Plan Review Details - Permit 06071876
Plan Review Stops For Permit 06071876
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-10-05 Cont ID  
Sent By rmcdouga Date 2006-10-05 Time 07:27 Rev Time 0.00
Received By rmcdouga Date 2006-10-05 Time 06:59 Sent To  
Notes
2006-10-04 00:00:00BUILDING PROVISO
  
 1) MINIMUM FIXTURE CLEARANCES MUST BE
 MAINTAINTED AS SPECIFIED IN FBC R307.1,
 IN NEW BATHROOM. SEE ATTACHMENT.
  
 2) GLASS SHOWER ENCLOSURE MUST BE SAFETY
 GLAZING AS REQUIRED BY FBC R308.4.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-21 Cont ID  
Sent By rmcdouga Date 2006-08-21 Time 11:28 Rev Time 0.00
Received By rmcdouga Date 2006-08-21 Time 11:28 Sent To  
Notes
2006-08-21 00:00:00BUILDING DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE WINDOW IN THE NEW BATHROOM MUST
 COMPLY WITH FBC R308.4 (5). SAFETY
 GLAZING IS REQUIRED IN THE FOLLOWING
 LOCATION.
 5.GLAZING IN DOORS AND ENCLOSURES
 FOR HOT TUBS, WHIRLPOOLS, SAUNAS, STEAM
 ROOMS, BATHTUBS AND SHOWERS. GLAZING IN
 ANY PART OF A BUILDING WALL ENCLOSING
 THESE COMPARTMENTS WHERE THE BOTTOM
 EXPOSED EDGE OF THE GLAZING IS LESS THAN
 60 INCHES (1524 MM) MEASURED VERTICALLY
 ABOVE ANY STANDING OR WALKING SURFACE.
  
 3) SPECIFY THE NEW WALLS ON THE PLANS.
  
 4) PROVIDE A DETAIL OF NEW WALLS.
 SPECIFY FRAMING MATERIAL, STUD SPACING,
 WALL SHEATHING.
  
 5) SPECIFY THE BATHROOM WALL AND FLOOR
 FINISHES.
  
 6) FBC R303.3BATHROOMS.
 BATHROOMS, WATER CLOSET COMPARTMENTS AND
 OTHER SIMILAR ROOMS SHALL BE PROVIDED
 WITH AGGREGATE GLAZING AREA IN WINDOWS
 OF NOT LESS THAN 3 SQUARE FEET (0.279 M
 2 ), ONE-HALF OF WHICH MUST BE OPENABLE.
  
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE
 REQUIRED WHERE ARTIFICIAL LIGHT AND A
 MECHANICAL VENTILATION SYSTEM ARE
 PROVIDED. THE MINIMUM VENTILATION RATES
 SHALL BE 50 CFM (23.6 L/S) FOR
 INTERMITTENT VENTILATION OR 20 CFM (9.4
 L/S) FOR CONTINUOUS VENTILATION.
 VENTILATION AIR FROM THE SPACE SHALL BE
 EXHAUSTED DIRECTLY TO THE OUTSIDE.
 MUST HAVE WINDOW THAT COMPLIES OR
 MECHANICAL VENTILATION.
  
 7) TWO COMPLETE SETS OF PLANS ARE
 REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-09-19 Cont ID  
Sent By btrobaug Date 2006-09-19 Time 11:08 Rev Time 0.33
Received By btrobaug Date 2006-09-19 Time 10:56 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-10 Cont ID  
Sent By btrobaug Date 2006-08-10 Time 06:51 Rev Time 0.50
Received By btrobaug Date 2006-08-10 Time 06:40 Sent To P
Notes
2006-08-10 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2.
  
 2} TWO SETS OF ALL DOCUMENTS MUST BE
 SUBMITTED FOR REVIEW PER 106.1 FBC AS
 AMMENDED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-12 Cont ID  
Sent By adarroug Date 2006-09-12 Time 09:18 Rev Time 0.00
Received By adarroug Date 2006-09-12 Time 09:18 Sent To E
Notes
2006-09-12 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-21 Cont ID  
Sent By rmcdouga Date 2006-08-21 Time 11:28 Rev Time 0.00
Received By rmcdouga Date 2006-08-01 Time 14:47 Sent To  
Notes
2006-08-01 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-08-10 Cont ID  
Sent By tgordon Date 2006-08-10 Time 10:39 Rev Time 0.15
Received By tgordon Date 2006-08-10 Time 10:39 Sent To B
Notes
2006-08-10 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-10-04 Cont ID  
Sent By jleech Date 2006-10-04 Time 12:49 Rev Time 0.00
Received By jleech Date 2006-10-04 Time 12:49 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-08-10 Cont ID  
Sent By jleech Date 2006-08-10 Time 09:25 Rev Time 0.00
Received By jleech Date 2006-08-10 Time 09:25 Sent To M
Notes
2006-08-10 00:00:00DENIED;
 1.PERSON RESPONSIBLE FOR DRAWING NEEDS
 TO PRINT AND SIGN PLANS.
 2.TWO SETS OF DRAWINGS ARE REQUIRED.
 3.A TWO WAY CLEANOUT IS REQUIRED AT THE
 JUNCTION OF THE BUILDING DRAIN AND THE
 BUILDING SEWER.
 3.SHOWER MUST HAVE 900 SQ. INS. INSIDE
 CURB. PLEASE PROVIDE MORE INFORMATION ON
 SHOWER SIZE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695


Account Summary | Usage Policy | Privacy Policy