Plan Review Details - Permit 06071634
Plan Review Stops For Permit 06071634
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-12-04 Cont ID  
Sent By rmcdouga Date 2006-12-04 Time 13:29 Rev Time 0.00
Received By rmcdouga Date 2006-12-04 Time 12:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-17 Cont ID  
Sent By rmcdouga Date 2006-10-17 Time 11:14 Rev Time 0.00
Received By rmcdouga Date 2006-10-17 Time 11:11 Sent To  
Notes
2006-10-17 11:09:55BUILDING DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE EXISTING BEDROOM TO WHICH THE NEW
 ADDITION IS ATTACHED MUST RETAIN AN
 EMERGENCY EGRESS EXIT THAT COMPLIES WITH
 FBC R310.1. SPECIFY THE SIZE OF THE REMAINING BEDROOM
 WINDOW ON THE PLANS, INDICATING THAT IT COMPLIES WITH
 EGRESS REQUIREMENTS.
  
 4) SPECIFY ON THE PLANS THE TERMITE TREATMENT REQUIRED
 BY FBC R320.
  
 5) SPECIFY ON THE PLANS THE UNDER FLOOR SPACE
 VENTILATION, SIZE AND LOCATION OF VENTS.
 SEE FBC R408.1 AND R408.2.
  
 6) SPECIFY ON THE PLANS THE ACCESS TO THE UNDER FLOOR
 SPACE AS REQUIRED BY FBC R408.3.
  
 7) THE LANDING AT THE REAR FRENCH DOORS
 SHALL COMPLY WITH FBC R311.4.3. A
 MINIMUM OF 36" IN THE DIRECTION OF
 TRAVEL IS REQUIRED. INDICATE THIS ON THE PLANS.
  
 8) SPECIFY THE TREAD DEPTHS AND RISE
 HEIGHTS. SEE FBC R311.5.3. PROVIDE A DETAIL SHOWING
 THIS ON THE PLANS.
  
 9)FBC R312.1 REQUIRES PORCHES MORE THAN 30" AND OPEN
 SIDES OF STAIRS WITH TOTAL RISE OF MORE THAN 30" TO
 HAVE GUARDS. INDICATE THE HEIGHT OF THE EXTERIOR
 PORCHES OR LANDINGS ON THE PLANS AND IF MORE THAN 30"
 ABOVE GRADE PROVIDE DETAILS OF THE GUARDRAILS ON THE
 PLANS.
  
 10) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY
 THE FASTENER TYPE, FASTENER SPACING, THE
 MOUNT TYPE, ETC. SEE ATTACHMENT. SEE ATTACHED
 INSTALLATION SCHEDULE.
  
 11) W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. THE ENGINEER IS REQUIRED
 TO REVIEW AND APPROVE THE PRODUCT APPROVALS IN
 WRITING.
  
 12) SUBMIT PRODUCT APPROVALS FOR THE
 TRUSS CONNECTORS, HANGERS AND STRAPS.
  
 13) THE FL COVERSHEETS SUBMITTED FOR THE
 WINDOWS DOORS, AND STORM PANELS ARE FROM DIFFERENT
 MANUFACTURERS THAN THE MIAMI-DADE NOAS. THE NOAS FOR
 THE LAWSON WINDOWS AND DOORS AND FROMFLORIDA STORM
 PANELS ARE ACCEPTABLE WITHOUT THE FL COVER SHEETS.
 HOWEVER, THEY STILL MUST BE APPROVED IN WRITING BY THE
 ENGINEER.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-21 Cont ID  
Sent By rmcdouga Date 2006-08-21 Time 08:46 Rev Time 0.00
Received By rmcdouga Date 2006-08-21 Time 07:14 Sent To  
Notes
2006-08-21 00:00:00BUILDING DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE EXISTING BEDROOM TO WHICH THE NEW
 ADDITION IS ATTACHED MUST RETAIN AN
 EMERGENCY EGRESS EXIT THAT COMPLIES WITH
 FBC R310.1.
  
 4) THE ENGINEER IS REQUIRED TO LIST THE CERTIFICATE OF
 AUTHORIZATION NUMBER FOR
 THE BUSINESS AS REQUIRED BY FAC
 61G15-23.002.
  
