| 2006-09-10 00:00:00 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE MISSING GFI RECEPTS |
| | PER 210.52C1 ALONG KITCHEN COUNTER |
| | SPACE. |
| | PLEASE SEE IS DIFFICULT TO SCALE AS |
| | PLANS SUBMITTED ARE NOT SCALED OR DONE |
| | TO THE MIN 1/8" SCALE AS REQUIRED UNDER |
| | THE FBC 106.1 |
| | |
| | 2) NOTE: PLEASE SEE MISSING AHU'S AND |
| | CU'S ON PLANS ALONG WITH DISCONNECTS PER |
| | 440.11, 110.26 |
| | |
| | 3) NOTE: PLEASE SEE AS THE A/C CU'S ARE |
| | NOT SHOWN, UNABLE TO VERIFY THE GFI |
| | RECEPTS REQUIRED PER 210.63/210.8A |
| | |
| | 4) NOTE: PLEASE SEE PLANS DO NOT SHOW |
| | WATER HEATERS AND DISCONNECTS REQUIRED. |
| | PLEASE SEE 422.31, 422.17 |
| | |
| | 5) NOTE: PLEASE SEE LOAD CALCULATIONS |
| | STILL BE TO BE REVISED TO NEC 220.31 |
| | PLEASE SEE THE A/C HEAT MAY NOT BE |
| | FIGURED IN WITH THE GEN LTS AND RECEPTS |
| | . |
| | |
| | 6) NOTE: PLEASE SEE 408.6, THE PANEL |
| | SCHEDULE SHALL BE SPECIFIC TO THE ROOMS |
| | AND AREAS IN WHICH THEY ARE FEEDING, IT |
| | IS KNOWN THAT THESE WILL MOST LIKELY BE |
| | REVISED DURING CONSTRUCTION, HOWEVER IF |
| | KNOWN AT THIS TIME PLEASE SHOW, AS THEY |
| | CAN BE REVISED AT A LATER DATE. |
| | |
| | 7) NOTE: PLEASE SEE GROUNDING ELECTRODE |
| | CONDUCTOR TO BE SIZED PER 250.66. |
| | #2 MIN). |
| | |
| | 8) NOTE: PLEASE SEE THAT ALL PLANS AND |
| | DESIGNS SHALL CONTAIN THE PRINTED NAME |
| | AND SIGNATURE OF THE PERSON RESPOSIBLE |
| | FOR PLANS/DESIGNS. |
| | DRAWN BY: ETC,,,, |
| | THIS IS FOR ALL DOCUMENTS. |
| | FBC 106.1.21 |
| | |
| | 9) NOTE: PLEASE KNOW ALL SD'S WITHIN 20' |
| | OF COOKING APPLIANCES SHALL BE RESETTING |
| | /PHOTO-ELECTRIC TYPE PER NFPA-72 11.8.3 |
| | PLEASE ALSO KNOW ALL SD'S MUST BE |
| | ATLEAST 3' FROM BATH DOOR. |
| | |
| | 10) NOTE: PLEASE SEE 410.8FOR CLOSET |
| | LTS WHICH ARE BEING SHOWN IN SHELVING |
| | AREA. |
| | |
| | 11) NOTE: PLEASE SEE 210.52B1 AS THE |
| | DINING ROOMS AND AREAS ARE REQUIRED TO |
| | BE ON ONE OR MORE OF THE SMALL APPLIANCE |
| | CIRUITS. PLEASE SEE 210.11C1, 220.16 |
| | |
| | 12) NOTE: PLEASE INCLUDE AIC RATINGS FOR |
| | ALL NEW MAINS PER 110.9. |
| | |
| | 13) NOTE: PLEASE SEE GAS PIPE REQUIRED |
| | TO BE BONDEDTO THE GROUNDING ELECTRODE |
| | SYSTEM.250.104 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |