| Plan Review Stops For Permit 06071370 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2007-02-20 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2007-02-20 |
Time |
09:19 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2007-02-20 |
Time |
09:19 |
Sent To |
|
|
| Notes |
| 2007-02-20 09:20:36 | SITE ADDRESS IS CORRECT.SINGLE HOUSE IS NOT PART OF THE | | | MERRY PL DEVELOPMENT. | | | | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | OFFICE:822-1239 | | | FAX: 822-1249 | | | E-MAIL:[email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-02-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2007-02-16 |
Time |
18:55 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2007-02-16 |
Time |
18:31 |
Sent To |
|
|
| Notes |
| 2007-02-16 18:56:17 | BUILDING REVIEWCHECKLIST: | | | | | | 1- NEED TO PASS ALL THE OTHER TRADES: MECHANICAL AND | | | PLUMBING. SEE PLAN REVIEWERS COMMENTS. | | | | | | 2- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS. | | | NOTE: THERE IS NOT FL240. NEED TO PROVIDE ANOTHER | | | PRODUCT APPROVAL.ALSO, PROVIDE A COMPLETE | | | INSTALLATION SCHEDULE. SEE ATTACHED SAMPLE.COMPLETE | | | ALL INFORMATIONOR PROVIDE ALL THE REQUIRED | | | INFORMATION IN ANOTHER FORMAT THAT WILL PROVIDE ALL | | | REQUIRED INFORMATION FOR PLAN REVIEW. | | | | | | 3- MISSINGGARAGE DOOR PRODUCT APPROVAL.AND, | | | DESIGNER OF RECORD TO APPROVE IT IN WRITTING AS | | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. | | | | | | 4- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC. | | | R401.3 2004 FLORIDA RESIDENTIAL CODE. | | | | | | 5- MISSING NOTICE OF COMMENCEMENT. | | | | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-10-31 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-10-30 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-10-31 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2006-10-31 11:51:55 | DENIED | | | | | | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF | | | THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 5.PRODUCT APPROVALS REQUIRED FOR LINTELS. | | | | | | 6.INCORRECT STATE PRODUCT APPROVAL PAGES SUBMITTED | | | FOR OWENS CORNING AND THERMA TRU IS MISSING STATE | | | PRODUCT APPROVAL. | | | | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A STATE PRODUCT APPROVAL | | | SHEETS THAT LISTS THE PRODUCT IDENTITY | | | NUMBER FROM THE STATE. IF THE PRODUCT | | | DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT | | | AN APPLICATION FOR LOCAL PRODUCT | | | APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72. SEE ATTACHMENT. | | | WWW.FLORIDABUILDING.ORG | | | | | | 8.SUBMIT TWO SETS OF TRUSS DRAWINGS | | | FOR REVIEW PER 2004 FBC R-802.10.1 | | | TRUSS DRAWING REQUIRED TO BE APPROVED | | | PRIOR TO INSTALLATION. | | | | | | 9.ENTRY SECTION, SHOW METHOD OF | | | ATTACHEMENT OF HEADERS TO COLUMN. | | | | | | 10.R401.3 DRAINAGE. | | | SURFACE DRAINAGE SHALL BE DIVERTED TO A | | | STORM SEWER CONVEYANCE OR OTHER APPROVED | | | POINT OF COLLECTION SO AS TO NOT CREATE | | | A HAZARD. LOTS SHALL BE GRADED SO AS TO | | | DRAIN SURFACE WATER AWAY FROM FOUNDATION | | | WALLS. THE GRADE AWAY FROM FOUNDATION | | | WALLS SHALL FALL A MINIMUM OF 6 INCHES | | | WITHIN THE FIRST 10 FEET. | | | | | | NEW COMMENT: | | | REAR COVERED PORCH IS IN DIFFERENT LOCATIONS ON PLANS. | | | PLEASE SHOW ONLY AT ONE LOCATION ON PLANS AND SURVEY. | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. SUBMIT ONE COPY OF | | | OLD PAGES FOR REFERENCE . A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET | | | OR SPECIFICATION PAGE WHERE THE CHANGES | | | CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | CONSTRUCTION SERVICES DEPARTMENT | | | BUILDING PLANS EXAMINER | | | 561-805-6672 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-08-08 |
|
|
Cont ID |
|
| Sent By |
astelly |
Date |
