Plan Review Details - Permit 06071633
Plan Review Stops For Permit 06071633
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-11 Cont ID  
Sent By adarroug Date 2006-08-11 Time 17:42 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 17:42 Sent To M
Notes
2006-08-11 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-28 Cont ID  
Sent By tgordon Date 2006-07-28 Time 16:37 Rev Time 0.00
Received By tgordon Date 2006-07-28 Time 13:38 Sent To  
Notes
2006-07-28 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-08-16 Cont ID  
Sent By tgordon Date 2006-08-16 Time 11:43 Rev Time 0.20
Received By tgordon Date 2006-08-16 Time 11:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-28 Cont ID  
Sent By tgordon Date 2006-07-28 Time 16:16 Rev Time 0.45
Received By tgordon Date 2006-07-28 Time 16:16 Sent To  
Notes
2006-07-28 00:00:00*** DENIED ***
 1) PLEASE ADJUST THE VALUE TO SHOW ALL
 LABOR AND MATERIALS EVEN IF SUPPLIED BY
 OWNER, OR PROVIDE A SIGNED CONTRACT.
  
 2) ENERGY CALCULATIONS NEED TO BE ON
 FORM 600A-04 (2004) PER FBC 13-600.3.A .
  
 3) SEE CONDENSER DETAIL, 18 GAGE STRAPS
 ARE NOT PERMITTED, NEED TO USE CLIPS,
 PLEASE CORRECT.
  
 4) SEE AIR HANDLER DETAIL, CLEARANCE
 AROUND A/H NEEDS TO BE 4", PLEASE
 CORRECT.
  
 5) PLEASE SHOW EQUIPMENT SCHEDULE &
 DETAIL ON MECHANICAL PLAN, NOT ON AN
 ATTACHED SHEET.
  
 6) RETURN AIR GRILLS 16X16 AND 14X14
 TOGETHER ARE NOT LARGE ENOUGH FOR A 4
 TON SYSTEM, PLEASE CORRECT.
  
 7) PROVIDE RETURN AIR TO ALL HABITABLE
 ROOMS WITH DOORS, SEE NOTE #8.
  
 8) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 9) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.