Plan Review Details - Permit 06071512
Plan Review Stops For Permit 06071512
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-11-13 Cont ID  
Sent By lmartine Date 2006-11-13 Time 16:41 Rev Time 0.00
Received By lmartine Date 2006-11-13 Time 16:41 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-10-23 Cont ID  
Sent By amorse Date 2006-10-23 Time 08:27 Rev Time 0.00
Received By amorse Date 2006-10-23 Time 08:27 Sent To  
Notes
2006-10-23 08:52:11 
  
 DENIED
  
 1) BUILDING REVIEW OK BUT REQUIREMENTS OF OTHER
 REVIEWERS SHALL BE MET
  
 2) THE CLAIMED VALUATION ON THE PERMITAPPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC* PLEASE SUBMITCOPY OF CONTRACT OR AN
 ESTIMATED VALUE BASED ON AVERAGE WATERFRONT CONDO
 BUILDOUTS WILL BE USED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-09-29 Cont ID  
Sent By amorse Date 2006-09-29 Time 14:30 Rev Time 0.00
Received By amorse Date 2006-09-29 Time 14:30 Sent To  
Notes
2006-09-29 00:00:00 
  
 DENIED
  
 NOTE ON PREVIOUS REVIEWS NOT ADDRESSED:
  
 1) THE MIN TYPE OF CONSTRUCTION REQUIRED
 IS THE CLASSIFICATION PER 602 AND TABLE
 503 FBC
  
 ****** PLEASE NOTE THAT THEIR IS NO
 CONSTRUCTION CLASSIFICATION "CBS" IN THE
 AFORE MENTIONED TABLES*****
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-12 Cont ID  
Sent By amorse Date 2006-09-12 Time 11:17 Rev Time 0.00
Received By amorse Date 2006-09-12 Time 11:17 Sent To  
Notes
2006-09-12 00:00:00 
  
 DENIED
  
 1) THE MIN TYPE OF CONSTRUCTION REQUIRED
 IS THE CLASSIFICATION PER 602 AND TABLE
 503 FBC
  
 2) AS THE PROPOSED WORK REQUIRES THE
 RECONFIGURATION OF SPACE IT WILL BE A
 LEVEL 2 ALTERATION
  
 3) THE SHOWER PAN DETAIL WAS CORRECT TO
 STATE FIRE RESISTANT WOOD(THIS MAY BE
 REQUIRED BY THE TYPE OF CONSTRUCTION),
 THE CODE SECTION WAS INCORRECT SHOULD
 HAVE STATED 603.1 FBC
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-17 Cont ID  
Sent By amorse Date 2006-08-17 Time 12:27 Rev Time 0.00
Received By amorse Date 2006-08-17 Time 12:27 Sent To  
Notes
2006-08-17 00:00:00 
  
 DENIED
  
 1) PROVIDE CONSTRUCTION TYPE ON DRAWING
 PER 106.3.5 FBC 2004
  
 2) PROVIDE ALTERATION LEVEL PER 305.1
 EXISTING BLDG CODE 2004
  
 3) SHOWER PAN DETAIL REFERENCES FBC 707
 FOR FIRE TREATED WOOD, THIS SECTION IS
 FOR SHAFT ENCLOSURES, PLEASE CORRECT
  
 4) SOFFIT DETAIL SHALL BE FIRE RETARDANT
 WOOD PER 603.1 FBC 2004 OR METAL
 FRAMING, PLEASE INDICATE ON DRAWING
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-11-14 Cont ID  
Sent By dpalmer Date 2006-11-14 Time 10:44 Rev Time 0.00
Received By dpalmer Date 2006-11-14 Time 09:32 Sent To B
Notes
2006-11-14 10:51:12**** NOTES REDLINED *****
  
 ** NEW ENGINEER OF RECORD.
  
 **CANALES AND ASSOCIATES AND LUIS LOPEZ ARE NOT ON THE
 TITLE BLOCKS FOR THE ELECTRICAL PLANS.
  
  
 1) NOTE: PLEASE WASHER/LAUNDRY LOAD SHOWN AS 1.2 ON
 PANEL SCHEDULE AND LOAD CALCULATIONS WHERE CODE
 210.11C2 AND 220.16 REQUIRES A MINIMUM OF 1.5.
 PLEASE SEE NOTE ON PANEL SCHEDULE WHICH ALSO MENTIONS
 LAUNDRY LOAD OF 1.5 FIGURED IN WITH SMALL APPLIANCE
 LOAD?
  
 2) NOTE: PLEASE SEE PANEL IS BEING SHOWN AS 200A?S WITH
 A 100A FEED. THIS IS TO BE VERIFIED IN FIELD AND
 CORRELATE/ADJUST ON PLANS IF NEEDED.
  
 3) NOTE: REDLINED CODES RELEVANT TO DESIGN WHICH SHOULD
 BE STATED ON PLANS.
 2002 NFPA-72, 2002 NFPA-70 (NEC).
  
  
 PLANS ARE BEING ROUTED BACK TO LUIS MARTINEZ AS THE
 VALUE WAS NOT ADJUSTED BASED ON THE PREVIOUS BUILDING
 REVIEWER?S COMMENTS. IF VALUE IS NOT BEING ADJUSTED,
 THE NEW BUILDING REVIEWER OF RECORD SHALL PROCESS PLANS
 FOR ISSUANCE.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-10-22 Cont ID  
Sent By dpalmer Date 2006-10-22 Time 10:32 Rev Time 0.00
Received By dpalmer Date 2006-10-22 Time 09:29 Sent To  
Notes
2006-10-22 10:32:18******** UNSAT 4THREVIEW ******
  
 *** PLEASE SEE NOTES FROM PREVIOUS REVIEWSWHICH STILL
 NEED TO BE ADDRESSED AND PLANS TO BE SUBMITTED TO THE
 2002 NEC. NFPA-70.
  
 ** PLEASE ALSO SEE NEW NOTES DUE TO CHANGES IN PLANS.
  
  
 1) NOTE: PLEASE SEE PLANS STILL NOT INIDCATE ALL
 CIRCUITING AND CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULES.
 PLEASE SEE THERE ARE STILL MANY DEVICES FOR WHAT IS
 DEDICATE D EQUIPMENT ETC WHICH IS NOT ON PANEL
 SCHEDULE. PLEASE SEE THE FOLLOWING.
  
 A) HALLWAY FOYER SHOWS UCFRIG, ICE MACHINE, COUNTER
 RECEPTS ETC WITH OUT ANY CIRCUITS.
 B) PLEASE SEE SPACES ON PANEL SCHEDULE SHOWING CIRCUITS
 HOWEVER NOT LOCATED ON PLANS?
 C) PLEASE SEE PLANS WHICH SHOWS CIRCUITS , 8, 10 ETC
 WHICH ARE SHOWN AS BLANK ON PANEL SCHEDULE??
 D) PLEASE SEE MISSING CIRCUITS ON OTHER DEVICES.
 ETC ETC.
 240.4,220.31,310.16, ETC
 FBC 106.1.2, 106.1.3, 106.3.5.1.2 ADMINISTRATIVE
 SECTIONS.
  
 2) NOTE: PLEASE SEE KITCHEN COUNTER SPACE MISSING GFI
 RECEPT AS REQUIRED AS A DEDICATED MICROWAVE CIRCUIT IS
 NOW SHOWN (#4) , HOWEVER NO THER RECEPT (GF) IS SHOWN
 ?
 PLEASE SEE 210.52C1, 220.16, 210.11C1, 210.8A6,
  
 3) NOTE: PLEASE SEE 250.52B1, 210.11C1,220.16 AS
 CIRCUIT, LOAD ETC FOR KITCHEN, DINING, AND AREAS OF THE
 LIKE ARE NOT COMPLIANT ON PLANS. (#21)
 PLEASE ALSO SEE RECEPT IN SMAE LOCATION MISSING
 CIRCUITING AS NOTED ABOVE IN NOTE #1.
  
