Plan Review Details - Permit 06071808
Plan Review Stops For Permit 06071808
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-09-25 Cont ID  
Sent By rmcdouga Date 2006-09-25 Time 07:54 Rev Time 0.00
Received By rmcdouga Date 2006-09-25 Time 07:54 Sent To  
Notes
2006-09-25 00:00:00REVISED ROOFING FROM BUR TO POLYGLASS
 MODIFIED BITUMEN OVER WOOD DECK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-08-09 Cont ID  
Sent By rmcdouga Date 2006-08-09 Time 08:41 Rev Time 0.00
Received By rmcdouga Date 2006-08-09 Time 07:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-01 Cont ID  
Sent By rmcdouga Date 2006-08-01 Time 13:35 Rev Time 0.00
Received By rmcdouga Date 2006-08-01 Time 13:35 Sent To  
Notes
2006-08-01 00:00:00DENIED
  
 1) THE ENGINEERING THAT WAS SUBMITTED IS
 BASED ON PAGE 11 OF NOA 03-0501.05WITH
 -45 PSF DESIGN PRESSURE. THE NOA
 SUBMITTED SPECIFIES A -52.5 PSF DESIGN
 PRESSURE LOCATED ON PAGE 18 OF THE SAME
 NOA. THE ENGINEERING MUST CORRESPOND TO
 THE SPECIFIED SYSTEM IN THE NOA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2006-07-28 Cont ID  
Sent By ptjomsto Date 2006-07-28 Time 13:20 Rev Time 0.00
Received By ptjomsto Date 2006-07-28 Time 13:20 Sent To  
Notes
2006-07-28 00:00:00HISTORIC APPROVED 7/28/06 BY JUDGE


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved