Plan Review Details - Permit 06071631
Plan Review Stops For Permit 06071631
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-08-16 Cont ID  
Sent By lursu Date 2006-08-16 Time 08:13 Rev Time 0.00
Received By lursu Date 2006-08-16 Time 08:13 Sent To  
Notes
2006-08-16 00:00:00ADDED EXT #0001 FOR THE UNIT 200 FOR THE
 TENANT : AIRCRAFT SYSTEMS COMPANY LTD.
 OWNER OF RECORD ON THE APPLICATION MUST
 BE THE OWNER OF RECORD FROM THE PAPA AND
 NOT THE TENANT NAME.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-03-16 Cont ID  
Sent By rmcdouga Date 2007-03-16 Time 13:57 Rev Time 0.00
Received By rmcdouga Date 2007-03-16 Time 13:57 Sent To  
Notes
2007-03-16 13:58:07STAMP PLANS AND PRINT PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-03-02 Cont ID  
Sent By rmcdouga Date 2007-03-02 Time 14:30 Rev Time 0.00
Received By rmcdouga Date 2007-03-02 Time 14:30 Sent To  
Notes
2007-03-02 14:32:12BUILDING PROVISO
 1) SPIRAL STAIRS SHALL COMPLY WITH 1009.9.2.
 1.THE CLEAR WIDTH OF THE STAIRS SHALL BE NOT LESS
 THAN 26 INCHES (660 MM).
 2.THE HEIGHT OF THE RISERS SHALL NOT EXCEED 9- 1/2
 INCHES (241 MM).
 3.HEADROOM SHALL BE NOT LESS THAN 6 FEET 6 INCHES
 (1981 MM).
 4.TREADS SHALL HAVE A DEPTH NOT LESS THAN 7-1/2
 INCHES (191 MM) AT A POINT 12 INCHES (305 MM) FROM THE
 NARROWER EDGE.
 5.ALL TREADS SHALL BE IDENTICAL.
 6.HANDRAILS COMPLYING WITH SECTION 1009.11 SHALL
 BE PROVIDED ON BOTH SIDES OF THE SPIRAL STAIRWAY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-30 Cont ID  
Sent By rmcdouga Date 2006-11-30 Time 07:33 Rev Time 0.00
Received By rmcdouga Date 2006-11-30 Time 07:33 Sent To  
Notes
2006-11-30 09:00:05DENIED BY BUILDING
  
 1) THE OWNER INFORMATION IS REQUIRED TO BE CORRECTED
 WITH THE CITY RECORDS BEFORE A PERMIT WILL BE ISSUED.
 SUBMIT A COPY OF THE WARRANTY DEED OR OTHER PROOF OF
 OWNERSHIP TO THE FRONT COUNTER SO THAT THE OWNER CAN BE
 UPDATED ON THE SYSTEM.
  
 2) THE NOC THAT WAS SUBMITTED HAS THE WRONG PROPERTY
 CONTROL NUMBER AND DOES NOT HAVE THE RECORDING STAMP ON
 IT. PLEASE SUBMIT A RECORDED COPY OF THE NOC WITH THE
 CORRECT INFORMATION ON IT.
  
 3) IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY,THE
 PLANS MUST BE STAMPED BY THEM AND A COPY OF THE PALM
 BEACH COUNTY PAID RECIEPT FOR THE IMPACT FEES MUST BE
 SUBMITTED BEFORE A PERMIT CAN BE ISSUED. ACCORDING TO
 THE BUILDING PLAN EXAMINER, S. HILL, FOR THE ORIGINAL
 STRUCTURE, IMPACT FEES WERE PAID FOR TWO MEZZANIES AND
 THEY HAVE ALREADY BEEN CONSTRUCTED. THEREFORE, IMPACT
 FEES ARE REQUIRED FOR ALL ADDITIONAL MEZZANIES ARE
 CONSTRUCTED.
  
