCE
 PITS AND PLATFORMS; (2) UNOCCUPIABLE
 SPACES, SUCH AS ROOMS, ENCLOSED SPACES,
 AND STORAGE SPACES THAT ARE NOT DESIGNED
 FOR HUMAN OCCUPANCY, FOR PUBLIC
 ACCOMMODATIONS, OR FOR WORK AREAS; AND
 (3) OCCUPIABLE SPACES AND ROOMS THAT ARE
 NOT OPEN TO THE PUBLIC AND THAT HOUSE NO
 MORE THAN FIVE PERSONS INCLUDING, BUT
 NOT LIMITED TO, EQUIPMENT CONTROL ROOMS
 AND PROJECTION BOOTHS. HOWEVER, AS
 PROVIDED IN SECTION 553.509, FLORIDA
 STATUTES , BUILDINGS, STRUCTURES, AND
 FACILITIES MUST, AT A MINIMUM, COMPLY
 WITH THE REQUIREMENTS OF THE ADAAG.
 THEREFORE, FACILITIES SUBJECT TO THE
 ADAAG MAY BE REQUIRED TO PROVIDE
 VERTICAL ACCESS TO AREAS OTHERWISE
 EXEMPT UNDER SECTION 11-4.1.3 (5) OF
 THIS CODE.
  
 6)TO CLASSIFY THIS SPACE AS A TWO
 STORY
 UNIT, A EXIT TO THE EXTERIOR WILL BE
 REQUIRED. 1017.2.2 ARRANGEMENT.
 EXTERIOR EXIT DOORS SHALL LEAD DIRECTLY
 TO THE EXIT DISCHARGE OR THE PUBLIC
 WAY.1017.1 GENERAL.
  
 EXITS SHALL COMPLY WITH SECTIONS 1017
 THROUGH 1022 AND THE APPLICABLE
 REQUIREMENTS OF SECTIONS 1003 THROUGH
 1012 . AN EXIT SHALL NOT BE USED FOR ANY
 PURPOSE THAT INTERFERES WITH ITS
 FUNCTION AS A MEANS OF EGRESS. ONCE A
 GIVEN LEVEL OF EXIT PROTECTION IS
 ACHIEVED, SUCH LEVEL OF PROTECTION SHALL
 NOT BE REDUCED UNTIL ARRIVAL AT THE EXIT DISCHARGE.
 EXIT
 1017.2 EXTERIOR EXIT DOORS.
 BUILDINGS OR STRUCTURES USED FOR HUMAN
 OCCUPANCY SHALL HAVE AT LEAST ONE
 EXTERIOR DOOR THAT MEETS THE
 REQUIREMENTS OF SECTION 1008.1.1 .
  
 MORE COMMENTS MAY APPEAR AS A RESULT OF
 THE RESPONCE COMMENTS.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-03-06 Cont ID  
Sent By dpalmer Date 2007-03-06 Time 09:06 Rev Time 0.00
Received By dpalmer Date 2007-03-06 Time 07:47 Sent To  
Notes
2007-03-06 09:07:42REDLINED NOTES FOR OCMAX TIMES PER 13-415.1.ABC.1.1

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-12-21 Cont ID  
Sent By dpalmer Date 2006-12-21 Time 15:15 Rev Time 0.00
Received By dpalmer Date 2006-12-21 Time 15:15 Sent To  
Notes
2006-12-21 15:16:20REDLINED MAX TIME ON OC TYPE DEVICES, 30MINS
 13-415.1.ABC.1.1

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-24 Cont ID  
Sent By dpalmer Date 2006-10-24 Time 18:55 Rev Time 0.00
Received By dpalmer Date 2006-10-24 Time 18:49 Sent To  
Notes
2006-10-24 18:56:15REDLINE DMAX TIME ON OCCUPANT SENSOR TYPE DEVICES
 30MIN.
 13-415.1.ABC.1.1, .1.2
  
 STAMPED ALL THREE SETS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-12 Cont ID  
Sent By dpalmer Date 2006-10-12 Time 09:56 Rev Time 0.00
Received By dpalmer Date 2006-10-12 Time 09:55 Sent To P
Notes
2006-10-12 10:42:44** UNSAT 2ND REVIEW***
  
 PLEASE SEE SOME NTOES FROM PREVIOUS REVIEW WHICH ARE
 STILL IN NEED OF ADDRESSING.
 PLEASE SEE SONE NEW COMMENTS BASED ON PLANS BEING
 SUBMITTED.
  