 4) NOTE: PLEASE SEE PANEL SCHEDULE AND LOAD
 CALCULATIONS DO NOT CORRELATE. THERE ARE LOADS ON PANEL
 SCHEDULE WHICH IS NOT IN CACULATIONS. PLEASE SEE OTHER
 CIRCUITS REQUIRED FOR DEDICATED EQUIPMENT AS NOTED
 ABOVE ARE ALSO NOT ON PANEL SCHEDULE OR IN LOAD
 CALCULATIONS, HOWEVER SHOWN ON PLANS??
 PLEASE SEE PREVIOUS PLANS FROM THE PREVIOUS 3 SUBMITTED
 SETS ALL INDICATED A 200A PANEL EXISTING. PLEASE SEE
 THIS PANEL IS BEING SHOWN AS 100A AND LOAD IS BEING
 SHOWN AT 100A'S ALREADY WITHOUT ANY OF THE OTHER ITEMS
 ON PANEL BEING FIGURED INTO THE LOAD CALCULATIONS.
 PLEASE KNOW, BASED ON THE PLANS, LOADS, CIRCUITS AND
 THE DEDICATED CIRCUITS NOT SHOWN, THE 100A PANEL IS
 OVERLOADED AND W3ILL BE REQUIRED TO BE UPGRADED FOR
 ADDTIONAL SERVICE LOADS.
 PLEASE ADJUST ALL; , SUBMIT NEW RISER, FOR NEW FEEDERS,
 UPDATE LOAD CALCULATIONS, SIZE OF THE OCP FEEDING NEW
 PANEL UPGRADE ETC ETC.
 PLEASE SEE NEC 2002,
 220.31, 408.4, 240.4, 310.16, 300, 230,ETC ETC.
 THERE ARE MANY ARTICLES IN THE NEC WHICH APPLY HOWEVER
 ALL ARTICLES WILL NOT BE LISTED.
  
 5) NOTE: PLEASE KNOW, AS CONSULATATION WITH THE STATE
 INVESTIGATOR FOR THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS HAS ALREADY TAKEN PLACE. PLEASE KNOW AS
 "CANALES AND ASSC'S" IS NOT LEGALLY EMPLOYED BY THE
 SAID ENGINEERSIGNING AND SEALING DOCUMENTS AND DO NOT
 MEET THE EXCEPTIONS UNDER FS 481.229 (1)(C, PLEASE BE
 SURE ANY NEW PLANS SUBMITTED ARE DONE LICENSED
 PROFESSIONALS WHICH ARE PERMITTED TO DO THE SCOPE OF
 WORK AS SHOWN.
 PLEASE KNOW ALL PREVIOUS PLANS WHICH WERE SIGNED DATED
 AND SEALED BY MR. LUIS LOPEZ HAVE BEEN RETAINED FOR
 THIS PROJECT WILL BE TURNED OVER TO THE BOARD OF
 ENGINEERS FOR REVIEW.
 PLEASEKNOW A 4XFEE HAS ONCE AGAIN BEEN ASSESSED AS
 REQUIRED PER FS 553.80(2)(B). THIS NOTICE WAS GIVEN ON
 ALL PREVIOUS REVIEWS AND A 4X FEE WAS ALREADY ASSESSED
 ON PREVIOUS REVIEW.AS REQUIRED UDNER FLORIDA STATUE
 AS NOTED, THIS FEE IS ASSESSED EACH TIME AFTER.
 PLEASE KNOW,ONE SET OF ALL PLANS, INCLUDING BUILDING,
 PLUMBING ETC WILL BE RETAINED BY THIS OFFICE AND SHALL
 BE FORWARDED WITH PREVIOUS SADI DOCUMENTS.
  
 THE FEE OF $624.00 WILL ONCE AGAIN BE REQUIRED TO BE
 PAID BEFORE RESUBMITTING PLANS.
  
 ****PLEASE KNOW, TO DATE THE DESIGNER OR ENGINEER OF
 RECORDED SHOWN ON SAID PLANS HAS NOT CONTACTED THIS
 REVIEWER FOR ANY QUESTIONS OR COMMENTS.
  
 6) NOTE: NOTICE TO CONTRACTOR, PLEASE KNOW THW RECORDED
 NOTICE OF COMMENCEMENT WILL EXPIRE ON OCT 25TH AS WORK
 HAS NOT COMMENCED WITHIN 90 DAYS OF RECORDING SUCH NOC.
 PLEASE SEE FS 713.13(2) .
 PLEASE ALSO KNOW, THE RE-RECORDED NOC IS ONLY NEEDS TO
 BE SUBMITTED ONCE PERMIT IS ISSUED AND IS BEING PICKED
 UP.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-09-24 Cont ID  
Sent By dpalmer Date 2006-09-24 Time 16:10 Rev Time 0.00
Received By dpalmer Date 2006-09-24 Time 15:36 Sent To  
Notes
2006-09-24 00:00:00***** UNSAT 3RD REVIEW ******
  
 ** PLEASE SEE PREVIOUS REVIEW NOTE
 REQUESTED TO SUBMIT PLANS FOR 2002 NEC
 CODE COMPLIANCE. PLEASE SEE MANY OF THE
 CODE REFERENCED IN PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS DUE TO THE PLANS SUBMITTED.
 PLEASE SEE NEW COMMENTS FOR NON-CODE
 COMPLIANT ITEMS.
  
