Plan Review Details - Permit 06071958
Plan Review Stops For Permit 06071958
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-22 Cont ID  
Sent By rmcdouga Date 2006-08-22 Time 11:05 Rev Time 0.00
Received By rmcdouga Date 2006-08-22 Time 07:31 Sent To  
Notes
2006-08-22 00:00:00BUILDING DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SPECIFY LOCATION AND SIZE OF ATTIC
 ACCESS REQUIRED BY FBC R807.1.
  
 4) THE REQUIRED SOIL BEARING CAPACITY
 FOR THE DESIGN SPECIFIED ON A1 IS 2500
 PSF AND THE SOIL REPORT IS FOR 2000 PSF.
  
 5) THE SOIL REPORT REQUIRES 20" WIDE
 FOOTINGS AND THE PLANS SPECIFY 18" WIDE
 FOOTINGS.
  
 6) THE FOUNDATION NOTES ON SHEET A1 CITE
 THE WRONG EDITIONS OF ACI 530 AND ACI
 318. THE 2002 EDITIONS ARE REFERENCED BY
 THE 2004 FBC.
  
 7) SPECIFY THE DESIGN CRITERIA. INCLUDE
 THE INTERNAL PRESSURE COEFFICENT,
 EXPOSURE CATEGORY, ETC. SEE R301.
  
 8) PROVIDE A SITE DRAINAGE PLAN. SEE
 R401.3.
  
 9) SPECIFY THE DISTANCE TO ALL PROPERTY
 LINES AND DISTANCE TO ASSUMED PROPERTY
 LINE BETWEEN OTHER BUILDINGS ON THE SAME
 LOT. SEE R302 AND FBC 704.3.
  
 10) SPECIFY THE REQUIRED WINDLOAD DESIGN
 PRESSURES FOR ALL EXTERIOR OPENINGS.
  
 11) PROVIDE STRUCTURAL DETAILS FOR THE
 EXTERIOR EGRESS STAIRS. SPECIFY SIZE AND
 LOCATIONS OF STEEL REINFORCEMENT FOR
 WALL AND STEPS IF CONCRETE. SPECIFY THE
 RISE AND TREAD DEPTH. PROVIDE HANDRAIL
 DETAILS. PROVIDE DIMENSIONS. SPECIFY
 HEIGHT OF GUARD WALL. SEE R311 AND R312.
  
 12) THE FOOTINGS FOR THE STAIRS ARE
 REQUIRED BY R403.1.4 TO HAVE A MINIMUM
 DEPTH OF 12" BELOW THE UNDISTURBED
 GROUND SURFACE.
  
 13) THE FLOOR/CEILING ASSEMBLY OF THE
 GARAGE IS REQUIRED BY R309.2 TO BE
 SEPARATED FROM THE HABITABLE SPACE ABOVE
 BY 5/8" TYPE X GYPSUM BOARD.
  
 14) THE SECTION ON A1 SPECIFIES 2X6
 STUDS 16"OC AND THE WALL LEGEND ON A2
 SPECIFIES A 4" WOOD PARTITION.
  
 15) THE ROOF NAILING NOTE ON A4
 SPECIFIES 8D COMMON NAILS AND ON A1 10D
 NAILS ARE SPECIFIED.
  
 16) FBC TABLE 2304.9.1 REQUIRES ROOF
 SHEATHING TO BE NAILED AT 4"OC AT THE
 EDGES AND 6"OC IN THE FIELD IN ZONE 3.
  
 17) SPECIFY HOW MANY 10D NAILS PER TILE
 WILL BE USED TO ATTACH THE ROOF TILES.
  
 18) THE ENERGY CALC. FORMS ARE REQUIRED
 TO BE SIGNED BY THE OWNER/AGENT. THE
 ENERGY CLAC. FORM SPECIFIES R-11 IN THE
 WOOD WALLS AND R-19 IN THE FLOOR. THE
 PLANS SPECIFY R-19 IN THE WALLS AND DO
 NOT SPECIFY FLOOR INSULATION.
  
 19) THE PRODUCT APPROVAL SUBMITTED FOR
 THE GUEST COTTAGE DOOR IS NOT IMPACT
 RATED AND IS REQUIRED TO BE SHUTTERED.
 SUBMIT PRODUCT APPROVAL FOR IMPACT
 PROTECTION. SPECIFY THE ANCHORS,
 SPACING, ETC. THAT WILL BE USED ON THE
 PRODUCT APPROVAL.
  
 20) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
 SUBMIT PRODUCT APPROVALS FOR THE ROOF
 TILES, STORM PANELS AND TRUSS
 CONNECTORS.
  