 1) NOTE: NO, COULD NOT LOCATE THIS?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE DECLARE USE. PLEASE SEE
 TYPE OF MERCHANTILE AND WAREHOUSE USE
 MUST BE STATED. PLEASE SEE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT THE
 ELECTRICAL PLANS.
 PLEASE SEE CHAPTER 5 IN THE NEC FOR ANY
 HAZARDOUS LOCATIONS/STORAGE ETC.
  
 2) NOTE: NO, PLEASE SEE ALL CIRCUITING IS SHOWN,
 HOWEVER PLEASE SEE SPECIFIC AREAS AND ROOMS ARE NOT
 SHOWING DESIGNATIONS ON PLANS AND ON PANEL SCHEDULES.;
 PLEASE SEE SCHEDULE MENTYIONS "LTS" OR RECEPT" W/OUT
 ANY LOCATION.
 PLEASE ALSO SEE ELECTRICAL "POWER PLAN" IS BEING SHOWN
 ON THE ARCHITECTURAL SHEETS AND NOT ON THE "E" SHEETS?
 PLEASE KNOW, IF BUIDLIGN REVIEW IS OK, THESE SHEETS MAY
 NOT BE STAMPED AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULES.
 PLEASE BE SURE ALL CIRCUITS ARE SPECIFIC
 TO AREAS, ROOMS ETC.
 408.4,240.4,310.16
 FBC 106.1.2
  
 3) NOTE: OK/NO, PLEASE SEE THE RECEPTSARE SHOWN,
 HOWEVER PLEASE CLARIFY/ HOW THE LOAD IS DERIVED AND
 SHOWN IN LOAD CALCULATIONS FOR THE SHOW WINDOWS PER
 220.12. THIS COULD NOT BE LCOATED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING SHOW WINDOW
 RECEPTS REQUIRED.
 210.62, 220.12
  
 4) NOTE:NO, PLEASE SEE A RECEPT IS SHOWN , HOWEVER
 NOT PER 600.5 WHICH REQUIRES A MINDEDICATED CIRCUIT
 AND ALSO THERE SHOULD BE A MIN VA FIGURED FOR THIS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING SIGN
 CIRCUIT.600.5
  
 5) NOTE:NO, PLEASE SEE SOME ITEMS ARE SHOWN, BUT NOT
 ALL. PLEASE SEE "SEPARATE SPACES" AND TYPES OF
 DEVICES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13 FOR
 LIGHTING CONTROLS REQUIRED. THIS SPACE
 IS LOCATED IN A BLDG GREATER THAN 5000
 SQ FT.
 13-415.1.ABC.1.1, .1.2, AND .1.3
  
 6) NOTE: NO, PLEASE SEE PLANS STILL INDICATE "LATEST
 EDITION"
 PLEASE SEEE "E" SHEETS".
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS MENTIONS THE
 "LATEST EDITIONS" OD THE CODES, HOWEVER
 PLEASE KNOW THAT THE LATEST EDITIONS OF
 THE CODE WHICH IS OUT AND AVAILABLE IS
 NOT YET ADOPTED BY THE STATE.
 PLEASE SEE THE FOLLOWING CODES AT A MIN
 SHALL BE REFLECTED ON THE ELECTRICAL
 PLANS.
 2002 NFPA-70 , 2002 NFPA-72, 2003
 NFPA-101.
  
