Plan Review Details - Permit 06071373
Plan Review Stops For Permit 06071373
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-02-20 Cont ID  
Sent By lursu Date 2007-02-20 Time 09:21 Rev Time 0.00
Received By lursu Date 2007-02-16 Time 09:06 Sent To  
Notes
2007-02-20 09:38:52THE SITE ADDRESS AND THE PARCEL CONTROL NUMBER ARE
 CORRECT.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
2007-02-16 09:08:11NEED TO COORDINATE PARCEL ID NUMBER AND CORRECT LOT AND
 ADDRESS.
 ALSO, COORDINATE WITH PALM BEACH COUNTY RECORDS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-02-20 Cont ID  
Sent By jgomez Date 2007-02-16 Time 09:08 Rev Time 2.00
Received By jgomez Date 2007-02-15 Time 12:40 Sent To  
Notes
2007-02-16 08:06:12BUILDING REVIEWCHECKLIST:
  
 1- NEED TO PASS ALL THE OTHER TRADES: MECHANICAL AND
 PLUMBING. SEE PLAN REVIEWERS COMMENTS.
  
 2- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS.
 NOTE: THERE IS NOT FL240. NEED TO PROVIDE ANOTHER
 PRODUCT APPROVAL.ALSO, PROVIDE A COMPLETE
 INSTALLATION SCHEDULE. SEE ATTACHED SAMPLE.COMPLETE
 ALL INFORMATIONOR PROVIDE ALL THE REQUIRED
 INFORMATION IN ANOTHER FORMAT THAT WILL PROVIDE ALL
 REQUIRED INFORMATION FOR PLAN REVIEW.
  
 3- GARAGE DOOR PRODUCT APPROVAL IS MISSINGDESIGNER OF
 RECORD APPROVAL IN WRITTING AS REQUIRED BY SEC. 106.3.3
 CITY AMENDMENTS TO FBC 2004.RESUBMIT.
  
 4- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 2004 FLORIDA RESIDENTIAL CODE.
  
 5- MISSING NOTICE OF COMMENCEMENT.
  
 6- CHECK WITH PALM BEACH COUNTY FOR CORRECT PARCEL ID
 NUMBER AND LOT NUMBER.ACCORDING TO PAPA RECORDS IT
 LOOKS LIKE THE LOT WAS REPLATTED. PROVIDE REVISED
 SURVEY WITH CURRENT INFORMATION.CALLLILY URSU.
 (561)822-1239FROM CITY OF WEST PALM BEACH ADDRESSING
 SECTION TO GET CORRECT INFORMATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-10-26 Cont ID  
Sent By jgomez Date 2006-10-26 Time 17:27 Rev Time 2.50
Received By jgomez Date 2006-10-25 Time 17:38 Sent To  
Notes
2006-10-26 17:38:45BUILDING REVIEW 2ND CHECKLIST:
  
 1- ENERGY CALCULATIONS:REVISE INFORMATION ON TOP OF
 FORM.NEED CORRECT ADDRESS,NAME OF BUILDER AND
 PERMITTING OFFICE.
  
 2- ENGINEER TO CLARIFY WHY ARE THERE 2 DIFFERENT ZIP
 CODES ON HIS ADDRESS. SEE ADDRESS ON DRAWING TITLE
 BLOCK (33314)AND ADDRESS ON RUBBER STAMP (33440) .
 WHICH ONE IS THE CORRECT ONE. REVISE AS REQUIRED.
  
 3- PROVIDE FLORIDA OR LOCAL PRODUCT APPROVAL AS
 REQUIRED BY DCA RULE 9B-72 FOR:
 A) SINGLE HUNG WINDOWS. DADE COUNTY NOA #05-0112.01
 SUBMITTED EXPIRED ON 10/08/06. NEED CURRENT ONE.
 ***NOTE: ENGINEER OF RECORD TO REVIEW AND APPROVE
 CURRENT NOA.
 B) PRECAST CONCRETE LINTELS.
 ***NOTE: ENGINEER TO REVIEW IT AND APPROVE IT AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 4- CLARIFY WHY EDGE DETAIL FOR GARAGE AND SHOWER STEP
 DOWN SHOW NO REINFORCEMENT.SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 5- SHEET T1:
 A) SPECIFY CONNECTORS AT THE ENDS OF DOUBLE 2X12
 WOOD BEAM WHEN RESTING ON THE MASONRY WALL. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 B) REVISE STRUCTURAL NOTE #3.STAPLEWITH 7/8 LEGS
 IS NOT ALLOWED. SEE ASTM C926 AND ASTM C1063. NEED MIN.
 1 3/4" PENETRATION INTO THE THE TRUSS. REVISE AS
 REQUIRED.
  
