Plan Review Details - Permit 06071405
Plan Review Stops For Permit 06071405
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-08-28 Cont ID  
Sent By rmcdouga Date 2006-08-28 Time 08:05 Rev Time 0.00
Received By rmcdouga Date 2006-08-28 Time 08:05 Sent To  
Notes
2006-08-28 00:00:00REVISED ROOFING PRODUCT APPROVAL AND
 ENGINEERING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-08-10 Cont ID  
Sent By rmcdouga Date 2006-08-10 Time 16:03 Rev Time 0.00
Received By rmcdouga Date 2006-08-10 Time 16:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-01 Cont ID  
Sent By rmcdouga Date 2006-08-01 Time 09:37 Rev Time 0.00
Received By rmcdouga Date 2006-08-01 Time 09:37 Sent To  
Notes
2006-08-01 00:00:00DENIED
  
 1) SPECIFY HOW THE ROOF PRESSURES FOR
 THE PERIMETER AND END ZONES WERE
 DETERMINED. SUBMIT THE SIGNED AND SEALED
 CALCULATIONS OR THE WIND TUNNEL TEST
 REPORT USED TO DETERMINE THE ROOF
 PRESSURES. SEE FIRST REVIEW.
  
 2) SUBMIT SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING. SEE
 ITEM 2 ON FIRST REVIEW.
  
 3) THE COVERSHEET WITH THE FL# THAT WAS
 SUBMITTED IS NOT THE ONE THAT
 CORRESPONDS WITH NOA 03-0501.03. THE
 CORRECT ONE IS FL#617-R1. PLEASE SUBMIT
 THE CORRECT ONE.
  
 4) FROM THE INFORMATION THAT WAS
 SUBMITTED IT APPEARS THAT ONLY A THREE
 FOOT WIDE ARE AT THE PERIMETER OF THE
 ROOF AND THE PARAPETS ARE BEING
 REROOFED. IS THIS CORRECT?
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-25 Cont ID  
Sent By rmcdouga Date 2006-07-25 Time 08:22 Rev Time 0.00
Received By rmcdouga Date 2006-07-25 Time 08:22 Sent To  
Notes
2006-07-25 00:00:00DENIED
  
 1) SUBMIT THE ROOF PRESSURES FOR ZONES
 1,2 AND 3 OF THE 15 STORY STRUCTURE.
 SPECIFY HOW THESE PRESSURES WERE
 DETERMINED(PROVIDE CALCULATIONS OR WIND
 TUNNEL TEST REPORT). SPECIFY THE MEAN
 ROOF HEIGHT AND EXPOSURE CATEGORY.
  
 2) SUBMIT SIGNED AND SEALED RAS 117
 CALCULATIONS FOR THE FASTENER DENSITIES
 WHICH INDICATE THAT THE REQUIRED UPLIFT
 PRESSURES WILL BE MET FOR THE VARIOUS
 ROOF ZONES.
  
 3) SUBMIT A COVERSHEET FROM THE STATE
 PRODUCT APPROVAL WEBSITE WITH THE FL#
 FOR THE ROOFING PRODUCT THAT WILL BE
 INSTALLED. SEE WWW.FLORIDABUILDING.ORG.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  