 7) NOTE: NO, PLEASE SEE ONLY THE FIRM LICENSE NUMBER IS
 SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE THE PRINTED
 LICENSE # OF THE ARCHITECT IS ON SAID
 TITLE BLOCK AS REQUIRED PER FAC
 61G1-16.004
  
  
 ** NEW NOTE **
  
 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-16 Cont ID  
Sent By dpalmer Date 2006-08-16 Time 19:09 Rev Time 0.00
Received By dpalmer Date 2006-08-16 Time 18:53 Sent To  
Notes
2006-08-16 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE DECLARE USE. PLEASE SEE
 TYOE OF MERCHANTILE AND WAREHOUSE USE
 MUST BE STATED. PLEASE SEE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT THE
 ELECTRICAL PLANS.
 PLEASE SEE CHAPTER 5 IN THE NEC FOR ANY
 HAZARDOUS LOCATIONS/STORAGE ETC.
  
 2) NOTE: PLEASE INDICATE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULES.
 PLEASE BE SURE ALL CIRCUITS ARE SPECIFIC
 TO AREAS, ROOMS ETC.
 408.4,240.4,310.16
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE MISSING SHOW WINDOW
 RECEPTS REQUIRED.
 210.62, 220.12
  
 4) NOTE: PLEASE SEE MISSING SIGN
 CIRCUIT.600.5
  
 5) NOTE: PLEASE SEE FBC CHAPTER 13 FOR
 LIGHTING CONTROLS REQUIRED. THIS SPACE
 IS LOCATED IN A BLDG GREATER THAN 5000
 SQ FT.
 13-415.1.ABC.1.1, .1.2, AND .1.3
  
 6) NOTE: PLEASE SEE PLANS MENTIONS THE
 "LATEST EDITIONS" OD THE CODES, HOWEVER
 PLEASE KNOW THAT THE LATEST EDITIONS OF
 THE CODE WHICH IS OUT AND AVAILABLE IS
 NOT YET ADOPTED BY THE STATE.
 PLEASE SEE THE FOLLOWING CODES AT A MIN
 SHALL BE REFLECTED ON THE ELECTRICAL
 PLANS.
 2002 NFPA-70 , 2002 NFPA-72, 2003
 NFPA-101.
  
 7) NOTE: PLEASE BE SURE THE PRINTED
 LICENSE # OF THE ARCHITECT IS ON SAID
 TITLE BLOCK AS REQUIRED PER FAC
 61G1-16.004
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-03-14 Cont ID  
Sent By mawillia Date 2007-03-14 Time 15:41 Rev Time 0.00
Received By mawillia Date 2007-03-14 Time 15:18 Sent To  
Notes
2007-03-14 15:41:06*****APPROVED*****
  
  
 REVISED PLAN SHEETS E-3 AND E-4 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-12-26 Cont ID  
Sent By mawillia Date 2006-12-26 Time 14:55 Rev Time 0.00
Received By mawillia Date 2006-12-26 Time 14:55 Sent To  
Notes
2006-12-26 14:58:39*****REVISIONS APPROVED*****
  
  
  
  
 STAMPED AND SIGNED SHEET A-2 AND E-4

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-10-26 Cont ID  
Sent By mawillia Date 2006-10-26 Time 16:11 Rev Time 0.00
Received By mawillia Date 2006-10-26 Time 16:11 Sent To  
Notes
2006-10-26 16:15:25 
 *****APPROVED*****
  
  
  
  
 *****PLEASE BE ADVISED THAT THE PERMIT SHOWS SUITE
 NUMBER AS 336 WHEREAS THE PLANS SHOW SUITES 36 &
 37******

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-10-17 Cont ID  
Sent By mwennerg Date 2006-10-17 Time 10:28 Rev Time 0.00
Received By mwennerg Date 2006-10-17 Time 10:28 Sent To  
Notes
2006-10-17 10:33:21***DENIED***
  
 1) PLEASE PROVIDE CORRECTIONS REGARDING ADDRESSING.
 PLEASE SEE OTHER REVIEW COMMENTS.
  
 2) THE RESPONSE LETTER INDICATES NEW MECHANICAL PLANS,
 HOEVER NO MENTION OR ACKNOWLEDGEMENT OF LOCAL
 REQUIREMENT FROM LAST REVIEW REGARDING DUCT SMOKE
 DETECTORS WAS FOUND.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-07 Cont ID  
Sent By mwennerg Date 2006-09-07 Time 11:16 Rev Time 0.00
Received By mwennerg Date 2006-10-17 Time 10:28 Sent To  
Notes
2006-09-07 00:00:00***DENIED***
  
 1) PLEASE PROVIDE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILING THAT IS SPECIFIC TO THIS
 PROJECT. SHEET A-1, NOTE (4) IS GENERAL
 CODE REFERENCE.
  
 2) NOTE REFERENCING SPRINKLER WORK
 ACKNOWLEDGED. IS THIS PROJECT PROTECTED
 BY A FIRE ALARM SYSTEM? IF SO, DUCT
 SMOKE DETECTORS SHALL INITIATE A GENERAL
 FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-04-02 Cont ID  
Sent By spalmer Date 2007-04-02 Time 17:38 Rev Time 0.00
Received By spalmer Date 2007-04-02 Time 17:38 Sent To B
Notes
2007-04-02 17:38:21TO JIM WITMER

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-03-06 Cont ID  
Sent By dpalmer Date 2007-03-06 Time 08:45 Rev Time 0.00
Received By dpalmer Date 2007-03-06 Time 08:45 Sent To  
Notes
2007-03-06 08:46:16BOB BOARD #13

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-03 Cont ID  
Sent By adarroug Date 2007-03-03 Time 14:30 Rev Time 0.00
Received By adarroug Date 2007-03-03 Time 14:30 Sent To E
Notes
2007-03-03 14:30:22TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-12-05 Cont ID  
Sent By adarroug Date 2006-12-05 Time 10:58 Rev Time 0.00
Received By adarroug Date 2006-12-05 Time 10:58 Sent To  
Notes
2006-12-21 09:25:36TO "BOB"#4
2006-12-05 10:59:21WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-20 Cont ID  
Sent By adarroug Date 2006-10-20 Time 10:21 Rev Time 0.00
Received By adarroug Date 2006-10-20 Time 10:21 Sent To  
Notes
2006-10-24 13:02:44TO "BOB"#17
2006-10-20 10:22:13WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-12 Cont ID  
Sent By adarroug Date 2006-10-12 Time 08:43 Rev Time 0.00
Received By adarroug Date 2006-10-12 Time 08:43 Sent To E
Notes
2006-10-12 08:43:34TO "DPALMER" DESK/RESUB--EXPEDITED PLANS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-07 Cont ID  
Sent By mwennerg Date 2006-09-07 Time 11:26 Rev Time 0.00
Received By mwennerg Date 2006-08-03 Time 10:58 Sent To  
Notes
2006-08-14 00:00:00TO "BOB"#8
2006-08-03 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-05-09 Cont ID  
Sent By rregueir Date 2007-05-09 Time 13:06 Rev Time 0.00
Received By rregueir Date 2007-05-09 Time 11:18 Sent To B
Notes
2007-05-09 13:06:54INSULATION R-VALUES OK. SENT TO JIM WITMER.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2006-12-21 Cont ID  
Sent By tgordon Date 2006-12-21 Time 15:58 Rev Time 0.20
Received By tgordon Date 2006-12-21 Time 15:58 Sent To  
Notes
2006-12-21 15:59:02REVISION WAS A BUILDING REVISION NOT MECHANICAL.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-10-24 Cont ID  
Sent By kstevens Date 2006-11-02 Time 16:34 Rev Time 0.30
Received By tgordon Date 2006-10-24 Time 08:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-10-13 Cont ID  
Sent By tgordon Date 2006-10-13 Time 12:08 Rev Time 0.45
Received By tgordon Date 2006-10-13 Time 12:08 Sent To B
Notes
2006-10-13 12:18:28*** DENIED ***
 1) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. PER FBC 104.2.1 .
  
 2) PLEASE SHOW JOB ADDRESS ON
 MECHANICAL PLANS.
  
 3) PLEASE SUBMIT TWO COPYS OF THE
 ENERGY CAL'S. AND MANUAL J CAL'S.
  
 4) ENERGY CALCULATIONS NEED TO BE
 SIGNED IN INK BY THE PREPARER
 AND THE OWNER/AGENT.
  
 5) PLEASE STATE LOCATION OF CONDENSER
 UNIT ON PLANS, AND SUBMIT INFORMATION
 REGARDING ANCHORING AND CONDENSER
 STAND IF BEING USED.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-08-17 Cont ID  
Sent By tgordon Date 2006-08-17 Time 10:53 Rev Time 0.30
Received By tgordon Date 2006-08-17 Time 10:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-03-10 Cont ID  
Sent By jleech Date 2007-03-10 Time 09:50 Rev Time 0.00
Received By jleech Date 2007-03-10 Time 09:50 Sent To  
Notes
2007-03-10 09:51:13PLUMBING AS-BUILTS

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-01-06 Cont ID  
Sent By jleech Date 2007-01-06 Time 14:18 Rev Time 0.00
Received By jleech Date 2007-01-06 Time 14:18 Sent To  
Notes
2007-01-06 14:23:07RE-STAMPED SANITARY RISER DIAGRAM NO CHANGE TO PLUMBING
 DIAGRAMON ELECTRICAL PAGE E-2

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-10-13 Cont ID  
Sent By kstevens Date 2000-10-13 Time 09:49 Rev Time 0.00
Received By kstevens Date 2006-10-13 Time 16:35 Sent To M
Notes
2006-10-13 09:51:59PER OWNER, BBQ GRILL ASSEMBLY ONLY. INDICATED NO LP GAS
 ON PREMISSIS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-09-06 Cont ID  
Sent By kstevens Date 2006-09-06 Time 16:23 Rev Time 0.00
Received By kstevens Date 2006-09-06 Time 16:20 Sent To  
Notes
2006-09-06 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SUBMIT A DETAIL FOR THE 2ND FLOOR
 SINK. SHOW THE FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD
 APPROACH REQUIRED) NO CABINET DOORS IN
 CLEAR FLOOR SPACE.
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
  
 2. SUBMIT A WATER RISER DIAGRAM SHOWING
 PIPE SIZES, VALVES, AND WATER HAMMER
 ARRESTORS (IF REQUIRED BY SECTION 604.9)
 SECTIONS 606 AND 106.3.5.1.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2006-11-02 Cont ID  
Sent By jroach Date 2006-11-02 Time 10:33 Rev Time 0.00
Received By jroach Date 2006-11-02 Time 10:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2006-11-01 Cont ID  
Sent By jroach Date 2006-11-01 Time 15:50 Rev Time 0.00
Received By jroach Date 2006-11-01 Time 15:50 Sent To  
Notes
2006-11-01 15:52:29***FAILED***
  
 AS TWO (2) CONDOMINIUM UNITS ARE BEING COMBINED, A
 UNITY OF TITLE SHALL BE RECORDED WITH THE PALM BEACH
 COUNTY CLERK OF THE CIRCUIT COURT.A CERTIFIED COPY OF
 THE RECORDED DOCUMENT SHALL BE INCLUDED WITH THE PERMIT
 PACKAGE.
  
 QUESTIONS/COMMENTS, PLEASE CONTACT JOHN ROACH, SENIOR
 PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-08-28 Cont ID  
Sent By jroach Date 2006-08-28 Time 12:26 Rev Time 0.00
Received By jroach Date 2006-08-28 Time 12:26 Sent To  
Notes
***NONE***