 6- STORM SHUTTERS:
 A) THERE ARE 2 DIFFERENT PRODUCT APPROVALS
 SUBMITTED. SUBMIT ONLY ONE TYPE.
 B) IF USING FLORIDA PRODUCT APPROVAL FL240, THEN
 PROVIDE FLORIDA COVER PAGE FOR 2004 VERSION. GO TO
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD ALL INFORMATION.
  
 C) IF USING FL5870, THEN MARK ON DRAWINGS SPECIFIC
 ANCHOR TYPE AND SPACING TO BE USED AS DONE WITH
 DRAWINGS FOR FL240. TO VERIFY COMPLIANCE WITH PRODUCT
 APPLICATION. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 D) PLEASE MAKE SURE ALL DRAWINGS ARE CLEAR AND
 LEGIBLE.
  
 ***NOTE: PLEASE MAKE SURE SELECTED PRODUCT IS REVIEWED
 AND APPROVED BY THE ENGINEER OF RECORD.
  
 7- CONTRACTOR TO UPDATE WORKERS COMPENSATIONAND
 LICENSE INFORMATION WITH PERMIT CLERK.
  
 8- TRUSS LAYOUT SUBMITTED. NEED COMPLETE TRUSS PACKAGE
 INCLUDING THE INDIVIDUAL TRUSSES. THIS INFORMATION NEED
 NO BE SUBMITTED NOW, BUT IT NEEDS TO BE SUBMITTED FOR
 REVIEW PRIOR TO INSTALLATION. SEE SEC. R802.10 FOR
 REQUIRED INFORMATION TO BE SUBMITTED.
  
 9- INDICATE ON SITE PLAN (OR SURVEY) HOW COMPLIANCE
 WITH SEC. R401.3 2004 FLORIDA RESIDENTIAL CODE IS
 ACHIEVED.
  
 10- ALL DRAWINGS NEED TO HAVE THE ADDRESS OF PROPOSED
 PROJECT.
  
 11- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS OF
 BEING RECORDED IF WORK IS NOT STARTED. NEED RE-RECORDED
 NOTICE OF COMMENCEMENT. SEC. 713.13(2) FLORIDA
 STATUTES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2006-10-16 Cont ID  
Sent By jgomez Date 2006-10-16 Time 13:42 Rev Time 0.00
Received By jgomez Date 2006-10-16 Time 13:42 Sent To  
Notes
2006-10-16 13:44:31RECEIVED ONLY THE SHUTTERS INFORMATION. CALLED
 CONTRACTOR TO FIND OUT WHY PACKAGE WAS SPLIT.
 CONTRACTOR SAY DRAWINGS ARE IN ZONING. HOLDING SHUTTERS
 PAKCAGE TILL GETTING PLANS BACK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-04 Cont ID  
Sent By jgomez Date 2006-08-04 Time 16:46 Rev Time 2.50
Received By jgomez Date 2006-08-04 Time 16:46 Sent To  
Notes
2006-08-04 00:00:00BUILDING REVIEW CHECKLIST:
 1- ENERGY CALCULATIONS:
 A) OWNER/AGENT TO SIGN AND DATE BOTTOM
 OF FORM.
 B) COMPLETE ALL INFORMATION ON TOP OF
 FORM, INCLUDING ADDRESS OF HOUSE.
 C) PROVIDE 2 COPIES OF ENERGY
 CALCULATIONS FOR GUEST HOUSE. ONLY ONE
 SUBMITTED.
  
 2- THERE ARE 2 DIFFERENT ZIP CODES ON
 ENGINEER'S ADDRESS. REVISE AS REQUIRED.
  
 3- SPECIFY SAFETY GLASS AT:
 A) LIVING ROOM WINDOW NEXT TO ENTRY
 DOOR.
 B) GARAGE WINDOW NEXT TO SWING DOOR.
 SECTION R308.4 2004 RESIDENTIAL CODE.
  
 4- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL AS REQUIRED BY DCA RULE 9B-72
 FOR:
 A) SINGLE HUNG WINDOWS. DADE COUNTY NOA
 #02-0419.13 SUBMITTED EXPIRED ON FEB.
 25, 2006.
 B) ALL TRUSS CONNECTORS AND STRUCTURAL
 CONNECTORS SPECIFIED ON PLANS & DETAILS.
 C) PRECAST CONCRETE LINTELS.
  
 5- ENGINEER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING ALL PRODUCT
 APPROVALS AS REQ'D BY SEC. 106.3.3 OF
 CITY AMENDMENTS TO FBC 2004.
  
 6- PROVIDE 2 COPIES OF SOIL TEST REPORT
 WITH ENGINEER'S ORIGINAL SEAL AND
 SIGNATURE AS REQ'D BY CHAPTER 471 FL.
 ST. AND SEC. 61G15-23.002. ONLY ONE
 SUBMITTED. THE OTHER ONE IS A COPY.
  
 7- SHEET #2:
 A) CONCRETE BLOCK COLUMN DETAIL: REVISE
 NUMBER OF NAILS FOR CONNECTOR META16.
 SEE CURRENT SIMPSON CATALOGUE FOR
 CORRECT NUMBER AND SIZE OF OF NAILS.
 B) REVISE SIZE OF CONCRETE PAD SHOWN ON
 CONCRETE BLOCK COLUMN DETAIL TO MATCH
 SIZE SPECIFIED ON FOUNDATION PLAN.
 C) PROVIDE EDGE DETAIL FOR SHOWER AND
 GARAGE CONCRETE SLAB RECESS. SECTION
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 8- SHEET #3:
 A) SPECIFY CALCULATED UPLIFT LOADS AND
 ALL CONNECTORS FOR DOUBLE 2X12 WOOD BEAM
 AT ENTRY PORCH. (CONNECTIONS AT THE ENDS
 OF BEAM, CORNER JOINT, ETC). SECTION
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 B) STRUCTURAL NOTE #3: REVISE SIZE OF
 FASTENER. FASTENER NEEDS TO HAVE 1 3/4"
 MIN. EMBEDMENT INTO THE TRUSS. SECTION
 R703.6 2004 RESIDENTIAL CODE AND ASTM
 C926 AND ASTM C1063.
 C) TRUSS ANCHOR SCHEDULE:
 * CONNECTOR "G": REVISE NUMBER OF NAILS.
 SEE CURRENT SIMPSON CATALOGUE.
 ** CONNECTOR "M": SPECIFY SPECIFIC SIZE
 OF CONNECTOR. REVISE NUMBER OF NAILS.
 REVISE LATERAL LOADS. SEE CURRENT
 SIMPSON CATALOGUE AND REVISE AS REQ'D.
 *** CONNECTOR "O": REVISE NUMBER OF
 NAILS. SEE SIMPSON CATALOGUE.
 D) DESIGN CRITERIA: ASCE 7-02 IS THE
 EDITION USED IN FBC 2004. NOT ASCE 7-98.
 REVISE AS REQUIRED.
 E) PROVIDE ONLY THE DETAILS THAT APPLY
 TO THIS JOB TO EXPEDITE THE REVIEW
 PROCESS & AVOID CONFUSIONS OR CONFLICTS.
  
 9- SHEET D-1:
 A) UPDATE NOTE #1. SEE SEC. R402.2 2004
 RESIDENTIAL CODE FOR REFERENCED
 STANDARDS TO BE USED.
 B) UPDATE REFERENCE ON NOTE #18. SEE
 R806 2004 RESIDENTIAL CODE.
 C) REVISE SIZE OF SOFFIT VENT ON NOTE
 #19 TO MATCH SIZE SPECIFIED ON WALL
 SECTION.
 D) REVISE NOTE #22: SEE R401.4 OF 2004
 RESIDENTIAL CODE FOR CORRECT CODE
 REFERENCE.
 E) PROVIDE ONLY THE DETAILS THAT APPLY
 TO THIS JOB TO EXPEDITE REVIEW PROCESS
 AND AVOID CONFUSION OR CONFLICTS.
  
 10- COMMENTS FOR MAIN HOUSE ALSO APPLY
 TO GUEST HOUSE. REVISE SHEET #2 AND
 SHEET D-1 OF GUEST HOUSE. SEE COMMENTS
 ABOVE.
  
 11- STORM SHUTTERS: PROVIDE KEY PLAN AND
 COMPLETE INSTALLATION SCHEDULE. SEE
 ATTACHED SAMPLE OF INSTALLATION SCHEDULE
 AND PROVIDE ALL INFORMATION REQUESTED.
  
 12- CONTRACTOR TO UPDATE WORKER
 INSURANCE INFORMATION WITH PERMIT CLERK
 SPECIALIST WHEN RESUBMITTING PERMIT
 APPLICATION.
  
 13- PLEASE RETURN SHEET #1 WITH THE
 IMPACT FEES STAMP AFTER CORRECTIONS ARE
 DONE ON ORIGINAL DRAWINGS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-01-31 Cont ID  
Sent By dpalmer Date 2007-01-31 Time 12:54 Rev Time 0.00
Received By dpalmer Date 2007-01-31 Time 07:57 Sent To M
Notes
2007-01-31 12:57:17CATV AND PHONES ARE NOT INCLUDED AND WILL BE REQUIRED
 TO BE UNDER SEPARATE PERMIT PLANS AND FEES AT A LATER
 DATE BEFORE INSTALLATION.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-23 Cont ID  
Sent By dpalmer Date 2006-10-23 Time 18:18 Rev Time 0.00
Received By dpalmer Date 2006-10-23 Time 18:00 Sent To M
Notes
2006-10-23 18:18:06*** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE MANY NOTES FROM PREVIOUS REVIEW ARE NOT
 ADDRESSED AND CANE NOT BE REVIEWED AT THIS TIME FOR
 CODE COMPLIANCE.
  
  
  
 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS FOR
 REWVIEW. PLEASE SEE SOME SHEETS HAVEOTHER SHEETS AND
 INFORMATION TAPED ONTO PLANS??
 PLEASE SEE SOME SETS CONTAIN AND HOUSE PLANS, YET NO
 GUEST HOUSE PLANS, AND OTHER SETS CONTAIN GUEST HOUSE
 BUT NO MAIN HOUSE??
  
 2) NOTE: PLEASE SEENOTES 1,2,3,5,6,7,8,9,10 FROM
 PREVIOUS REVIEW.
 FBC 106.3.5.4(8),
 PLEASE ALSO SEE FS 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY ANOTICE GIVEN AT THIS TIME.
  
 ** PLEASE SEE NEC 2002 FOR CODE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-26 Cont ID  
Sent By dpalmer Date 2006-07-26 Time 10:45 Rev Time 0.00
Received By dpalmer Date 2006-07-26 Time 09:42 Sent To Z
Notes
2006-07-26 00:00:00*******UNSAT ************
  
 1) NOTE: PLEASE SEE MISSING RECEPT FOR
 WHAT APPEARS TO BE MORE THAN 2 FT OF
 WALL IN MAIN HOUSE.
  
 2) NOTE: PLEASE COMPLETE PANEL SCHEDULES
 TO INDICATE ALL SPECIFYOED AREAS AND
 RMS. IE; LIV RM TLS, DINING RECEPTS ,
 BEDRM #1 RECEPTS ETC.
 408.4,240.4,310.16
  
 3) NOTE: PLEASE SEE PANEL FOR MAIN HOUSE
 IS NOT ON PLANS., 110.26,240.24 ETC
 PLEASE ALSO SHOW SERVICE AND LOCATION OF
 SERVICE. PLEASE SEE NOTES FOR GUEST
 HOUSE ALSO AS MAINS DO NOT APPEAR TO BE
 GROUPED ETC.
 PLEASE SEE 230.70,230.72,225.31-225.39
 PLEASE SEE MISSING DISCONNECTING MEANS
 AT GUEST HOUSE. RISER SHOWS A DISCONNECT
 HOWEVER IT IS NOT SHOWN ON PLANS WHERE
 THIS ITS.
  
 4) NOTE: PLEASE SEE MISSING GROUNDING
 ELECTRODE SYSTEM AT GUEST HOUSE PER
 250.32, 250.50
  
 5) NOTE: PLEASE CORRELATE PLANS AS GUEST
 HOUSE SHOWS 60A PANEL, AND RISER SHOWS
 100A ALONG WITH PANEL SCHEDULE.
 PLEASE SEE LOAD SHOWN EXCEEDS THE RATING
 OF THE 60A PANEL.
 2404.310.16
 106.1.2 FBC
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 7) NOTE: PLEASE VERIFY THE 60A OCP SHOWN
 FO THE 7.5KW HEAT IN GUEST HOUSE.
  
 8) NOTE: PLEASE SEE DINING RM SHALL BE
 ON ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS. PLEASE SEE IF DINING IS ON
 THEIR OWN, PLEASE SEE 210.52B1,210.11C1
 AND 220.16 AS THE THESE SHALL BE FIGURED
 AS 1500 VA.
  
 9) NOTE: PLEASE SEE NFPA-72 11.8.3 FOR
 SD'S LOCATED WITHIN 20' OF COOKING
 EQUIPMENT.
  
 10) NOTE: PLEASE CLARIFY IF THEIR ARE
 GONG TO BE LAUNDRY FACILITIES IN GUEST
 HOUSE.?
  
 ** PLEASE SEE ANY POSSIBLE ZONING
 COMMENTS WHICH MAY AFFECT PLANS.
  
 ** BEFORE AND WHEN RESUBMITTING PLANS,
 PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 SUBMIT ONE COPY OF THE OLD/VOIDED SHEETS
 FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-03-23 Cont ID  
Sent By adarroug Date 2007-03-23 Time 09:58 Rev Time 0.00
Received By adarroug Date 2007-03-23 Time 09:58 Sent To M
Notes
2007-03-23 09:59:11TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-01-31 Cont ID  
Sent By adarroug Date 2007-01-29 Time 08:46 Rev Time 0.00
Received By adarroug Date 2007-01-29 Time 14:27 Sent To  
Notes
2007-01-29 14:28:22TO "DPALMER" DESK/RESUB--EXPEDITED PERMIT--

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-01-24 Cont ID  
Sent By adarroug Date 2007-01-24 Time 10:25 Rev Time 0.00
Received By adarroug Date 2007-01-24 Time 10:25 Sent To Z
Notes
2007-01-24 10:26:20TO 5TH FL ZONING BOX/RESUB--NEW SHEETS FOR "Z"EXPEDITED
 PERMIT

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-23 Cont ID  
Sent By adarroug Date 2006-10-23 Time 15:32 Rev Time 0.00
Received By adarroug Date 2006-10-23 Time 15:32 Sent To E
Notes
2006-10-23 15:33:04TO "DPALMER"DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-14 Cont ID  
Sent By adarroug Date 2006-10-14 Time 16:58 Rev Time 0.00
Received By adarroug Date 2006-10-14 Time 16:58 Sent To B
Notes
2006-10-14 16:59:12TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-29 Cont ID  
Sent By adarroug Date 2006-09-29 Time 13:59 Rev Time 0.00
Received By adarroug Date 2006-09-29 Time 13:59 Sent To Z
Notes
2006-09-29 00:00:00TO "Z" BOX/RESUB--EXPEDITED PERMIT--

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-04 Cont ID  
Sent By jgomez Date 2006-08-04 Time 16:46 Rev Time 0.00
Received By jgomez Date 2006-07-25 Time 14:49 Sent To  
Notes
2006-07-25 00:00:00TO "SFR" "Z"-EXPEDITED PERMIT

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-03-26 Cont ID  
Sent By tgordon Date 2007-03-26 Time 14:46 Rev Time 0.30
Received By tgordon Date 2007-03-26 Time 14:46 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-02-01 Cont ID  
Sent By tgordon Date 2007-02-01 Time 08:11 Rev Time 0.45
Received By tgordon Date 2007-02-01 Time 08:11 Sent To P
Notes
2007-02-01 08:24:45*** DENIED ***
  
 1) AS NOTED IN LAST REVIEW 10-24-07 NOTE #2, MECHANICAL
 PLANS FOR MAIN GUEST HOUSE, NEED JOB ADDRESS ON THEM.
  
 2) AS NOTED IN LAST REVIEW 10-24-07 NOTE #3, THE A/C
 SYSTEM FOR THE MAIN HOUSE IS OVER-SIZED, THE MAIN HOUSE
 MANUAL J CALCULATIONS ARE CALLING FOR 19,578 SENSIBLE
 BTU'S, THE MECHANICAL PLANS ARE CALLING FOR 33,322
 SENSIBLE BTU'S, THE PLANS CAN ONLY CALL FOR 20% MORE
 THAN THE MANUAL J CAL'S, PER 2004 FBC 13-607.1.ABC.1.1,
 PLEASE CORRECT.
  
 3) SEE MAIN HOUSE MECH. PLAN, 12"RETURN AIR TRANSFER
 DUCT TO MASTER SUITE IS TO SMALL. BALANCED RETURN AIR
 MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS,
 EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL
 BE INCLUDED. PER 2004 FBC/R M1602.4.
  
 4) PLEASE SHOW ON MECHANICAL PLANS WERE THE CLOTHES
 DRYER VENT WILL TERMINATE (VENT MAY NOT DISCHARGE NEAR
 A/C CONDENSER UNIT).
  
 5) SEE MECHANICAL PLANS TO MAIN HOUSE, WHITE-OUT MAY
 NOT BE USED ON PLANS, AND DO NOT SUBMIT CHANGES IN PEN.
 PLEASE MAKE COPY'S AFTER CHANGES HAVE BEEN MADE AND
 SUBMIT COPY'S.
  
 6) ONE SET OF PLANS TO MAIN HOUSE HAS TWO DIFFERENT
 MECHANICAL PLANS, PLEASE REMOVE ONE.
  
 7) SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR
 TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-10-24 Cont ID  
Sent By tgordon Date 2006-10-24 Time 11:37 Rev Time 0.30
Received By tgordon Date 2006-10-24 Time 11:37 Sent To P
Notes
2006-10-24 11:55:21*** DENIED ***
 1) MECHANICAL PLANS NEED THE NAME AND SIGNATURE OF THE
 DESIGN PERSON ON THEM, FOR MAIN HOUSE AND COTTAGE. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE
 FOR THE DESIGN. PER FBC 104.2.1 .
  
 2) SEE MECHANICAL PLANS FOR MAIN HOUSE AND COTTAGE,
 NEED JOB ADDRESS ON THEM.
  
 3) THE MAIN HOUSE MANUAL J CALCULATIONS ARE CALLING FOR
 13,909 TOTAL SENSIBLE BTU'S, THE MECH. PLANS ARE
 CALLING FOR 33,322 TOTAL SENSIBLE BTU'S, THE PLANS CAN
 ONLY CALL FOR 20% MORE THAN THE MANUAL J CAL'S, PRE
 2004 FBC 13-607.1.ABC.1.1, PLEASE CORRECT.
  
 4) SEE MAIN HOUSE MECH. PLAN, PLEASE SHOW SIZE OF THE
 SUPPLY AIR DUCTS GOING TO THE TWO BATHROOMS.
  
 5) SETS OF PLANS ARE MIXED-UP PAGES FOR THE COTTAGE ARE
 IN WITHTHE SET FOR THE MAIN HOUSE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-04 Cont ID  
Sent By tgordon Date 2006-08-04 Time 14:34 Rev Time 0.45
Received By tgordon Date 2006-08-04 Time 14:34 Sent To B
Notes
2006-08-04 00:00:00*** DENIED ***
 1) MECHANICAL PLANS HAVE TO MUCH FLOOR
 PLAN DETAIN ON THEM AND ARE DIFFICULT TO
 READ. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
 .
  