 21)W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-10 Cont ID  
Sent By btrobaug Date 2006-08-10 Time 17:40 Rev Time 0.33
Received By btrobaug Date 2006-08-10 Time 17:05 Sent To P
Notes
2006-08-10 00:00:00 
  
  
 NONCOMPLIANT
  
 THE PLAN INDICATES AN ADDITION ON THE
 EXISTING DWELLING BUT NO PLANS SUBMITTED
 FOR THIS WORK. SUBMIT PLANS FOR SCOPE OF
 WORK. 10601 FBC AS AMMENDED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-10 Cont ID  
Sent By mmiller Date 2006-08-10 Time 15:11 Rev Time 0.00
Received By mmiller Date   Time   Sent To E
Notes
2006-08-10 00:00:00SENT "E BOX"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-22 Cont ID  
Sent By rmcdouga Date 2006-08-22 Time 11:05 Rev Time 0.00
Received By rmcdouga Date 2006-08-01 Time 13:50 Sent To  
Notes
2006-08-01 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-21 Cont ID  
Sent By tgordon Date 2006-08-21 Time 08:31 Rev Time 0.15
Received By tgordon Date 2006-08-21 Time 08:31 Sent To B
Notes
2006-08-21 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT, PER 2004 FBC
 13-600.3.ABC.2
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-08-19 Cont ID  
Sent By pschmitz Date 2006-08-19 Time 10:33 Rev Time 0.00
Received By pschmitz Date 2006-08-19 Time 10:14 Sent To M
Notes
2006-08-19 00:00:00SEE SCOPE OF WORK ON PERMIT APPLICATION
 PHASE I
 TWO CAR GARAGE AND 2ND FLOOR APT ONLY.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-09 Cont ID  
Sent By mmclean Date 2006-08-09 Time 11:20 Rev Time 0.00
Received By mmclean Date 2006-08-09 Time 11:20 Sent To I
Notes
2006-08-28 00:00:008/28/06 THE CUSTOMER MUST REMOVE KITCHEN
 FROM ACCESSORY STRUCTURE.
  
  
2006-08-09 00:00:00DENIED,
 1. PLEASE SUBMIT A COPY OF CURRENT
 SHOWING WHAT IS LOCATED ON THE PROPERTY
 AND WHAT IS BEING PROPOSED.
 2. SITEPLAN SHOW A FEW PROPOSED WORK AND
 NEED ONLY TO SHOW WHAT IS BEING APPLIED
 FOR. ALSO, THE SITEPLAN DOES NOT PROVIDE
 SETBACK OF THE EXISTING STRUCTURE AND
 THE SETBACK OF THE PROPOSED ADDITION TO
 EXISTING STRUCTURE.
 3. PERMIT APPLICATION IS CROSSED OUT TO
 WHAT IS BEING DONE AND THE SYSTEMS SHOW
 SOMETHING DIFFERENT, PLEASE CLEARLY
 STATES WHAT THE PROPOSED WORK IS.
 4. MUST PULL A SEPARATE PERMIT FOR THE
 PROPOSED CBS WALL/GATE/FENCE WITH CITY
 OF WEST PALM BEACH UTILITY EASEMENT
 APPROVAL.
 5. THE SITEPLAN MUST SHOW ALL & NEW
 DRIVEWAY/WALKWAY.
 6. NEED TO PROVIDE ADDITIONAL PARKING
 FOR THE PROPOSED TWO STORY ACCESSORY
 STRUCTURE.
 7. SITEPLAN DOES NOT SHOW THE COMPLETE
 LOT TO KNOW WHERE THE PROPERTY LINE AND
 WHAT THE SETBACK SHOULD BE FOR THE
 EXISTING AND PROPOSED. NEED A COMPLETE
 SITEPLAN
 8. WALL MUST MEET THE 20FT VISIBILITY
 TRIANGLE ON O STREET & FLORIDA AVE
  
 NOTE: AT ANY ROAD INTERSECTION,
 VISIBILITY SHALL NOT BE OBSCURED BY THE
 CONSTRUCTION, PLACEMENT, OR MAINTENANCE
 OF A STRUCTURE WALL, SIGN, FENCE, BERM
 PLANT MATERIAL, SHRUBS, OR ANY SIMILAR
 ITEM BETWEEN 18 INCHES OR EIGHT POINT
 WHERE PROPERTY LINES MEET AT THE CORNER,
 THEN 20FT ALONG THE FRONT PROPERTY LINE
 20FT FROM THE POINT OF BEGINING, AND
 THENCE TO THE POINT OF BEGINING.IN THE
 EVENT THE CORNER OF AN INTERSECTION IS
 ROUNDED, THE MEASUREMENT SHALL BEGIN AT
 THE POINT THE PROPERTY LINES WOULD MEET
 WITHOUT ROUNDING. (SEE FIGURE X-1).
  
 9. THE TOTAL SQ FT ALLOWED FOR ACCESSORY
 APT IS 800SQ SEC 94-305. PROPOSED TWO
 STORY IS OVER THE REQUIREMENTS TOTAL
 968.
 10. THE EXTERIOR STAIRS MUST BE SHOWN ON
 THE SURVEY AS PART OF THE REQUIRED
 SETBACK FROM PROPERTY LINE.
 11. MAXIMUM HEIGHT ALLOWED FOR ACCESSORY
 STRUCUTRE IS 25FT ONLY.
 12. PLANS ARE NOT PROVIDE FOR THE
 PROPOSED ADDITION TO THE EXISTING
 STRUCTURE AS WELL AS THE NEW PANTRY AND
 NEW ENTRY
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720