 5) SPECIFY THE TERMITE TREATMENT
 REQUIRED BY FBC R320.
  
 6) SPECIFY THE UNDER FLOOR SPACE
 VENTILATION, SIZE AND LOCATION OF VENTS.
 SEE FBC R408.1 AND R408.2.
  
 7) SPECIFY THE ACCESS TO THE UNDER FLOOR
 SPACE AS REQUIRED BY FBC R408.3.
  
 8) THE LANDING AT THE REAR FRENCH DOORS
 SHALL COMPLY WITH FBC R311.4.3. A
 MINIMUM OF 36" IN THE DIRECTION OF
 TRAVEL IS REQUIRED.
  
 9) SPECIFY THE TREAD DEPTHS AND RISE
 HEIGHTS. SEE FBC R311.5.3.
  
 10) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY
 THE FASTENER TYPE, FASTENER SPACING, THE
 MOUNT TYPE, ETC. SEE ATTACHMENT.
  
 11) W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 12) SUBMIT PRODUCT APPROVALS FOR THE
 TRUSS CONNECTORS, HANGERS AND STRAPS.
  
 13) THE FL COVERSHEETS SUBMITTED FOR THE
 WINDOWS DOORS, AND STORM PANELS ARE NOT
 VALID. THEY ARE NO LONGER LISTED ON THE
 STATE WEBSITE OR ARE STILL PENDING
 APPROVAL. HOWEVER, THEY HAVE CURRENT
 MIAMI DADE NOAS, WHICH ARE ACCEPTABLE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-06-28 Cont ID  
Sent By dpalmer Date 2007-06-28 Time 09:14 Rev Time 0.00
Received By dpalmer Date 2007-06-28 Time 09:13 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-11-20 Cont ID  
Sent By dpalmer Date 2006-11-20 Time 14:48 Rev Time 0.00
Received By dpalmer Date 2006-11-20 Time 13:09 Sent To M
Notes
2006-11-20 14:50:27****** PROVISO ********
  
 1) NOTE: PLEASE SEE 310.15B6 FOR THE MINIMUM SIZE FOR
 THE FEEDER CONDUCTORS FOR NEW 125A PANEL FROM THE 125A
 BREAKER LOCATED IN NEW 200A METER/MAIN COMBO PANEL.
 THE #3'S AS SHOWN ON PANEL SCHEDULE ARE NOT LARGE
 ENOUGH.
 PLEASE SEE RISER SHOWS 3-3/0'S WHICH ARE WELL OVER THE
 MINIMUM REQUIRED. THE 3/0'S ARE PERMITTED, HOWEVER WILL
 MOST LIKELY NOT FIT INTO A 125A BREAKER.
  
  
 *** PLEASE CORRELATE AND ADJUST THE ABOVE BEFORE ANY
 ROUGH/SLAB INSPECTION.
 "THIS WILL BE REQUIRED BEFORE THE INSPECTION FOR THE
 REQUIRED FOOTER STEEL CONNECTION"
  
 ** IF PLANS COME BACK FOR ANY REASON WITH COMMENTS FROM
 ANY OF THE OTHER TRADES, PLEASE ADDRESS AT THIS TIME.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-01 Cont ID  
Sent By dpalmer Date 2006-10-01 Time 09:37 Rev Time 0.00
Received By dpalmer Date 2006-10-01 Time 08:47 Sent To M
Notes
2006-10-01 00:00:00**** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE SOME FROM PREVIOUS REVIEW
 AND SOME NEW NOTES.
 NOTES BELOW ARE TAKEN DIRECLTY FROM
 PREVIOUS REVIEW WITH NEW NOTES ADDED.
  
 1) NOTE: OK.
  
 2) NOTE: OK, 22K SHOWN.
  
