Plan Review Details - Permit 06071436
Plan Review Stops For Permit 06071436
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2007-06-01 Cont ID  
Sent By mjacobs Date 2007-06-01 Time 14:26 Rev Time 0.00
Received By mjacobs Date 2007-06-01 Time 14:20 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-11-09 Cont ID  
Sent By alange Date 2006-11-09 Time 14:42 Rev Time 0.00
Received By alange Date 2006-11-09 Time 14:42 Sent To  
Notes
2006-11-09 14:43:23SEPERATE PERMIT REQUIRED FOR FENCING

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-08-10 Cont ID  
Sent By alange Date 2006-08-10 Time 10:58 Rev Time 0.00
Received By alange Date 2006-08-10 Time 10:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-04-10 Cont ID  
Sent By dpalmer Date 2007-04-10 Time 11:31 Rev Time 0.00
Received By dpalmer Date 2007-04-10 Time 08:14 Sent To  
Notes
2007-04-10 11:33:55** NEEDS NEW RE-RECORDED NOC ONCE PERMIT IS READY FOR
 ISSUANCE. THE NOC HAS EXPIRED PER FS 713.13(2).
  
 ** REDLINED PLANS.
  
 ATS IS SE RATED AS SUBMITTED ON SPECS AND TAPS SHOULD
 BE MADE ON THE LOAD SIDE OF THE MAIN FOR AIC RATING
 PROTECTION OF MAIN. 110.9.
 STAMP FOR ELEC ONLY.
 NEEDS GAS AND ZONING REVIEWS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-11-21 Cont ID  
Sent By dpalmer Date 2006-11-21 Time 14:49 Rev Time 0.00
Received By dpalmer Date 2006-11-21 Time 14:30 Sent To  
Notes
2006-11-21 14:49:31*** UNSAT2ND REVIEW ***
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW AND
 PLEASE SUBMIT TWO COMPLETED SETS FOR REVIEW. PLEASE
 REMOVE ALL SHEETS WHICH ARE NOT RELEVANT TO THIS SCOPE
 OF WORK BEING DONE.
 PLEASE SEE NO REVISED RISER DIAGRAM COULD BE LOCATED.
 IT IS NO CLEAR WHICH SETS ARE TO BE REVIEWED AS WHAT
 APPEARS TO BETHE NEW SETS ARE NOT COMPLETE WITH
 INFORMATION WHICH IS NEED FROM THE PREVIOUS NOTES OR
 PREVIOUS PLANS.
  
 FBC 106.1.2, 106.1.3, ADMIN SECTION.
  
 2) NOTE: PLEASE BE SURE MAKE PHOTO-COPIES OF ANY PLANS
 WHICH ARE DRAWN IN PEN OR PENCIL. PLEASE KNOW WE CAN
 NOT ACCEPT PLANS DONE LIKE THIS AS CHANGES CAN BE
 READILY DONE.
 FBC 106.1.3.
  
 3) NOTE: PLEASE SEE BASED ON THE NEW CONTRACT VALUE
 SUBMITTED, ADDITIONAL FEES WILL BE OWED
  
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
 *IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF THE
 NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE DO
 NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-09 Cont ID  
Sent By dpalmer Date 2006-08-09 Time 18:27 Rev Time 0.00
Received By dpalmer Date 2006-08-09 Time 17:36 Sent To  
Notes
2006-08-09 00:00:00***** UNSAT ****
  
 1) NOTE: PLEASE SEE THE 2002 NEC.
 225.31-225.39, 230.72, 240.4, 310.16,
 408.16, 408, 250.110, 250.122, 250.24B,
 240.21 ETC
 PLEASE SEE THERE ARE MANY ITEMS MISSING
 AND/OR ARE NOT SHOWN FOR CODE
 COMPLIANCE.
 PLEASE VERIFY THE RISER WITH EQUIPMENT
 WHICH IS BEING SHOWN FOR USE. PLEASE SEE
 OCP ON GEN, RATINGS OF EQUIPMENT,
 MISSING DISCONNECTING MEANS FOR FEEDERS
 FROM GEN (MAY NOT USE BRKR ON UNIT),
 CONDUCTORS SIZING, EQUIPMENT USED AS
 RACEWAYS, GTOUNDING/EQUIPMENT GORUNDING
 CONDUCTORS. ETC.
  
