| Plan Review Stops For Permit 06071428 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-09-29 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-09-29 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-09-29 |
Time |
08:45 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-08-17 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-08-17 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-08-17 |
Time |
08:51 |
Sent To |
|
|
| Notes |
| 2006-08-17 00:00:00 | DENIED | | | | | | SHOW GENERATOR SLAB DETAIL AND METHOD OF | | | ATTACHMENT TO SLAB. | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2006-09-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-09-20 |
Time |
17:53 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-09-20 |
Time |
17:28 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-08-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2006-08-09 |
Time |
09:53 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2006-08-09 |
Time |
07:57 |
Sent To |
P |
|
| Notes |
| 2006-08-09 00:00:00 | | | | | | | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | THE VALUE ON THE APPLICATION MUST | | | INCLUDE THE TOTAL COST OF LABOR AND | | | MATERIAL FOR THE GENERATOR, EQUIPMENT | | | (TRANSFER SWITCHES, PANELS ETC.) | | | AND PAD PER 108.3 FBC AS AMENDED. | | | INCREASE THE VALUE AT THE COUNTER WHEN | | | RESUBMITTING, AND GET A RECEIPT FROM THE | | | PERMIT CLERK. | | | | | | 1} PROVIDE A RISER DIAGRAM PER 215.5 | | | INCLUDING GENERATOR AND RELATED | | | EQUIPMENT. | | | | | | 2} PROVIDE MANUFACTURERS SPECIFICATIONS | | | INDICATING RECOMMENDED SETBACKS AND | | | ELECTRICAL SPEC'S FOR THE GENERATOR AND | | | TRANSFER SWITCH. | | | | | | 3} PLEASE NOTE A DISCONNECT IS REQUIRED | | | PER 225.31 AND 32. INDICATE LOCATION ON | | | THE RISER AND SITE PLAN. THE TRANSFER | | | SWITCH MAY NOT MEET THIS REQUIREMENT, | | | SEE SPECS BEFORE SUBMITTING. | | | | | | 4} PROVIDE A LOAD CALCULATION FOR THE | | | LOAD INTENDED TO BE SERVED. 215.5. | | | | | | 5} PROVIDE A PANEL SCHEDULE FOR THE | | | GENERATOR PANEL. 106.3.5.4 FBC AS | | | AMMENDED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2006-08-10 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-08-10 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2006-08-10 |
Time |
15:03 |
Sent To |
M |
|
| Notes |
| 2006-08-10 00:00:00 | NOTE: GAS PERMIT REQUIRED. GAS CONTRAC- | | | TOR TO SUBMIT PLANS WITH PERMIT APPLICA- | | | TION. ALL GAS INSPECTIONS TO BE COMPLETE | | | BEFORE FINAL GEN/RES INSPECTION. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-09-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-19 |
Time |
08:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-19 |
Time |
08:29 |
Sent To |
E |
|
| Notes |
| 2006-09-19 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-09-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-13 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-13 |
Time |
14:15 |
Sent To |
Z |
|
| Notes |
| 2006-09-13 00:00:00 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-08-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-07 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-07 |
Time |
11:54 |
Sent To |
E |
|
| Notes |
| 2006-08-07 00:00:00 | TO "GEN-RES" "E" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-08-17 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-08-17 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-07-26 |
Time |
16:03 |
Sent To |
|
|
| Notes |