 2) SHOW A/C EQUIPMENT LISTING WITH ALL
 THE PERTINENT INFORMATION ON THE
 MECHANICAL PLANS.
  
 3) THE MECHINACLE PLANS NEED THE
 ENGINEER"S SEAL ON THEM DUE TO HIS NAME
 AND INFORMATION IS IN THE TITLE BLOCK,
 PER FAC 61G15-23.002 .
  
 4) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT ALSO, PER 2004 FBC
 13-600.3.ABC.2
  
 5) ENERGY CALCULATIONS NEED THE ADDRESS,
 AND JURISDICTION NUMBER ON THEM.
  
 6) NEED TWO COPY'S OF ENERGY CAL'S FOR
 THE GUEST SUITE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-03-30 Cont ID  
Sent By jleech Date 2007-03-30 Time 07:23 Rev Time 0.00
Received By jleech Date 2007-03-30 Time 07:23 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-02-12 Cont ID  
Sent By jleech Date 2007-02-12 Time 07:50 Rev Time 0.00
Received By jleech Date 2007-02-12 Time 07:50 Sent To B
Notes
2007-02-12 08:00:43DENIED;
 1. WATER HEATER REQUIRED TO HAVE THERMAL EXPANSION
 PROTECTION, SECTION 607.3 SHOW ON PLANS.
 2. ADD NOTE TO PLANS THAT AREDUCED PRESSURE PRINCIPAL
 BACKFLOW PREVENTOR IS REQUIRED AT THE WATER METER.
 3. AN AUTOMATIC CLOTHES WASHER HOOKUP IS REQUIRED IN
 THE GUEST HOUSE. TABLE 403.1 (7 R3) UNDER OTHER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-10-25 Cont ID  
Sent By jleech Date 2006-10-25 Time 14:40 Rev Time 0.00
Received By jleech Date 2006-10-25 Time 14:40 Sent To B
Notes
2006-10-25 14:49:35DENIED;
 COMMENTS NOT ADDRESSED ON LAST REVIEW;
 1. QUEST HOUSE NOT ON SANITARY RISER DIAGRAM (2ND
 REQUEST)
 2. WATER SEVICE ONE METER OR TWO SHOW ON PLANS. IF
 ONE METER A BACKFLOW PREVENTER IS REQUIRED. (2ND
 REQUEST)
 3. OK
 4.THERMAL EXPANTION CONTROL REQUIRED ON WATER HEATERS
 IF BACKFLOW PREVENTOR IS INSTALLED (2ND REQUEST)

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-26 Cont ID  
Sent By jleech Date 2006-07-26 Time 12:59 Rev Time 0.00
Received By jleech Date 2006-07-26 Time 12:59 Sent To Z
Notes
2006-07-26 00:00:00DENIED;
 1.PLEASE INCLUDE GUEST HOUSE ON THE
 PLUMBING SANITARY RISER DIAGRAM.
 2.IS WATER SERVICE OFF ONE METER? IF SO
 A BACKFLOW PREVENTOR IS REQUIRED TO BE
 INSTALLED AT WATER METER.
 3.IS WATER HEATER IN MAIN HOUSE THE HOT
 WATER SUPPY FOR THE GUEST HOUSE? IF SO
 PLEASE SHOW ON PLAN THE DISTANCE FROM
 WATER HEATER TO LAST FIXTURE IN GUEST
 HOUSE. IF 100' A METHOD OF MAINTAINING
 THE TEMPERATURE IN ACCORDANCE WITH
 CHAPTER 13 OF THE FBC-2004.
 4.IF A BACKFLOW IS INSTALLED IN THE
 WATER SYSTEM SYSTEM THEN A MEANS OF
 THERMAL EXPANSION SHELL BE REQUIRED
 PLEASE SHOW ON DRAWINGS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status N Date 2007-01-29 Cont ID  
Sent By astelly Date 2007-01-29 Time 13:36 Rev Time 0.00
Received By astelly Date 2007-01-29 Time 13:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2006-10-23 Cont ID  
Sent By astelly Date 2006-10-23 Time 08:57 Rev Time 0.00
Received By astelly Date 2006-10-23 Time 08:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2006-08-04 Cont ID  
Sent By astelly Date 2006-08-04 Time 14:16 Rev Time 0.00
Received By astelly Date 2006-08-03 Time 10:51 Sent To M
Notes
2006-08-04 00:00:00THE FOLLOWING RECOMMENDATIONS ARE
 STRONGLY ADVISED FOR THE IMPROVEMENT OF
 THE ARCHITECTURE AND THE INTERIOR
 ENVIRONMENT.
  
 MAIN HOUSE
 ALL ELEVATIONS:
 1.MAINTAIN THE SAME WINDOW PROPORTIONS
 (3'X5') IN ALL ROOMS EXCEPT KITCHEN AND
 BATHS.
  
 FRONT ELEVATION:
 1.FLATTEN OR REMOVE ARCHES AT PORCH IN
 ORDER TO FULLY REVEAL WINDOWS.
 2. PROVIDE A BASE AND CAPITAL FOR THE
 COLUMNS.
  
 INTERIOR LIVING ENVIRONMENTS:
 1. ADD WINDOW TO LEFT ELEVATION AT
 BEDROOM #1 TO PROVIDE CROSS VENTILLATION
 AND IMPROVE THE AESTHETICS OF THELEFT
 FACADE.
 2. EITHER CENTER THE WINDOW IN THE WALL
 FOR BEDROOM #2 OR ADD AN ADDITIONAL
 WINDOW FOR IMPROVED LIGHT AND
 VENTILLATION.
 3. ADD WINDOW IN MASTER BEDROOM AT RIGHT
 ELEVATION TO PROVIDE CROSS VENTILLATION
 ANDIMPROVE THE AESTHETICS OF THE RIGHT
 FACADE.
 4. CONSIDER REDUCING ROOF PITCH TO 3:12
 TO IMPROVE THE MASSING OF THE HOUSE.
  
 GUEST HOUSE
 1. CENTER WINDOW IN BEDROOM #1 TO
 IMPROVE FRONT ELEVATION.
 2. ADD AN ADDITIONAL WINDOW IN THE
 LIVING ROOM AT THE FRONT ELEVATION TO
 IMPROVE FRONT FACADE.
 3. ADD ADDITIONAL WINDOW IN LIVING ROOM
 AT LEFT ELEVATION TO IMPROVE LEFT
 FACADE.
 4. ADD WINDOWS TO REAR ELEVATION. A
 BLANK FACADE IS UNACCEPTABLE.
 5. CHANGE WINDOW IN BEDROOM #1 TO A
 SINGLE UNIT IN FAVOR OF ADDING WINDOWS
 AT FRONT AND LEFT ELEVATIONS.
 6. MAINTAIN WINDOW PROPORTIONS THROUGHT
 THE HOUSE WHENEVER IT'S POSSIBLE.
  
 PLEASE SCHEDULE A MEETING WITH AMY
 STELLY IN THE URBAN DESIGN DIVISION TO
 DISCUSS THE ARCHITECTURE. 822-1440
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-27 Cont ID  
Sent By mmclean Date 2006-07-27 Time 14:30 Rev Time 0.00
Received By mmclean Date 2006-07-27 Time 14:30 Sent To M
Notes
2006-07-27 00:00:00DENIED,
 1. THE PROPOSED WALKWAY & DRIVEWAY WILL
 EXCEED THE LANDSCAPE REQUIREMENTS.
 PLEASE PROVIDE THE DIMENSION OF THE
 PROPOSED WALKWAY.CAN HAVE A TOTAL OF
 12.5SQ FT OF CONCRETE WITHIN THE FRONT
 SETBACK (THIS WILL INCLUDE DRIVEWAY &
 WALKWAY).
  
 NOTE:MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
  
 2. MUST PROVIDE ADDITIONAL PARKING FOR
 THE PROPOSED GUEST HOUSE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720