 1) NOTE: NO, SAME NOTE.
  
 **PREVIOUS REVIEW NOTE REVIEW #2**
 NO, PREVIOUS REVIEW NOTE #1.
 PLEASE COMPLETE ALL CIRCUITING ON PLANS
 AND CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULE.
 PLEASE SEE PLANS DO NOT INDICATE ANY
 CIRCUITS AND REVIEW FOR CODE COMPLIANCE
 FOR MANY ITEMS CAN NOT BE DONE AT THIS
 TIME.
 PLEASE INDICATE ALL NEW ELECTRICAL AND
 INDICATE ALL EXISTING ELECTRICAL.
 FBC 106.1.2 ADMIN SECT.
 240.4,310.16,408.4 ETC 2002 NEC.
  
 2) NOTE: NO, SAME AS NOW BOTH BATHRMS
 ARE SHOWN ON THE SAME CIRCUIT WHICH IS
 NOT PERMITTED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 PLEASE SEE MISSING RECEPTS
 LOCATED IN BATHRM W/IN 3' OF LAV. PLEASE
 SEE MASTER BATH, EITHER ADD OR RELOCATE
 GFI AS SHOWN. PLEASE SEE OTHER BATH
 WHERE NO GFI IS SHOWN? (NEW OR EXSIT)?
 210.52D
 PLEASE SEE MISSING THE REQUIRED
 DEDICATED BATH CIRCUIT(S) PER 210.11C3
 MUST BE 20A AND #12. SHOWN AS 15A ON
 SCHEDULE.
  
 3) NOTE:??OK. TANKLESS WH REMOVED FROM
 PLANS?
  
  
 4) NOTE:NO, PLEASE SEE DRYER IS STILL
 BEING SHOWN ON A SINGLE POLE CIRCUIT
 WHEN THIS A 220/240 UNIT.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 PLEASE SEE DRYER IS BEING SHOWN
 ON A 1-P15A ON PANEL SCHEDULE, YET THIS
 UNIT IS SHOWN AS 6KW UNIT ON LOAD
 CALCULATIONS. PLEASE SEE NEC FOR SIZING
 OCP AND AWG.
 240.4, 310.16, 220.18
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE:OK, NOTED ON PLANS HOWEVER THE
 CIRCUTING NOT SHOWN ON PANEL SCHEDULE
 FOR CIRCUITS. PLEASE SEE NEC 210.12, IT
 IS THE PROTECTION FOR THE "BRANCH
 CIRCUIT".
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE REQUIRED
 ARC FAULT PROTECTION REQUIRED FOR ALL
 OUTLETS IN BEDRMS. RECEPTS, SD'S,LTS,
 FANS ETC,
 2002 NEC 210.12
  
 8) NOTE: OK, THE SIZE OF THE UNIT HAS
 CHANGED.
  
 9) NOTE: NO, NOT COMPLETE AS LOADS, AND
 CIRCUTING WITH NOTES ABOVE ARE NOT
 COMPLETE AT THIS TIME. PLEASE SEE LOAD
 AT PANEL SCHEDULE IS BLANK ALSO.
  
 ** PREVIOUS REVIEW NOTE ** PLEASE
 COMPELTE PANEL SCHEDULE
 AS NO CONDUCTOR SIZES ARE BEING SHOWN
 FOR BRANCH CIRCUITS. UNABLE TO VERIFY
 MANY REQUIRED MIN SIZES ATTHIS TIME.
 408.6,240.4,310.16 ETC
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE 210.11C2,220.16 FOR
 MIN KVA TO BE FIGURED FOR WASHER/LAUNDRY
 CRICUIT.
  