 3) NOTE: NO, SERVICE IS NOT CLEAR.
 PLEASE SEE A NEW SERVICE IS BEING
 INSTALLED ON ADDTION WHICH IS OK,
 HOWEVER THERE IS A 150A BREAKER BEING
 NOTED, HOWEVER THIS DOES NOT INDICATE
 WHERE THIS IS GOING. PLEASE ALSO SEE THE
 EXISTIGN METER/MAIN PANEL LOCATION IS
 BEING NOTED AS BEING CHANGED TO A
 "J-BOX"?? PLEASE CLARIFY THIS . IS THERE
 ANOTHER SUB FEED TO AND PANEL SOMEWHERE
 ELSE? AS PLANS ONLY SHOW THIS AS A
 'J-BOX" HOW ARE ALL THE EXISTIGN
 CIRCUITS BEING FED? IF THIS EXISTING
 PANEL IS WP RATED, W/OUT THE METER BEING
 INSTALLED THEN THE PLEASE INDICATE, AS
 WELL ASFEEDERS ALONG WITH SHOWING THE
 CONDUCTORS, AS COUNDUIT ONLY MENTIONS 2"
 WITH #6 GROUND??
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PANEL NOTES MENTIONS
 THIS IS AN EXISTING SERVICE YET PLANS
 AND RISER SHOWS THIS AS NEW> PLEASE
 CORRELATE AND PLACE ON PLANS WHAT THIS
 IS?
 PLEASE ALSO SEE LOCATION OF ALL SERVICE
 EQUIPMENT SHOULD BE SHOWN.
 PLEASE SEE TWO AREAS OF PLANS WHERE
 PANELS SEEM TO BE DRAWN. PLEASE SEE SEE
 IF NOTE MENTIONS THIS IS EXISTING, IT IS
 UNCLEAR HOW THIS IS POSSIBLE WHEN ONE
 LOCATION ON PLANS HAS NOT BEENBUILT
 YET??
 240.4, 110.26, UNABLE TO VERIFY AT THIS
 TIME.
 FBC 106.1.2 ADMIN SECT.
  
 4) NOTE: OK, ALL SD'S ARE NOW SHOWN.
  
  
 5) NOTE: OK, HOWEVER PLEASE SEE CIRCUIT
 WHICH SHOWS 1.92 LOAD ON A #14/15A
 CIRCUIT. PLEASE SEE THE MAX KVA ONA 15A
 NCIRCUIT IS 1440VA. PLEASE ADJUST.
 THE NEW AF CIRCUITS ARE NOTED .
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SPECIFY THE NEW GENERAL
 LIGHTING CIRCUIT AS THE CIRCUITS IN
 BEDRMS WHERE THIS ADDITION IS BEING
 BUILT REQUIRES ARC FAULT FOR
 ALL,INCLUDING LTS, RECEPTS, FANS, SD'S
 ETC.
 PLEASE SEE ONLY CIRUITS OUTSIDE THE
 BEDRM UNDER THE CURRENT NEC 2002 DO NOT
 REQUIRE THIS.
 210.12B, 408.4
  
 6) NOTE: NO, PLEASE SEE NOTE ## ABOVE AS
 THESE ARE ABOUT THE SAME NOTE.
  
 ** PREVIOUS REVIE WNOTE **
 PLEASE VERIFY THE NEW "J-BOX"
 WITH WHAT IS BEING SHOWN WITH A 2"
 CONDUIT AND #4. WHAT IS THIS FOR?
  
  
 ******** NEW NOTE **********
  
 7) NOTE: PLEASE SEE PREVIOUS PLANS CAME
 IN BEING SIGNED AND SEALED BY AN
 ENGINEER, HOWEVER THESE PLANS ARE NOW
 COMING BACK WITHOUT ANYTHING??
 PLEASE KNOW, UNDER FS 481.229, THE PLANS
 FOR THE ELECTRICLA , PLUMB, MECH AND
 ELECTRICAL DO "NOT" HAVE TO BE SIGNED
 AND SEALED BY AN ENGINEER OR ARCHITECT
 WHEN IT COMES TO A SF RESIDENCE. THESE
 MAY BE DONE BY THE CONTRACTOR/OR THE O/B
 IN THIS CASE. PLEASE DO KNOW HOWEVER THE
 PLANS ARE REQUIRED TO CONTAIN THE
 PRINTED NAME AND THE SIGNATURE OF THE
 PERSON TAKING RESPONSIBILTY OF SAID
 PLANS.
 FS 481.229,
 FBC 106.1.2 ADMIN SECT.
  
 8) NOTE: PLEASE SEE MISSING RECEPT W/IN
 6' OF REAR DOOR INSIDE, REDLINED ON ONE
 SET.210.52
  
 ** PLEASE CALL TO GO OVER THE SCENARIO
 OF THE SERVICE.
  
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-09 Cont ID  
Sent By dpalmer Date 2006-08-09 Time 08:40 Rev Time 0.00
Received By dpalmer Date 2006-08-09 Time 07:43 Sent To M
Notes
2006-08-09 00:00:00*** UNSAT ***
  
  
 1) NOTE: PLEASE SEE NOTE #7 WHICH IS
 STATING A CODE NOT FROM THE 2002 NEC. IN
 FACT IT APPEARS TO BE FROM THE 1996 NEC.
 PLEASE ADJUST.
  
 2) NOTE: PLEASE VERIFY WITH FPL THE
 AVAILABLE FAULT CURRENT AND THEN PLANS
 CORRELATE THAT RATING WITH EQUIPMENT ON
 PLANS. PLEASE SEE PLANS NOTE TWO
 SEPARATE AIC RATINGS.
 PLEASE SEE 110.9.
 FBC 106.1.2 ADMIN SECT.
  
 3) NOTE: PLEASE SEE PANEL NOTES MENTIONS
 THIS IS AN EXISTING SERVICE YET PLANS
 AND RISER SHOWS THIS AS NEW> PLEASE
 CORRELATE AND PLACE ON PLANS WHAT THIS
 IS?
 PLEASE ALSO SEE LOCATION OF ALL SERVICE
 EQUIPMENT SHOULD BE SHOWN.
 PLEASE SEE TWO AREAS OF PLANS WHERE
 PANELS SEEM TO BE DRAWN. PLEASE SEE SEE
 IF NOTE MENTIONS THIS IS EXISTING, IT IS
 UNCLEAR HOW THIS IS POSSIBLE WHEN ONE
 LOCATION ON PLANS HAS NOT BEENBUILT
 YET??
 240.4, 110.26, UNABLE TO VERIFY AT THIS
 TIME.
 FBC 106.1.2 ADMIN SECT.
  
 4) NOTE: PLEASE NOTE ABOVE ON LANS
 MENTIONS THE REQUIEMENT FOR SD'S IN
 EXISTING DWELLING, YET THE EXISTING
 DWELLING LAYOUT IS NOT SHOWN SHOWING
 SD'S INSIDE AND OUTSIDE THE EXISTING
 BEDRMS.
 R313, FBC 2004 NFPA-72 11.5.1.1, 11.8.3
  
 5) NOTE: PLEASE SPECIFY THE NEW GENERAL
 LIGHTING CIRCUIT AS THE CIRCUITS IN
 BEDRMS WHERE THIS ADDITION IS BEING
 BUILT REQUIRES ARC FAULT FOR
 ALL,INCLUDING LTS, RECEPTS, FANS, SD'S
 ETC.
 PLEASE SEE ONLY CIRUITS OUTSIDE THE
 BEDRM UNDER THE CURRENT NEC 2002 DO NOT
 REQUIRE THIS.
 210.12B, 408.4
  
 6) NOTE: PLEASE VERIFY THE NEW "J-BOX"
 WITH WHAT IS BEING SHOWN WITH A 2"
 CONDUIT AND #4. WHAT IS THIS FOR?
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-06-27 Cont ID  
Sent By adarroug Date 2007-06-27 Time 13:32 Rev Time 0.00
Received By adarroug Date 2007-06-27 Time 13:32 Sent To E
Notes
2007-06-27 13:33:13TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-11-17 Cont ID  
Sent By adarroug Date 2006-11-17 Time 09:50 Rev Time 0.00
Received By adarroug Date 2006-11-17 Time 09:50 Sent To E
Notes
2006-11-17 09:50:25TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-15 Cont ID  
Sent By adarroug Date 2006-11-15 Time 11:34 Rev Time 0.00
Received By adarroug Date 2006-11-15 Time 11:34 Sent To Z
Notes
2006-11-15 11:35:10TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-26 Cont ID  
Sent By adarroug Date 2006-09-26 Time 14:46 Rev Time 0.00
Received By adarroug Date 2006-09-26 Time 14:46 Sent To E
Notes
2006-09-26 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-07 Cont ID  
Sent By adarroug Date 2006-08-07 Time 14:22 Rev Time 0.00
Received By adarroug Date 2006-08-07 Time 14:22 Sent To E
Notes
2006-08-07 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-21 Cont ID  
Sent By rmcdouga Date 2006-08-21 Time 08:46 Rev Time 0.00
Received By rmcdouga Date 2006-07-28 Time 13:11 Sent To  
Notes
2006-07-28 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-11-21 Cont ID  
Sent By tgordon Date 2006-11-21 Time 10:37 Rev Time 0.20
Received By tgordon Date 2006-11-21 Time 10:37 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-10-02 Cont ID  
Sent By tgordon Date 2006-10-02 Time 11:07 Rev Time 0.25
Received By tgordon Date 2006-10-02 Time 11:07 Sent To P
Notes
2006-10-02 00:00:00*** DENIED ***
 1) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-08-10 Cont ID  
Sent By tgordon Date 2006-08-10 Time 08:24 Rev Time 0.20
Received By tgordon Date 2006-08-10 Time 08:24 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-11-30 Cont ID  
Sent By mperson Date 2006-11-30 Time 14:24 Rev Time 0.33
Received By mperson Date 2006-11-30 Time 14:24 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-10-14 Cont ID  
Sent By jleech Date 2006-10-14 Time 10:42 Rev Time 0.00
Received By jleech Date 2006-10-14 Time 10:42 Sent To B
Notes
2006-10-14 10:44:48DENIED;
 PLANS MUST BE SIGNED BY THE PERSON RESPONSIBLE FOR THE
 DRAWINGS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-08-14 Cont ID  
Sent By jleech Date 2006-08-14 Time 08:04 Rev Time 0.00
Received By jleech Date 2006-08-14 Time 08:04 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2006-11-16 Cont ID  
Sent By mmclean Date 2006-11-16 Time 11:56 Rev Time 0.00
Received By mmclean Date 2006-11-16 Time 11:56 Sent To I
Notes
2006-11-16 11:57:29NOTE: THE PROPOSED A/C UNIT WILL BE 1'-375".

Review Stop Z ZONING
Rev No 2 Status F Date 2006-09-23 Cont ID  
Sent By mmclean Date 2006-09-23 Time 14:02 Rev Time 0.00
Received By mmclean Date 2006-09-23 Time 14:02 Sent To I
Notes
2006-09-23 00:00:00DENIED,
 1. THE PROPOSED A/C UNIT CANNOT BE
 LOCATED AT THE SIDE SETBACK.
 2. SURVEY SHOWS THE SIDE SETBACK AT 4.81
 AND SITEPLANS SHOWS 5FT. SURVEY IS A
 LEGAL DOCUMENT, NEED TO RE-LOCATE THE
 PROPOSED A/C UNIT.
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
 A/C UNIT WILL BE ON PROPERTY LINE.
 3. THE SITEPLANS DOES NOT SHOW THE
 SETBACKS OF THE EXISTING PROPERTY FRONT
 & SIDE.
 4. PLEASE USE THE SURVEY (LEGAL
 DOCUMENT) TO SHOW THE PROPOSED ADDITION
 WITH SETBACKS AND SHOW THE LOCATION OF
 THE A/C UNIT. (2 COPIES OF SURVEYS)
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-05 Cont ID  
Sent By mmclean Date 2006-08-05 Time 13:43 Rev Time 0.00
Received By mmclean Date 2006-08-05 Time 13:43 Sent To I
Notes
2006-08-05 00:00:00DENIED,
 1. THE SITEPLAN PROVIDE DOES NOT PROVIDE
 ALL THAT'S ON THE PROPERTY (DRIVEWAY,
 ALL SETBACKS OF THE EXISTING STRUCTURE
 ETC)
 2. PLEASE SHOW THE PROPOSE ADDITION ON
 THE TWO COPY OF SURVEY WITH SETBACKS FOR
 THE SIDES.
  
 NOTE: THE PROPOSED A/C SHALL NOT BE CLOSER
 THAN 1FT FROMSIDE PROPERTY LINE.
  
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720