 2) NOTE: PLEASE SEE NEC 220 FOR LOAD
 CALCULATIONS WHICH ARE TO BE COMPLETED
 PER NEC. THE RESIDENTIAL USE IS NOT
 CLEAR AT THIS TIME, HOWEVER IN ANY CSE
 PLEASE COMPLETE ELECTRICAL CALCULATIONS
 FOR COMMERICAL LOADS ETC.
 220.3,220.10,220.13,220.11 ETC
 PLEASE SEE 215.3,230.42 ETC
  
 3) NOTE: PLEASE SEE RESIDENTIAL PANEL IS
 SHOWING AN AHU#9??? WHERE IS 1-8?
 NONE COULD BE LOCATED ON THESE PANEL
 SCHEDULE EXCEPT FOR TWO.??
  
 4) NOTE: PLEASE PROVIDE A LAYOUT OF ALL
 SERVICE EQUIPMENT. PLEASE PROVIDE AN
 OVERVIEW AS THE ONLY EQUIPMENT SHOWN WAS
 THE EXISTING 800A MAIN.
  
 5) NOTE: PLEASE SEE ATS NEEDS TO BE
 HIGHLIGHTED ON SPECS FOR WHICH ONE IS
 BEING USED. PLEASE KNOW AS PER NOTES
 ABOVE, THE ATS THE WAY IT IS SHOWN DOES
 NOT MEET CODE.
  
 6) NOTE: PLEASE SEE ALL PLANS, DESIGNS
 AND LOAD CALULATIONS SHALL CONTAIN A
 STATEMENT" DRAWN BY: PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPSOSIBLE FOR
 SAID PLANS AND DESIGNS.
 FBC 106.1.2
  
 7) NOTE: PLEASE PROVIDE COPY OF CONTRACT
 FOR COMPLETE SCOPE OF WORK FOR THIS
 PERMIT. PLEASE SEE FBC 108.3 WHICH
 REQUIRES VALUE FOR ALL LABOUR AND
 MATERIALS EVEN IF ANY EQUIPMENT IS OWNER
 SUPPLIED. PLEASE KNOW, THE MARSHALL'S
 /SWIFT GUIDE MAY BE USED IN VALUATIONS
 BY THIS OFFICE AS ADOPTED BY THE FBC
 2004.
  
 ** UNABLE TO DO A COMPLETE REVIEW AT
 THIS TIME.
 PLEASE BE SURE TO GO OVER PLANS AND
 RISER BEFORE RESUBMITTING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-29 Cont ID  
Sent By mwennerg Date 2006-12-29 Time 13:18 Rev Time 0.00
Received By mwennerg Date 2006-12-29 Time 13:18 Sent To  
Notes
2006-12-29 13:24:37***PROVISO***
  
 1) IF THE POSSIBILITY OF MECHANICAL DAMAGE EXISTS WITH
 REGARDS TO THE LOCATION OF THE GENERATOR, PROTECTIVE
 BARRIERS MAY NEED TO BE INSTALLED.
  
 2) PLEASE CLARIFY WHAT BUILDING EQUIPMENT WILL BE
 IMPACTED UNDER POWER OF THE GENERATOR.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-09-01 Cont ID  
Sent By mwennerg Date 2006-09-01 Time 14:15 Rev Time 0.00
Received By mwennerg Date 2006-09-01 Time 14:15 Sent To  
Notes
2006-09-01 00:00:00***PROVISO***
  
 1) WORK SHALL COMPLY WITH NFPA 110,
 STANDARD FOR EMERGENCY AND STANDBY POWER
 SYSTEMS.
  
