Plan Review Details - Permit 06071793
Plan Review Stops For Permit 06071793
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-08-15 Cont ID  
Sent By mjacobs Date 2006-08-15 Time 09:21 Rev Time 0.00
Received By mjacobs Date 2006-08-15 Time 07:13 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-18 Cont ID  
Sent By btrobaug Date 2006-10-18 Time 11:46 Rev Time 0.33
Received By btrobaug Date 2006-10-18 Time 11:46 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-23 Cont ID  
Sent By btrobaug Date 2006-08-23 Time 07:23 Rev Time 0.50
Received By btrobaug Date 2006-08-23 Time 06:42 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-08 Cont ID  
Sent By btrobaug Date 2006-08-08 Time 15:02 Rev Time 0.50
Received By btrobaug Date 2006-08-08 Time 13:35 Sent To P
Notes
2006-08-08 00:00:00 
  
 PLEASE SUBMIT MANUFACTURERS
 SPECIFICATIONS FOR THE "BADU JET", AND
 LOCATE IN ELECTRICAL SCHEMATIC.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-10-14 Cont ID  
Sent By adarroug Date 2006-10-14 Time 14:14 Rev Time 0.00
Received By adarroug Date 2006-10-14 Time 14:14 Sent To P
Notes
2006-10-14 14:14:40TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-09-25 Cont ID  
Sent By adarroug Date 2006-09-25 Time 15:42 Rev Time 0.00
Received By adarroug Date 2006-09-25 Time 15:42 Sent To P
Notes
2006-09-25 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-15 Cont ID  
Sent By adarroug Date 2006-09-15 Time 16:10 Rev Time 0.00
Received By adarroug Date 2006-09-15 Time 16:10 Sent To P
Notes
2006-09-15 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-08 Cont ID  
Sent By adarroug Date 2006-09-08 Time 10:57 Rev Time 0.00
Received By adarroug Date 2006-09-08 Time 10:57 Sent To P
Notes
2006-09-08 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-22 Cont ID  
Sent By adarroug Date 2006-08-22 Time 18:31 Rev Time 0.00
Received By adarroug Date 2006-08-22 Time 18:31 Sent To E
Notes
2006-08-22 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-08 Cont ID  
Sent By adarroug Date 2006-08-08 Time 11:25 Rev Time 0.00
Received By adarroug Date 2006-08-08 Time 11:25 Sent To E
Notes
2006-08-08 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-08-15 Time   Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 18:41 Sent To  
Notes
2006-07-31 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 7 Status P Date 2006-11-07 Cont ID  
Sent By mperson Date 2006-11-07 Time 13:10 Rev Time 0.33
Received By mperson Date 2006-11-07 Time 13:10 Sent To PC
Notes
2006-11-07 13:27:04REVISION: CHANGED PIPING SIZE OF BADU-JET MAIN DRAINS
 FROM FOUR INCH (4") TO TWO INCH (2")

Review Stop P PLUMBING
Rev No 6 Status P Date 2006-10-17 Cont ID  
Sent By mperson Date 2006-10-17 Time 15:44 Rev Time 0.33
Received By mperson Date 2006-10-17 Time 15:44 Sent To E
Notes
2006-10-17 15:49:37REVISION: ADDING 4 HP BADU-JET PUMP SYSTEM, CODE
 COMPLIANT TO MEET THREE (3) SECOND RELEASE.

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-09-29 Cont ID  
Sent By mperson Date 2006-09-29 Time 14:18 Rev Time 0.33
Received By mperson Date 2006-09-29 Time 14:18 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-09-21 Cont ID  
Sent By mperson Date 2006-09-21 Time 13:14 Rev Time 0.33
Received By mperson Date 2006-09-21 Time 13:14 Sent To PC
Notes
2006-09-21 00:00:00******DENIED 4TH TIME******
 REFERENCE: FBC-2004 SEC. 402.2 OR
 FBRC-2004 SEC. 4101 SWIMMING POOLS AND
 FBC-2004 CHAPTER 1:
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW:
  
 1. I KNOW THAT IT IS THE INTENT TO
 DELETE THE BADU JET PUMP AND ALL
 COMPONENTS RELATED, BUT PER FBC-2004
 CHAPTER 1 SEC. 106.1, FLORIDA STATUTES
 CHAPTER 471, STATES THAT ANY HAND
 WRITTEN CHANGES TO SIGNED AND SEALED
 ENGINEERED DRAWINGS SHALL BE BY THE
 ENGINEER OF RECORD, STEPHEN M. SINCLAIR,
 P.E. FLORIDA LICENSE NO. 35631,
 INITIALED AND DATED.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-09-14 Cont ID  
Sent By mperson Date 2006-09-14 Time 11:53 Rev Time 0.33
Received By mperson Date 2006-09-14 Time 11:53 Sent To PC
Notes
2006-09-14 00:00:00******DENIED 3RD TIME******
 REFERENCE: FBC-2004 SEC. 402.2 OR
 FBRC-2004 SEC. R4101 SWIMMING POOLS:
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR PLUMBING PLAN REVIEW:
 NOTE: THE SUBMITTED MANUFACTURER SHEETS
 WITH THE MET LABORATORIES, INC.
 CERTIFICATION RECORD, FILE NUMBER,
 E212148 APPROVES THE SUCTION FITTING PER
 ASME/ANSI A112.19.8M. ALL SUCTION AND
 RETURN PIPING TO THE BADU-JET PUMP SHALL
 BE INSTALLED CODE COMPLIANT TO THE
 FOLLOWING COMMENTS.
  
 1) FBC-2004 SEC 424.2.6.6, OR FBCR-2004
 SEC R4101.6.6 ENTRAPMENT PROTECTION FOR
 SUCTION INLETS. (DETAIL REQUIRED)
  
 2) FBC-2004424.2.6.6.3, OR FBCR-2004
 SEC R4101.6.6.3 (1,2,3) ENTRAPMENT
 AVOIDANCE. (DETAIL REQUIRED)
  
 3) FBC-2004 SEC.424.2.6.6.4, OR
 FBCR-2004 SEC. R4101.6.6.4 MINIMUM OF
 TWO SUCTION INLETS SHALL BE PROVIDED FOR
 EA PUMP. SEPARATED BY A MINIMUM OF 3
 FEET OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL REQUIRED)
  
 4) FBC-2004 SEC. 424.6.6 OR FBC-2004
 RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. PLEASE
 SUBMIT AN ENGINEERED TABLE FOR "VENT
 PIPE MAXIMUM LENGTH" INDICATING PUMP
 SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH
 OF THE 1", 1-1/2" PVC VENT PIPE, FROM
 WHERE IT STARTS TO WHERE IT ENDS UP,
 COMPLYING WITH THE THREE SECOND RELEASE.
 (NOTE: THE VENT TABLE ON THE PRINT ONLY
 GOES TO TWO HORSE POWES (2 HP) THE BADU-
 JET PUMP PUMP IS FOUR HORSE POWER (4 HP)
 PLEASE SUBMIT A TABLE FOR THE HORSE
 POWER (4 HP) BADU-JET PUMP.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-08-24 Cont ID  
Sent By mperson Date 2006-08-24 Time 11:39 Rev Time 0.33
Received By mperson Date 2006-08-24 Time 11:38 Sent To PC
Notes
2006-08-24 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 SEC. 402.2 OR
 FBRC-2004 SEC. 4101 SWIMMING POOLS
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR PLUMBING PLAN REVIEW:
 NOTE: THE SUBMITTED SHEETS DO NOT
 ADDRESS PREVIOUS PLAN REVIEW COMMENTS.
  
 1) PLEASE SUBMIT MANUFACTURER'S SPECIFI-
 CATIONS FOR THE "BADU-JET" AND PROVIDE
 THE FOLLOWING INFORMATION INDICATING THE
 SYSTEM IS CODE COMPLIANT.
 2) FBC-2004 SEC 424.2.6.6, OR FBCR-2004
 SEC R4101.6.6 ENTRAPMENT PROTECTION FOR
 SUCTION INLETS. (DETAIL REQUIRED)
 3) FBC-2004 424.2.6.6.2, OR FBCR-2004
 SEC R4101.6.6.2 SHOW COMPLIANCE WITH
 ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUFACTURER INFORMATION FOR
 VAC LOCK. (GIVE DETAIL, SUBMITTAL OR ADD
 TO NOTES)
 4) FBC-2004424.2.6.6.3, OR FBCR-2004
 SEC R4101.6.6.3 (1,2,3) ENTRAPMENT
 AVOIDANCE. (DETAIL REQUIRED)
 5) FBC-2004 SEC.424.2.6.6.4, OR
 FBCR-2004 SEC. R4101.6.6.4 MINIMUM OF
 TWO SUCTION INLETS SHALL BE PROVIDED FOR
 EA PUMP. SEPARATED BY A MINIMUM OF 3
 FEET OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL REQUIRED)
 6) FBC-2004 SEC. 424.6.6 OR FBC-2004
 RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. PLEASE
 SUBMIT AN ENGINEERED TABLE FOR "VENT
 PIPE MAXIMUM LENGTH" INDICATING PUMP
 SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH
 OF THE 1", 1-1/2" PVC VENT PIPE, FROM
 WHERE IT STARTS TO WHERE IT ENDS UP,
 COMPLYING WITH THE THREE SECOND RELEASE.
 (NOTE: THE VENT TABLE ON THE PRINT ONLY
 GOES TO TWO HORSE POWER (2 HP) THE
 "BADU-JET" PUMP IS FOUR HORSE POWER (4-
 HP) PLEASE SUBMIT TABLE FOR SAID PUMP.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-08-10 Cont ID  
Sent By mperson Date 2006-08-10 Time 13:22 Rev Time 0.45
Received By mperson Date 2006-08-10 Time 13:22 Sent To B
Notes
2006-08-10 00:00:00******DENIED******
 REFERENCE: FBC-2004 SEC. 402.2 OR
 FBRC-2004 SEC. 4101 SWIMMING POOLS:
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW:
  
 1) PLEASE SUBMIT MANUFACTURER'S SPECIFI-
 CATIONS FOR THE "BADU-JET" AND PROVIDE
 THE FOLLOWING INFORMATION INDICATING THE
 SYSTEM IS CODE COMPLIANT.
 2) FBC-2004 SEC 424.2.6.6, OR FBCR-2004
 SEC R4101.6.6 ENTRAPMENT PROTECTION FOR
 SUCTION INLETS. (DETAIL REQUIRED)
 3) FBC-2004 424.2.6.6.2, OR FBCR-2004
 SEC R4101.6.6.2 SHOW COMPLIANCE WITH
 ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 4) FBC-2004424.2.6.6.3, OR FBCR-2004
 SEC R4101.6.6.3 (1,2,3) ENTRAPMENT
 AVOIDANCE. (DETAIL REQUIRED)
 5) FBC-2004 SEC.424.2.6.6.4, OR
 FBCR-2004 SEC. R4101.6.6.4 MINIMUM OF
 TWO SUCTION INLETS SHALL BE PROVIDED FOR
 EACH PUMP. SEPARATED BY A MINIMUM OF 3
 FEET OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL REQUIRED)
 6) FBC-2004 SEC. 424.6.6 OR FBC-2004
 RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. PLEASE
 SUBMIT AN ENGINEERED TABLE FOR "VENT
 PIPE MAXIMUM LENGTH" INDICATING PUMP
 SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH
 OF THE 1" OR 1-1/2" PVC VENT PIPE, FROM
 WHERE IT STARTS TO WHERE IT ENDS UP,
 COMPLYING WITH THE THREE SECOND RELEASE.
 (NOTE: THE VENT TABLE ON THE DRAWING
 ONLY GOES TO 2 HP THE "BADU-JET" PUMP IS
 4 HP)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2006-08-07 Cont ID  
Sent By mmclean Date 2006-08-07 Time 15:39 Rev Time 0.00
Received By mmclean Date 2006-08-07 Time 15:39 Sent To I
Notes
2006-08-07 00:00:00THE PROPOSED POOL EQUIPMENT SHALL NOT BE
 CLOSER THAN 6FT FROM REAR PROPERTY LINE.