 11) NOTE: NO? PLEASE VERIFY THE PANEL
 FOR THIS AT THIS TIME. PLEASE KNOW THIS
 IS A NEW BUILDING AND THE SIZE AND
 VOLTAGE SHOULD BE READILY AVAILABLE.
 VOLTAGE IS BEING SHOWN 120/240 AND
 100A'S NOW INSTEAD OF THE PREVIOUS PLANS
 WHICH SHOWED 200A 'S>
 THE CONTRACTOR IS NOT TO VERIFY THIS,
 THIS IS REQUIRED TO BE VERIFIED BY THE
 DESIGN PROFESSIONAL AND PLACED ON PLANS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 PLEASE SEE NOTE ON PLANS
 MENTIONS FOR CONTRACTOR TO VERIFY 200A
 SERVICE AND TO VERIFY THE CALCULATIONS,
 PANEL SCHEDULE ETC.
 PLEASE KNOW, THIS IS THE RESPONSIBILITY
 OF THEDESIGN PROFESSIONALS AT THIS
 TIME OF THE DESIGN PHASE OF PERMITTING.
 ANY REVISIONS DONE TO PROJECT THEN
 BECOMES THE RESPONSIBILITY OF THE
 CONTRACTOR TO NOTIFY THE DESIGN
 PROFESSIONAL OF REVISIONS AND CHANGES.
 PLEASE VERIFY ALL OF THE ABOVE INCLUDING
 THE VERIFICATION OF A 200A SERVICE,
 INCLUDING THE SIZE OF THE FEEDERS COMING
 INTO THE EXSTING PANEL. IT IS UNCLEAR
 EVEN IF A 200A PANEL WAS INSTALLED IF
 THERE ARE INDEED FEEDERS RATED FOR
 200A'S AND THE INCREASED LOADS.
  
 12) NOTE:NO, AS THERE ARE STILL CODE
 COMPLIANT COMMENTS FOR SOME OF THE SAME
 COMMENTS AS MADE ON TWO PREVIOUS
 REVIEWS, A 4X FEE FOR THE PLAN REVIEW
 PORTION OF THE PERMIT FEE HAS NOW BEEN
 ASSESSED. THIS FEE IS ASSESSED TO THE
 DESIGN PROFESSIONAL AND MUST BE PAID
 BEFORE PLANS CAN BE RESUBMITTED. PLEASE
 KNOW, ALL PREVIOUS PLANS AND CURRENT
 PLANS WILL NOW BE FORWARDED TO THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS
 AND THE STATE BOARD'S LEGAL COUNSEL WITH
 ALL OTHER PREVIOUS PLANS IN FILE. PLEASE
 KNOW IT WILL ALSO BE CONFIRMED AS A
 "DESIGN"/ "DRAFTING FIRM" MAY NOT BE
 ABLE TO DESIGN OR DRAW PLANS FOR A
 COMMERCIAL BUILDING. THIS WILL BE
 CONFIRMED AS FS 481.203, 481.223 AND FS
 481.229 DOES NOT PERMIT THESE TYPES OF
 FIRMS TO PRACTICE "ARCHITECTURE" WITHOUT
 THE PROPER LICENSURE.
 THE AMOUNT OF $624.00 IS NOW DUE BEFORE
 PLANS MAY BE RESUBMITTED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 PLEASE SEEFS 553.80(2)(B)
 WITH RESPECT TO DESIGN PROFESSIONALS AND
 REPEAT CODE COMPLIANT COMMENTS.
 PLEASE SEE MANY OF THE COMMENTS WERE
 REPEAT AS CODES AND ITEMS WERE STATED ON
 THE PREVIOUS REVIEW. PLEASE SEE THIS IS
 A NOTICE GIVEN AT THIS TIME.
 ** PLEASE KNOW ONE SET OF ELECTRICAL
 PLANS FROM EACH OF THE PREVIOUS REVIEWS
 ARE BEING RETAINED BY THIS OFFICE FOR
 POSSIBLE REVIEW BY THE FBPE'S.
  
