Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-05 Cont ID  
Sent By alange Date 2006-09-05 Time 16:53 Rev Time 0.50
Received By alange Date 2006-09-05 Time 16:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-18 Cont ID  
Sent By alange Date 2006-08-18 Time 09:30 Rev Time 0.50
Received By alange Date 2006-08-18 Time 09:30 Sent To  
Notes
2006-08-18 00:00:00DENIED
  
 SHOW GENERATOR SLAB DETAIL AND METHOD OF
 ATTACHMENT TO SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-14 Cont ID  
Sent By btrobaug Date 2006-09-14 Time 11:13 Rev Time 0.50
Received By btrobaug Date 2006-09-14 Time 10:55 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-05 Cont ID  
Sent By btrobaug Date 2006-09-05 Time 12:56 Rev Time 0.50
Received By btrobaug Date 2006-09-05 Time 12:26 Sent To M
Notes
2006-09-05 00:00:00 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL FOR THE GENERATOR, EQUIPMENT
 (TRANSFER SWITCHES, PANELS ETC.)
 AND PAD PER 108.3 FBC AS AMENDED.
 INCREASE THE VALUE AT THE COUNTER WHEN
 RESUBMITTING, AND GET A RECEIPT FROM THE
 PERMIT CLERK.
  
 1} THE "SITE PLAN " THAT WAS REQUESTED
 IN THE PREVIOUS REVIEW DOES NOT SHOW A
 DISCONNECTING MEANS AT THE NEAREST POINT
 OF ENTRANCE OF THE CONDUCTORS FROM THE
 GENERATOR, NOR DOES THE RISER.
  
 2} PLEASE SUBMIT A SITE PLAN AND LOCATE
 ALL THE SERVICE AND GENERATOR GEAR ON
 SAME SO THAT COMPLIANCE WITH
 230.72(GROUPING), 225.31-39 FOR THE
 DISCONNECTING MEANS REQUIREMENTS AND
 250.32 FOR GROUNDING CAN BE REVIEWED.
  
  
 WILLIAM R TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/561) 805-6731
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-16 Cont ID  
Sent By btrobaug Date 2006-08-16 Time 14:31 Rev Time 0.50
Received By btrobaug Date 2006-08-16 Time 14:09 Sent To M
Notes
2006-08-16 00:00:00 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 THE VALUE ON THE APPLICATION MUST
 INCLUDE THE TOTAL COST OF LABOR AND
 MATERIAL FOR THE GENERATOR, EQUIPMENT
 (TRANSFER SWITCHES, PANELS ETC.)
 AND PAD PER 108.3 FBC AS AMENDED.
 INCREASE THE VALUE AT THE COUNTER WHEN
 RESUBMITTING, AND GET A RECEIPT FROM THE
 PERMIT CLERK.
  
 1} PROVIDE A RISER DIAGRAM PER 215.5
 INCLUDING GENERATOR AND RELATED
 EQUIPMENT.
  
 2} PLEASE SUBMIT A SITE PLAN AND LOCATE
 ALL THE SERVICE AND GENERATOR GEAR ON
 SAME SO THAT COMPLIANCE WITH
 230.72(GROUPING), 225.31-39 FOR THE
 DISCONNECTING MEANS REQUIREMENTS AND
 250.32 FOR GROUNDING CAN BE REVIEWED.
  
 3} PROVIDE MANUFACTURERS SPECIFICATIONS
 INDICATING RECOMMENDED SETBACKS.
  
  
 WILLIAM R TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/561) 805-6731
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-08-17 Cont ID  
Sent By mperson Date 2006-08-17 Time 14:43 Rev Time 0.15
Received By mperson Date 2006-08-17 Time 14:43 Sent To B
Notes
2006-08-17 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-05 Cont ID  
Sent By adarroug Date 2006-09-05 Time 09:51 Rev Time 0.00
Received By adarroug Date 2006-09-05 Time 09:51 Sent To E
Notes
2006-09-05 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-26 Cont ID  
Sent By adarroug Date 2006-08-26 Time 15:53 Rev Time 0.00
Received By adarroug Date 2006-08-26 Time 15:53 Sent To Z
Notes
2006-08-26 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-10 Cont ID  
Sent By mmiller Date 2006-08-10 Time 15:13 Rev Time 0.00
Received By adarroug Date 2006-08-10 Time 15:51 Sent To E
Notes
2006-08-10 00:00:00SENT TO "E GENERATOR" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-18 Cont ID  
Sent By alange Date 2006-08-18 Time 09:35 Rev Time 0.00
Received By alange Date 2006-08-02 Time 13:17 Sent To  
Notes
2006-08-02 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-09-18 Cont ID  
Sent By tgordon Date 2006-09-14 Time 12:20 Rev Time 0.30
Received By tgordon Date 2006-09-18 Time 10:28 Sent To  
Notes
2006-09-14 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 FOLLOW MANUFACTURE'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING,AND PROVIDE MANUFACTURE'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-09-05 Cont ID  
Sent By tgordon Date 2006-09-05 Time 14:23 Rev Time 0.15
Received By tgordon Date 2006-09-05 Time 14:23 Sent To B
Notes
2006-09-05 00:00:00*** DENIED ***
 1) PLEASE SHOW AND LABEL THE PURPOSED
 LOCATION OF THE GENERATOR ON SURVEY.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-11 Cont ID  
Sent By tgordon Date 2006-08-11 Time 16:34 Rev Time 0.15
Received By tgordon Date 2006-08-11 Time 16:34 Sent To E
Notes
2006-08-11 00:00:00*** DENIED ***
 1) SEE ZONING REVIEW, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-09-02 Cont ID  
Sent By mmclean Date 2006-09-02 Time 07:28 Rev Time 0.00
Received By mmclean Date 2006-09-02 Time 07:28 Sent To I
Notes
2006-09-02 00:00:00PROVISO:
 THE PROPOSED GENERATOR SHALL NOT BE
 CLOSER THAN 6FT FROM REAR PROPERTY LINE
 AND 2FT FROM SIDE PROPERTY LINE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-09 Cont ID  
Sent By mmclean Date 2006-08-08 Time 10:48 Rev Time 0.00
Received By mmclean Date 2006-08-08 Time 10:48 Sent To  
Notes
2006-08-09 00:00:00DENIED,
 1. PLEASE SHOW THE LOCATION OF THE
 PROPOSED GENERATOR ON THE TWO COPY OF
 SURVEY.
 2. SURVEY DOES NOT SHOW LOCATION.
  
 NOTE:
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720