 4)THE SPIRAL EGRESS STAIRS AT THE MEZZANINE ARE
 REQUIRED TO COMPLY WITH 2004 FBC 1009.9.2. HANDRAILS
 ARE REQUIRED ON BOTH SIDES, ETC.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-15 Cont ID  
Sent By rmcdouga Date 2006-08-15 Time 13:10 Rev Time 0.00
Received By rmcdouga Date 2006-08-15 Time 13:10 Sent To  
Notes
2006-08-15 00:00:00DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SPECIFY THE OCCUPANCY AND
 CONSTRUCTION TYPE ON THE PLANS.
  
 4) SPECIFY IF THE BUILDING IS
 SPRINLERED. IF SPRINKLERED THE SPACE
 ABOVE AND BELOW THE MEZZANINE IS
 REQUIRED TO BE SPRINKLERED.
  
 5) SPECIFY ON THE PLANS THAT THE
 MEZZANINE IS A STORAGE OCCUPANCY WHICH
 IS LOCATED WITIN A BUSINESS OCCUPANCY.
  
 6) SPIRAL STAIRS IN A MEANS OF EGRESS
 MUST COMPLY WITH FBC 1009.9.1. SEE FBC
 1032.2. PROVIDE DETAILS ON SIGNED AND
 SEALED PLANS.
  
 7) FBC 110.4.3* (CITY AMENDMENTS)
 REQUIRES THE OWNER TO POST A SIGN WITH
 THE SAFE ALLOWABLE FLOOR LOAD STATED IN
 A CONSPICUOUS PLACE.
  
 8) THE ENGINEER'S AFFIDAVIT FOR THE SAFE
 FLOOR LOAD REQUIRED BY FBC 110.4.2* HAS
 BEEN ALTERED. THE COVERSHEET FOR THE
 LOAD CALCULATIONS REQUIRED BY FBC
 110.4.2 HAS BEEN ALTERED. THE FLOOR
 LOAD, DIMENSIONS AND AREA HAVE BEEN
 ALTERED ON SHEET A1 OF THE PLANS.
 SOMEONE HAS DRAWN IN THE CLEAR HEIGHT
 ABOVE THE MEZZANINE AND INCORRECT
 OCCUPANCY. SIGNED AND SEALED DOCUMENTS
 CAN NOT BE ALTERED. ONLY THE PERSON
 SIGNING AND SEALING THE DOCUMENTS CAN
 MAKE CHANGES.
  
 9) PROVIDE A FLOOR PLAN OF THE UNIT
 SHOWING THE DIMENSIONS AND ANY BUILDOUT
 IN THE UNIT. THE AREA ALLOWED FOR THE
 MEZZANINE IS BASED ON THE AREA OF THE
 ROOM OR SPACE IN WHICH THEY ARE LOCATED.
 SEE FBC 505.2.
  
 10) THE CLEAR HEIGHT ABOVE AND BELOW THE
 MEZZANINE FLOOR CONSTRUCTION SHALL NOT
 BE LESS THAN 7 FEET PER FBC 505.1.
  
 11) SPECIFY THE WELD TYPE ON SHEET A1
 WHERE THE STEEL ANGLE IS WELDED TO THE
 EMBEDS.
  
 12) ADDITIONAL COMMENTS MAY RESULT WHEN
 THESE COMMENTS ARE ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-04-14 Cont ID  
Sent By dpalmer Date 2007-04-14 Time 08:58 Rev Time 0.00
Received By dpalmer Date 2007-04-14 Time 08:48 Sent To PC
Notes
2007-04-14 08:59:20REDLINED, CONTROL FOR LIGHTING OF STAIRS STILL REQUIRED
 AT UPPER LEVEL. IN THE EVEN THE LIGHTING IS OFF, AN
 OCCUPANT CAN TURN ON LIGHTING ATTHE UPPER FLOOR FOR
 EGRESS OF STAIRS.
 LS 101 7.8 AND 7.9

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-03-14 Cont ID  
Sent By dpalmer Date 2007-03-14 Time 10:01 Rev Time 0.00
Received By dpalmer Date 2007-03-14 Time 10:01 Sent To  
Notes
2007-03-14 10:02:13REDLINED,
 STILL MUST SUPPLY CONTROL FOR LIGHTING AT THE MEZZ/2ND
 LEVEL FOR EGRESS. LS 101 7.8

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-03-02 Cont ID  
Sent By dpalmer Date 2007-03-02 Time 18:19 Rev Time 0.00
Received By dpalmer Date 2007-03-02 Time 18:19 Sent To  
Notes
2007-03-02 18:20:28*** UNSAT **
  
 1) NOTE: PLEASE SEE PREVIOUS NOTES. PLEASE PROVIDE
 MINIMUM LIGHTING LEVELS PER LIFE SAFETY CODE. NFPA-101
 7.8.1.3, 7.9.2.2.
 LIGHTING FOR CONTROL OF LIGHTS TO BE AT THE UPPER
 LOCATION OF STAIRS FOR EGRESS AND LOWER PORTION OF
 STAIRS.
  
 2) NOTE: PLEASE SEE 13-415.1.1, .1.2, AND .1.3
 AUTOMATIC LIGHTING CONTROL SHUT OFF FOR NEW UPSTAIRS
 AREA REQUIRED.
 THIS IS A NEW NOTE AND CONFIRMED WITH THE STATE.
  
 ** NOTE # 2 COULD BE REDLINED ON PLANS WITH REVISION TO
 FOLLOW, HOWEVER PLEASE SEE NOTE #1 IS MINIMUM NEEDED
 FOR LIFE SAFETY.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-11-16 Cont ID  
Sent By dpalmer Date 2006-11-16 Time 11:47 Rev Time 0.00
Received By dpalmer Date 2006-11-16 Time 11:45 Sent To  
Notes
2006-11-16 11:51:32*** UNSAT ***
  
 1) NOTE: PLEASE SUBMIT A PLAN/DETAIL FOR THE REQUIRED
 LIGHTING UNDER NORMAL AND EMERGENCY FOR NEW STORAGE
 AREA EGRESS. THE SHEETS AS SUBMITTED DO NOT COMPLY AND
 DO NOT PROVIDE ENOUGH INFORMATION FOR THE SAGE LIGHTING
 ILLUMINATION OF THESE NEW STAIRS AS SHOWN.
 PLEASE ALSO ONLY SUBMIT PLANS, AND INFORMATION FOR NEW
 AREA AND STAIRS.
  
 THIS IS REQUIRED AT THIS TIME.
 FBC ADMIN SECT(S) 106.1.2, 106.3.5.1.2,AND LIFE
 SAFETY CODE 101 2003, 7.8.1.3, 7.9.2.2.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. *
 *IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF THE
 NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE DO
 NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-11 Cont ID  
Sent By dpalmer Date 2006-08-11 Time 21:01 Rev Time 0.00
Received By dpalmer Date 2006-08-11 Time 21:01 Sent To  
Notes
2006-08-11 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE PROVIDE MINIMUM EGRESS
 LIGHTING AND CONTROLS FOR STAIR AREAS.
 PLEASE SEE MIN REQUIRMENTS PER
 2003 NFPA-1017.8.1.3, 7.9.2.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-03-15 Cont ID  
Sent By mawillia Date 2007-03-15 Time 18:29 Rev Time 0.00
Received By mawillia Date 2007-03-15 Time 18:18 Sent To  
Notes
2007-03-15 18:29:40*****APPROVED*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN SATISFIED.PLAN SHEET FP-1 STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-03-06 Cont ID  
Sent By mawillia Date 2007-03-06 Time 12:48 Rev Time 0.00
Received By mawillia Date 2007-03-06 Time 12:42 Sent To  
Notes
2007-03-06 12:48:08*****INCOMPLETE*****
  