  
 ***** NEW NOTE ***
  
 1) NOTE: PLEASE SEE NOW A FAULT CURRENT
 CALCULATION HAS NOW BEEN SHOWN ON
 PLANS?? PLEASE SEE THIS NOW STATES MIN
 AIC RATINGS FOR ALL EQUIPMENT TO BE 22K.
 PLEASE SEE PANEL IS BEING SHOWN AS 10K.
 PLEASE VERIFY THIS.
 110.9, 90.7
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-10 Cont ID  
Sent By dpalmer Date 2006-09-10 Time 13:54 Rev Time 0.00
Received By dpalmer Date 2006-09-10 Time 13:18 Sent To  
Notes
2006-09-10 00:00:00***** UNSAT 2ND REVIEW ******
  
 ** PLEASE SEE PREVIOUS REVIEW NOTE
 REQUESTED TO SUBMIT PLANS FOR 2002 NEC
 CODE COMPLIANCE. PLEASE SEE MANY OF THE
 CODE REFERENCED IN PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH NEW
 COMMENTS DUE TO THE PLANS SUBMITTED.
 PLEASE SEE NEW COMMENTS FOR NON-CODE
 COMPLIANT ITEMS.
  
 1) NOTE: NO, PREVIOUS REVIEW NOTE #1.
 PLEASE COMPLETE ALL CIRCUITING ON PLANS
 AND CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULE.
 PLEASE SEE PLANS DO NOT INDICATE ANY
 CIRCUITS AND REVIEW FOR CODE COMPLIANCE
 FOR MANY ITEMS CAN NOT BE DONE AT THIS
 TIME.
 PLEASE INDICATE ALL NEW ELECTRICAL AND
 INDICATE ALL EXISTING ELECTRICAL.
 FBC 106.1.2 ADMIN SECT.
 240.4,310.16,408.4 ETC 2002 NEC.
  
 2) NOTE: PLEASE SEE MISSING RECEPTS
 LOCATED IN BATHRM W/IN 3' OF LAV. PLEASE
 SEE MASTER BATH, EITHER ADD OR RELOCATE
 GFI AS SHOWN. PLEASE SEE OTHER BATH
 WHERE NO GFI IS SHOWN? (NEW OR EXSIT)?
 210.52D
 PLEASE SEE MISSING THE REQUIRED
 DEDICATED BATH CIRCUIT(S) PER 210.11C3
 MUST BE 20A AND #12. SHOWN AS 15A ON
 SCHEDULE.
  
 3) NOTE: PLEASE SUBMIT MANUFACTURE
 SPECS/CUT SHEETS FOR THE TWO NEW
 TANKLESS WATER HEATERS BE PORPOSED.
 PLEASE BE SURE THE LISTING FROM A NRTL
 IS SHOWN.
 PLEASE ALSO SEE BOTH OF THESE ON PANEL
 SCHEDULE DO NOT INDICATE ANY CONDUCTOR
 SIZES OR OCP ??
 240.4,310.16 408.6 ETC
  
 4) NOTE: PLEASE SEE DRYER IS BEING SHOWN
 ON A 1-P15A ON PANEL SCHEDULE, YET THIS
 UNIT IS SHOWN AS 6KW UNIT ON LOAD
 CALCULATIONS. PLEASE SEE NEC FOR SIZING
 OCP AND AWG.
 240.4, 310.16, 220.18
  
 5) NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52 FOR WALL SPACE. (EXISTING TO BE
 SHOWN) NEW WALLS TO CONTAIN SPACING PER
 210.52
  
 6) NOTE: PLEASE SEE LIBRARY/ ADAPTABLE
 SLEEPING ROOM SHALL CONTAIN SD'S INSIDE
 AND OUTSIDE IF NOT EXISTING.
 PLEASE SEE NFPA-72 11.5.1.1,11.8.3 R313
 2004 FBC.
  
 7) NOTE: PLEASE INDICATE THE REQUIRED
 ARC FAULT PROTECTION REQUIRED FOR ALL
 OUTLETS IN BEDRMS. RECEPTS, SD'S,LTS,
 FANS ETC,
 2002 NEC 210.12
  
 8) NOTE: PLEASE SEE 424.3B AS LOAD CALCS
 INDICATE THE HEAT , A/C LOAD AT 10KW,
 HOWEVER THE OCP SHOWN IS ONLY AT 40A'S??
 PLEASE SEE MIN SIZING OF THE OCP IS TO
 BE 125%.)MIN)
  
 9) NOTE: PLEASE COMPELTE PANEL SCHEDULE
 AS NO CONDUCTOR SIZES ARE BEING SHOWN
 FOR BRNACH CIRCUITS. UNABLE TO VERIFY
 MNAY REQUIRED MIN SIZES ATTHIS TIME.
 408.6,240.4,310.16 ETC
 FBC 106.1.2
  
 10) NOTE: PLEASE SEE 210.11C2,220.16 FOR
 MIN KVA TO BE FIGURED FOR WASHER/LAUNDRY
 CRICUIT.
  
 11) NOTE: PLEASE SEE NOTE ON PLANS
 MENTIONS FOR CONTRACTOR TO VERIFY 200A
 SERVICE AND TO VERIFY THE CALCULATIONS,
 PANEL SCHEDULE ETC.
 PLEASE KNOW, THIS IS THE RESPONSIBILITY
 OF THEDESIGN PROFESSIONALS AT THIS
 TIME OF THE DESIGN PHASE OF PERMITTING.
 ANY REVISIONS DONE TO PROJECT THEN
 BECOMES THE RESPONSIBILITY OF THE
 CONTRACTOR TO NOTIFY THE DESIGN
 PROFESSIONAL OF REVISIONS AND CHANGES.
 PLEASE VERIFY ALL OF THE ABOVE INCLUDING
 THE VERIFICATION OF A 200A SERVICE,
 INCLUDING THE SIZE OF THE FEEDERS COMING
 INTO THE EXSTING PANEL. IT IS UNCLEAR
 EVEN IF A 200A PANEL WAS INSTALLED IF
 THERE ARE INDEED FEEDERS RATED FOR
 200A'S AND THE INCREASED LOADS.
  
 12) NOTE: PLEASE SEEFS 553.80(2)(B)
 WITH RESPECT TO DESIGN PROFESSIONALS AND
 REPEAT CODE COMPLIANT COMMENTS.
 PLEASE SEE MANY OF THE COMMENTS WERE
 REPEAT AS CODES AND ITEMS WERE STATED ON
 THE PREVIOUS REVIEW. PLEASE SEE THIS IS
 A NOTICE GIVEN AT THIS TIME.
 ** PLEASE KNOW ONE SET OF ELECTRICAL
 PLANS FROM EACH OF THE PREVIOUS REVIEWS
 ARE BEING RETAINED BY THIS OFFICE FOR
 POSSIBLE REVIEW BY THE FBPE'S.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-18 Cont ID  
Sent By dpalmer Date 2006-08-18 Time 07:23 Rev Time 0.00
Received By dpalmer Date 2006-08-18 Time 07:21 Sent To  
Notes
2006-08-18 00:00:00*** UNSAT *****
  
 1) NOTE: PLEASE COMPLETE ALL NEW
 CIRCUITING ON PLANS AND CORRELATE WITH
 PANEL SCHEDULE(S) TO BE SUBMITTED.
 PLEASE SHOW ALL NEW ELECTRICAL ETC.
 PLEASE CLARIFY RECEPTS (GFI) IN BATH
 RMS.
 PLEASE SEE MISSING GFI RECEPTS ALONG
 KITCHEN COUNTER SPACE.
 PLEASE SEE MISSING ARC FAULT PROTECTION
 INDICATED FOR NEW ELECTRICAL IN BEDRMS.
 210.8A6,210.12B,210.11C1,210.11C3,408.4,
 240.4, 310.16, 210.52D ETC.
 2002 NEC.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-11-13 Cont ID  
Sent By mawillia Date 2006-11-13 Time 09:34 Rev Time 0.00
Received By mawillia Date 2006-11-13 Time 09:34 Sent To  
Notes
2006-11-13 09:35:46******STAMPED AS APPROVED*****

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-09-13 Cont ID  
Sent By mwennerg Date 2006-09-13 Time 09:49 Rev Time 0.00
Received By mwennerg Date 2006-09-13 Time 09:49 Sent To  
Notes
2006-09-13 00:00:00STAMPED PLANS THAT WERE PASSED ON
 8/21/06 BY M.A. WILLIAMS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-08-21 Cont ID  
Sent By mawillia Date 2006-08-21 Time 15:17 Rev Time 0.00
Received By mawillia Date 2006-08-21 Time 15:17 Sent To P
Notes
2006-08-21 00:00:00**ATTENION**
  