 2) PLEASE SUBMIT ALL APPLICABLE
 MANUFACTURER SPEC SHEETS FOR EQUIPMENT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2007-05-29 Cont ID  
Sent By kstevens Date 2007-05-29 Time 08:29 Rev Time 0.00
Received By kstevens Date 2007-05-29 Time 08:29 Sent To  
Notes
2007-05-29 08:30:03SEPARATE GAS PERMIT REQUIRED
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL) - (SITE
 PLAN INDICATES NATURAL, BUT GAS TYPE IS
 REQUIRED ON ISOMETRIC).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF
 SHEETS SUBMITTED DO NOT SHOW
 INSTALLATION INSTRUCTIONS NOR DO THEY
 INDICATE MINIMUM CLEARANCES FROM
 STRUCTURES.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-08-21 Cont ID  
Sent By kstevens Date 2006-08-21 Time 18:21 Rev Time 0.00
Received By kstevens Date 2006-08-21 Time 18:20 Sent To  
Notes
2006-08-21 00:00:00SEPARATE GAS PERMIT REQUIRED
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL) - (SITE
 PLAN INDICATES NATURAL, BUT GAS TYPE IS
 REQUIRED ON ISOMETRIC).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF
 SHEETS SUBMITTED DO NOT SHOW
 INSTALLATION INSTRUCTIONS NOR DO THEY
 INDICATE MINIMUM CLEARANCES FROM
 STRUCTURES.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-18 Cont ID  
Sent By adarroug Date 2007-06-18 Time 14:18 Rev Time 0.00
Received By adarroug Date 2007-06-18 Time 14:18 Sent To Z
Notes
2007-06-18 14:18:29TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-02 Cont ID  
Sent By spalmer Date 2007-04-02 Time 18:17 Rev Time 0.00
Received By spalmer Date 2007-04-02 Time 18:17 Sent To  
Notes
2007-04-04 17:16:34TO COMM BOARD # 49
2007-04-02 18:17:38WAITING FOR COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-04 Cont ID  
Sent By adarroug Date 2006-11-04 Time 18:35 Rev Time 0.00
Received By adarroug Date 2006-11-04 Time 18:35 Sent To  
Notes
2006-11-07 14:31:01TO "COMM" BD#1
2006-11-04 18:35:23WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-01 Cont ID  
Sent By mwennerg Date 2006-09-01 Time 14:20 Rev Time 0.00
Received By mwennerg Date 2006-07-27 Time 13:52 Sent To  
Notes
2006-08-09 00:00:00TO "COMM" BD#51
2006-07-27 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-08-11 Cont ID  
Sent By pkrauss Date 2006-08-11 Time 06:55 Rev Time 0.00
Received By pkrauss Date 2006-08-11 Time 06:50 Sent To  
Notes
2006-08-11 00:00:00NATURAL GAS GENERATOR.

Review Stop Z ZONING
Rev No 4 Status P Date 2007-07-17 Cont ID  
Sent By lfranco Date 2007-07-17 Time 18:35 Rev Time 0.00
Received By lfranco Date 2007-07-17 Time 18:35 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2007-04-19 Cont ID  
Sent By lfranco Date 2007-04-19 Time 19:30 Rev Time 0.00
Received By lfranco Date 2007-04-19 Time 19:30 Sent To I
Notes
2007-04-20 15:58:33PLANNING AND ZONING DEPARTMENT:*** FAILED***
 4-19-07 COMMENTS WERE NOT ADDRESSED.
  
 1.PROVIDE ALL RESPONSES IN WRITING.
  
 2.PURSUANT TO SECTION 94-444(B) PROVIDE APPROPRIATE
 SCREENING, WHICH INCLUDES WALLS WITH LANDSCAPING.
 REVISE ACCORDINGLY. ALSO, SUBMIT ELEVATIONS OF THE
 GENERATOR SHOWING THE SCREENING
 REQUIREMENTS.
  
 3.IS THE GENERATOR PROPOSED ON THE SIDE OF THE ROAD?
 PROVIDE WIDTH OF THE ROADWAY TO MAKE SURE CLEARANCE FOR
 CARS IS THERE.
  
