Plan Review Details - Permit 06071740
Plan Review Stops For Permit 06071740
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-26 Cont ID  
Sent By alange Date 2006-09-26 Time 13:55 Rev Time 0.50
Received By alange Date 2006-09-26 Time 12:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-18 Cont ID  
Sent By alange Date 2006-08-18 Time 08:57 Rev Time 0.50
Received By alange Date 2006-08-18 Time 08:55 Sent To  
Notes
2006-08-18 00:00:00DENIED
  
 1.ENGINEERING FROM HILLMAN
 ENGINEERING SHALL BE ORIGINAL SIGNED AND
 SEALED DOCUMENTS.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-08-08 Cont ID  
Sent By btrobaug Date 2006-08-08 Time 15:52 Rev Time 0.50
Received By btrobaug Date 2006-08-08 Time 15:13 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-09-18 Cont ID  
Sent By mperson Date 2006-09-18 Time 11:49 Rev Time 0.33
Received By mperson Date 2006-09-18 Time 11:49 Sent To B
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-08-11 Cont ID  
Sent By mperson Date 2006-08-11 Time 08:07 Rev Time 0.33
Received By mperson Date 2006-08-11 Time 08:07 Sent To M
Notes
2006-08-11 00:00:00REFERENCE: GAS PERMIT #06071744

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-14 Cont ID  
Sent By adarroug Date 2006-09-14 Time 13:31 Rev Time 0.00
Received By adarroug Date 2006-09-14 Time 13:31 Sent To M
Notes
2006-09-14 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-08 Cont ID  
Sent By adarroug Date 2006-08-08 Time 11:38 Rev Time 0.00
Received By adarroug Date 2006-08-08 Time 11:38 Sent To E
Notes
2006-08-08 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-18 Cont ID  
Sent By alange Date 2006-08-18 Time 08:59 Rev Time 0.00
Received By alange Date 2006-07-31 Time 16:04 Sent To  
Notes
2006-07-31 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-09-18 Cont ID  
Sent By tgordon Date 2006-09-18 Time 08:04 Rev Time 0.20
Received By tgordon Date 2006-09-18 Time 08:04 Sent To P
Notes
2006-09-18 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 FOLLOW MANUFACTURE'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING,AND PROVIDE MANUFACTURE'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-11 Cont ID  
Sent By tgordon Date 2006-08-11 Time 16:40 Rev Time 0.15
Received By tgordon Date 2006-08-11 Time 16:40 Sent To B
Notes
2006-08-11 00:00:00*** DENIED ***
 1) SEE ZONING REVIEW, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-09-12 Cont ID  
Sent By mmclean Date 2006-09-12 Time 14:30 Rev Time 0.00
Received By mmclean Date 2006-09-12 Time 14:30 Sent To I
Notes
2006-09-12 00:00:00NOTE:
 THE PROPOSED GENERATOR SHALL NOT BE
 CLOSER THAN 6FT FROM SIDE PROPERTY LINE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-07 Cont ID  
Sent By mmclean Date 2006-08-07 Time 17:45 Rev Time 0.00
Received By mmclean Date 2006-08-07 Time 17:45 Sent To I
Notes
2006-08-07 00:00:00DENIED,
 1. PLEASE PROVIDE A CURRENT AND FULL
 SURVEY OF THE PROPERTY THAT HAS THE
 ADDRESS OF THE PROPERTY DE SOTA RD &
 WASHINGTON ROAD.
 2. INFORMATION PROVIDED DOES NOT SHOW
 ALL THAT IS NEEDED TO CORRECTLY REVIEW
 THE PLANS.
 3. THE SURVEY MUST PROVIDE THE SETBACKS
 OF THE EXISTING STRUCUTRES FROM PROPERTY
 LINE.
  
 NOTE:
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720