  
 1.EVEN THOUGH YOU ACKNOWLEDGED THAT J.W. FIRE
 SPRINKLER HAS OR WILL SUBMIT SEPARATE PLANS FOR THIS
 JOB, A LAYOUT OF THE PROPOSED FIRE SPRINKLER IS
 REQUIRED FOR THIS REVIEW.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-12-12 Cont ID  
Sent By mawillia Date 2006-12-12 Time 16:36 Rev Time 0.00
Received By mawillia Date 2006-12-12 Time 16:36 Sent To  
Notes
2006-12-12 16:55:00*****DENIED*****
  
  
  
 *THEPREVIOUS FIRE PLAN REVIEW OF 08/24/06HAS NOT
 BEEN ADDRESSED.
  
 *TO EXPEDITE THE FIRE PLAN REVIEW PROCESS, INCLUDE A
 RESPONSE INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
 *IT IS ASSUMED THAT THE SUBMITTED SPRINKLER PLANS WERE
 DUE TO A MODIFICATION NEEDED FOR THE SCOPE OF WORK.
 HOWEVER, THE UNIT NUMBER OF THE STRUCTURE IS NOT
 INCLUDED IN THE TITLE BLOCK OF THE PLANS. ADDITIONALLY,
 SEPARATE PERMIT AND PLAN WILL BE REQUIRED FOR THE
 SPRINKLER REMODEL.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-08-24 Cont ID  
Sent By nmccray Date 2006-08-24 Time 11:20 Rev Time 0.00
Received By nmccray Date 2006-08-24 Time 10:39 Sent To  
Notes
2006-08-24 00:00:00DENIED:********************
  
 1) THE MEANS OF EGRESS SHALL BE
 ACCORDANCE WITH CHAPTER 7 AND CHAPTER
 39.
  
 2) SPIRAL STAIRS SHALL COMPLY WITH
 CHAPTER 7.2.2.2.3.
  
 3) PLEASE PROVIDE A CLEAR REPRESENTATION
 OF THE MEZZANINE STRUCTURE IN RELATION
 TO THE FLOOR PLAN.
  
 4) HOW WILL THIS MEZZANINE IMPACT THE
 EXISTING FIRE SPRINKLER AND FIRE ALARM
 SYSTEM.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-04-12 Cont ID  
Sent By adarroug Date 2007-04-12 Time 14:06 Rev Time 0.00
Received By adarroug Date 2007-04-12 Time 14:06 Sent To E
Notes
2007-04-12 14:06:55TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-03-14 Cont ID  
Sent By adarroug Date 2007-03-14 Time 09:17 Rev Time 0.00
Received By adarroug Date 2007-03-14 Time 09:17 Sent To  
Notes
2007-03-14 09:17:57TO "BOB"#10

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-03-01 Cont ID  
Sent By adarroug Date 2007-03-01 Time 14:05 Rev Time 0.00
Received By adarroug Date 2007-03-01 Time 14:05 Sent To  
Notes
2007-03-01 14:08:01TO "BOB"#11

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-07 Cont ID  
Sent By adarroug Date 2006-11-07 Time 16:20 Rev Time 0.00
Received By adarroug Date 2006-11-07 Time 16:19 Sent To  
Notes
2006-11-16 11:41:47TO "BOB"#3
2006-11-07 16:20:41WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-09-08 Time   Rev Time 0.00
Received By adarroug Date 2006-08-02 Time 13:36 Sent To  
Notes
2006-08-11 00:00:00TO "BOB"#10
2006-08-02 00:00:00WAITING FOR "BOB"

Review Stop Z ZONING
Rev No 1 Status P Date 2006-09-05 Cont ID  
Sent By eschneid Date 2006-09-05 Time 12:09 Rev Time 0.00
Received By eschneid Date 2006-09-05 Time 12:09 Sent To  
Notes
***NONE***