  
  
  
 STRUCTURES UNDERGOING CONSTRUCTION,
 ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-11-13 Cont ID  
Sent By adarroug Date 2006-11-13 Time 08:42 Rev Time 0.00
Received By adarroug Date 2006-11-13 Time 08:42 Sent To E
Notes
2006-11-13 08:43:10TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-11-12 Cont ID  
Sent By adarroug Date 2006-11-12 Time 11:10 Rev Time 0.00
Received By adarroug Date 2006-11-12 Time 11:10 Sent To  
Notes
2006-11-12 11:10:29WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-13 Cont ID  
Sent By adarroug Date 2006-10-13 Time 15:09 Rev Time 0.00
Received By adarroug Date 2006-10-13 Time 15:09 Sent To  
Notes
2006-10-22 09:29:55BOB BOARD #6
2006-10-13 15:10:06WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-22 Cont ID  
Sent By adarroug Date 2006-09-22 Time 16:43 Rev Time 0.00
Received By adarroug Date 2006-09-22 Time 16:43 Sent To  
Notes
2006-09-23 00:00:00TO "BOB"#18
2006-09-22 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-09 Cont ID  
Sent By adarroug Date 2006-09-09 Time 17:49 Rev Time 0.00
Received By adarroug Date 2006-09-09 Time 17:49 Sent To  
Notes
2006-09-09 00:00:00TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-21 Cont ID  
Sent By mawillia Date 2006-08-21 Time 15:13 Rev Time 0.00
Received By mawillia Date 2006-08-17 Time 09:41 Sent To  
Notes
2006-08-17 00:00:008/17/06-THIS APPL. WAS ROUTED TO
 INCOMING TODAY. ADARROUGH
  
 TO "BOB"#17
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-09-05 Cont ID  
Sent By tgordon Date 2006-09-05 Time 10:52 Rev Time 0.15
Received By tgordon Date 2006-09-05 Time 10:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-10-23 Cont ID  
Sent By jleech Date 2006-10-23 Time 14:25 Rev Time 0.00
Received By jleech Date 2006-10-23 Time 14:25 Sent To  
Notes
2006-10-23 14:28:40PROVISO;
 AIR GAP FITTING REQUIRED
 FOR ICE MACHINE DRAIN LINE

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-10-11 Cont ID  
Sent By jleech Date 2006-10-11 Time 08:30 Rev Time 0.00
Received By jleech Date 2006-10-11 Time 08:30 Sent To  
Notes
2006-10-11 08:35:09 
 1.THIRD REQUEST. PLEASE PROVIDEINFOREMATION ON ICE
 MACHINE FROM THE MANUFACTURE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-09-11 Cont ID  
Sent By jleech Date 2006-09-11 Time 08:10 Rev Time 0.00
Received By jleech Date 2006-09-11 Time 08:10 Sent To  
Notes
2006-09-11 00:00:00DENIED;
 1. (SECOND REQUEST) PLEASE PROVIDE CUT
 SHEETS FOR ICE MACHINE.
 2.MECHANICAL VENTS ARE ONLY PERMITED ON
 THE TOP 4 HORIZONTAL BRANCH INTERVALS.
 IS THIS UNIT ON THE TOP 4 FLOORS?
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-08-31 Cont ID  
Sent By jleech Date 2006-08-31 Time 15:21 Rev Time 0.00
Received By jleech Date 2006-08-31 Time 15:13 Sent To  
Notes
2006-08-31 00:00:00DENIED;
 NOT ENOUGH INFORMATION TO COMPLETE A
 PLUMBING PLAN REVIEW.
 A BAR SINK IS BEING ADDED TO THE
 PLUMBING SYSTEM, A SANITARY RISER
 DIAGRAM IS REQUIRED SHOWING WHERE THE
 SANITARY BRANCH DRAIN WILL DISCHARGE AND
 HOW THE BAR SINK WILL BE VENTED.
 SUBMIT SPECIFICATION SHEETS FOR ICE
 MACHINE, AND SHOW HOW IT WILL DRAIN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status N Date 2006-09-05 Cont ID  
Sent By mmclean Date 2006-09-05 Time 10:54 Rev Time 0.00
Received By mmclean Date 2006-09-05 Time 10:54 Sent To  
Notes
***NONE***