| 2006-07-26 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2006-09-29 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-09-29 |
Time |
12:05 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2006-09-29 |
Time |
12:05 |
Sent To |
|
|
| Notes |
| 2006-09-29 00:00:00 | *** PROVISO *** | | | 1) PER 2004 FBC, FUEL GAS - POWERED | | | EQUIPMENT - PERMANENTLY INSTALLED | | | EQUIPMENT POWERED BY INTERNAL COMBUSTION | | | ENGINES SHALL BE INSTALLED IN ACCORDANCE | | | WITH MANUFACTURE'S INSTALLATION | | | INSTRUCTIONS AND NFPA 37. | | | | | | NFPA 37 INSTALLATION & USE OF STATIONARY | | | COMBUSTION ENGINES & GAS TURBINES: | | | 4.1.4ENGINES (GENERATORS) LOCATED | | | OUTDOORS SHALL BE MINIMUM OF 5 FT FROM | | | OPENINGS IN WALLS & AT LEAST 5 FT FROM | | | STRUCTURES HAVING COMBUSTIBLE WALLS.A | | | MINIMUM CLEARANCE IS NOT REQUIRED WHEN | | | (1) THE ADJACENT WALL HAS A MINIMUM FIRE | | | RESISTANCE RATING OF 1 HOUR OR (2) THE | | | WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF | | | NON-COMBUSTIBLE MATERIALS, AND IT HAS | | | BEEN DEMONSTRATED THAT A FIRE WITHIN THE | | | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE | | | MATERIALS OUTSIDE THE ENCLOSURE. | | | INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS | | | SHOULD NOT TERMINATE UNDER STRUCTURES OR | | | WHERE THE EXHAUST MIGHT BE DRAWN INTO | | | THE VENTILATION INTAKES. | | | | | | 2004 FMC 804.3.5 #3, WHERE THE | | | TERMINATION IS LOCATED BELOW AN ADJACENT | | | ROOF STRUCTURE, THE TERMINATION POINT | | | SHALL BE LOCATED AT LEAST 3 FT FROM THE | | | ROOF STRUCTURE. | | | | | | PLEASE NOTE, WHILE ZONING ALLOWS | | | MECHANICAL EQUIPMENT TO ENCROACH 4 FT | | | INTO THE REQUIRED SETBACK, GENERATORS | | | SHALL MAINTAIN THE REQUIRED ABOVE | | | MENTIONED CLEARANCES TO THE ADJACENT | | | PROPERTY STRUCTURES, I.E. FENCE, | | | BUILDING, WINDOWS, DOORS, OR OPENINGS. | | | | | | FOLLOW MANUFACTURE'S RECOMMENDED | | | CLEARANCES AROUND EQUIPMENT FOR | | | SERVICING,AND PROVIDE MANUFACTURE'S | | | INSTALLATION INSTRUCTIONS AT THE JOBSITE | | | FOR THE FIELD INSPECTOR. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-08-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-08-11 |
Time |
16:21 |
Rev Time |
0.15 |
| Received By |
tgordon |
Date |
2006-08-11 |
Time |
16:21 |
Sent To |
B |
|
| Notes |
| 2006-08-11 00:00:00 | *** DENIED *** | | | 1) SEE ZONING REVIEW, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-09-15 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-09-15 |
Time |
18:27 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-09-15 |
Time |
18:27 |
Sent To |
I |
|
| Notes |
| 2006-09-15 00:00:00 | NOTE: THE PROPOSED GENERATOR SHALL NOT | | | BE CLOSER THAN 6FT FROM REAR PROPERTY | | | LINE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-08-05 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-08-05 |
Time |
11:28 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-08-05 |
Time |
11:28 |
Sent To |
I |
|
| Notes |
| 2006-08-05 00:00:00 | DENIED, | | | 1. THE PROPOSED GENERATOR MUST BE SHOWN | | | ON THE TWO COPY OF SURVEY. | | | 2. THE SURVEY MUST PROVIDE THE REAR | | | SETBACK OF THE EXISTING STRUCTURE FROM | | | PROPERTY LINE. | | | 3. THE DRAWING DOES NOT PROVIDE | | | INFORMATION FOR A COMPLETE REVIEW. | | | | | | NOTE: | | | SEC 94-303 MECHANICAL/POOL | | | EQUIPMENT/GENERATOR MAY NOT PROJECT MORE | | | THAN FOUR FEET INTO A SETBACK. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|