 4.THE SITE PLAN SHOWS PARKING THAT IS NO LONGER PART
 OF THE STORAGE FACILITY.PLEASE CONTACT STAFF BELOW TO
 DISCUSS SURVEY, ORIGINAL APPROVAL FOR THIS COMMERCIAL
 PLANNED DEVELOPMENT, ETC.THERE ARE DISCREPANCIES IN
 THE ORIGINAL APPROVAL AND WHAT WAS ACTUALLY BUILT.
  
 IF YOU HAVE ANY QUESTIONS,PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1435

Review Stop Z ZONING
Rev No 2 Status F Date 2006-11-17 Cont ID  
Sent By lfranco Date 2006-11-17 Time 20:06 Rev Time 0.00
Received By lfranco Date 2006-11-17 Time 20:06 Sent To I
Notes
2006-11-17 20:16:10PLANNING AND ZONING DEPARTMENT:***** FAILED ******
  
 1.PROVIDE ALL RESPONSES IN WRITING.
  
 2.PURSUANT TO SECTION 94-444(B) PROVIDE APPROPRIATE
 SCREENING, WHICH INCLUDES WALLS WITH LANDSCAPING.
 REVISE ACCORDINGLY. ALSO, SUBMIT ELEVATIONS OF THE
 GENERATOR SHOWING THE SCREENING REQUIREMENTS.
  
 3.IS THE GENERATOR PROPOSED ON THE SIDE OF THE ROAD?
 PROVIDE WIDTH OF THE ROADWAY TO MAKE SURE CLEARANCE FOR
 CARS IS THERE.
 ALTHOUGH SITE PLAN WAS SUBMITTED IN RE-SUBMITTAL
 PACKET.IT DOES NOT ADDRESS THE LAST CONVERSATION I
 HAD WITH THE APPLICANT.THE SITE PLAN SHOWS THE AREA
 WHERE THE PROPOSED GENERATOR IS TO BE PLACED, AS A
 TWO-WAY ROADWAY.PROVIDE GENERATOR, SCREENING (FENCE
 AND LANDSCAPE) TO SCALE ON SITE PLAN AND SHOW HOW THE
 MANEUVERING OF VEHICLES WILL TAKE PLACE IN THE
 IMMEDIATE AREA.PROPER MANEUVERING FOR VEHICLES TO
 TURN AROUND NEED TO BE SHOW IN THIS AREA.STAFF
 SUGGESTED THE GENERATOR TO BE PLACED IN AN AREA THAT
 WAS NOT ON THE ROADWAY ACCESS, SUCH AS THE NORTHWEST
 CORNER WHERE BLDG. A AND "L SHAPE" BUILDING MEET.
  
 4.A SEPARATE PERMIT APPLICATION FOR THE FENCE NEEDS
 TO BE SUBMITTED TO CONSTRUCTION SERVICES FOR THE
 SCREENING OF THE GENERATOR.
  
  
 IF YOU HAVE ANY QUESTIONS,PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1435
  

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-28 Cont ID  
Sent By lfranco Date 2006-08-28 Time 18:03 Rev Time 0.00
Received By lfranco Date 2006-08-28 Time 18:03 Sent To I
Notes
2006-08-28 00:00:00PLANNING AND ZONING DEPARTMENT:FAILED
  
 1.PROVIDE ALL RESPONSES IN WRITING.
  
 2.PURSUANT TO SECTION 94-444(B)
 PROVIDE APPROPRIATE SCREENING, WHICH
 INCLUDES WALLS WITH LANDSCAPING.REVISE ACCORDINGLY.
 ALSO, SUBMIT ELEVATIONS OF
 THE GENERATOR SHOWING THE SCREENING
 REQUIREMENTS.
  
 3.IS THE GENERATOR PROPOSED ON THE
 SIDE OF THE ROAD?PROVIDE WIDTH OF THE
 ROADWAY TO MAKE SURE CLEARANCE FOR CARS
 IS THERE.
  
 IF YOU HAVE ANY QUESTIONS,PLEASE
 CONTACT ME AT THE NUMBER BELOW.
  
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1435
  