2006-08-08 |
Time |
09:09 |
Rev Time |
2.66 |
| Received By |
alange |
Date |
2006-08-08 |
Time |
09:09 |
Sent To |
|
|
| Notes |
| 2006-08-08 00:00:00 | DENIED | | | | | | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF | | | THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 2.HAND DRAWN CHANGES NOT PERMITTED ON | | | PLANS. | | | | | | 3.SOILS REPORTS SUBMITTED ARE NOT | | | ORIGONAL SIGNED AND SEALED DOCUMENTS. | | | SUBMIT TWO ORIGONALS. | | | | | | 4.SIGN OWNER/AGENT ON ENERGY CALCS PER | | | 2004 FBC. | | | | | | 5.PRODUCT APPROVALS REQUIRED FOR 8FT. | | | OVERHEAD DOOR AND LINTELS. | | | | | | 6.ALL PRODUCT APPROVALS SUBMITTED WITH | | | QUALITY ASSURANCE SHALL HAVE THE | | | FOLLOWING STATE APPROVAL ATTACHED. | | | | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A STATE PRODUCT APPROVAL | | | SHEETS THAT LISTS THE PRODUCT IDENTITY | | | NUMBER FROM THE STATE. IF THE PRODUCT | | | DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT | | | AN APPLICATION FOR LOCAL PRODUCT | | | APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72. SEE ATTACHMENT. | | | WWW.FLORIDABUILDING.ORG | | | | | | 7.THOSE PRODUCT APPROVALS WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL.WPB | | | AMENDMENT TO FBC 106.3.3. | | | | | | 8.SUBMIT TWO SETS OF TRUSS DRAWINGS | | | FOR REVIEW PER 2004 FBC R-802.10.1 | | | TRUSS DRAWING REQUIRED TO BE APPROVED | | | PRIOR TO INSTALLATION. | | | | | | 9.ENTRY SECTION, SHOW METHOD OF | | | ATTACHEMENT OF HEADERS TO COLUMN. | | | | | | 10.R401.3 DRAINAGE. | | | SURFACE DRAINAGE SHALL BE DIVERTED TO A | | | STORM SEWER CONVEYANCE OR OTHER APPROVED | | | POINT OF COLLECTION SO AS TO NOT CREATE | | | A HAZARD. LOTS SHALL BE GRADED SO AS TO | | | DRAIN SURFACE WATER AWAY FROM FOUNDATION | | | WALLS. THE GRADE AWAY FROM FOUNDATION | | | WALLS SHALL FALL A MINIMUM OF 6 INCHES | | | WITHIN THE FIRST 10 FEET. | | | | | | 11.WIND DESIGN CRITERIA SHOULD BE ASCE | | | 7-02. | | | | | | 12.CODE SECTIONS USED ARE STILL UNDER | | | THE 2001 FBC CODE SECTIONS USED SHOULD | | | RERFLECT THE 2004 FLORIDA RESIDENTIAL | | | CODE. | | | SEE FOUNDATION AND CONCRETE NOTES #18 | | | AND #22 ... ATTIC VENTILATION IS R-806 | | | AND SOIL BEARING IS R-401.4.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. SUBMIT ONE COPY OF | | | OLD PAGES FOR REFERENCE . A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET | | | OR SPECIFICATION PAGE WHERE THE CHANGES | | | CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | CONSTRUCTION SERVICES DEPARTMENT | | | BUILDING PLANS EXAMINER | | | 561-805-6672 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2007-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-01-31 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-01-31 |
Time |
13:08 |
Sent To |
M |
|
| Notes |
| 2007-01-31 13:08:24 | CATV AND PHONES ARE NOT INCLUDED AND WILL BE REQUIRED | | | TO BE UNDER SEPARATE PERMIT PLANS AND FEES AT A LATER | | | DATE BEFORE INSTALLATION. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-10-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-23 |
Time |
19:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-23 |
Time |
19:25 |
Sent To |
M |
|
| Notes |
| 2006-10-23 19:29:14 | ** UNSAT 2ND REVIEW ** | | | | | | ** PLEASE SEE MANY NOTES FROM PREVIOUS REVIEW ARE NOT | | | ADDRESSED AND CANE NOT BE REVIEWED AT THIS TIME FOR | | | CODE COMPLIANCE. | | | | | | | | | | | | 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS FOR | | | REWVIEW. PLEASE SEE SOME SHEETS HAVEOTHER SHEETS AND | | | INFORMATION TAPED ONTO PLANS?? | | | PLEASE SEE SOME SETS CONTAIN AND HOUSE PLANS, YET NO | | | GUEST HOUSE PLANS, AND OTHER SETS CONTAIN GUEST HOUSE | | | BUT NO MAIN HOUSE?? | | | | | | 2) NOTE: PLEASE SEENOTES 1,2,3,5,6,7,8,9,10 FROM | | | PREVIOUS REVIEW. | | | FBC 106.3.5.4(8), | | | PLEASE ALSO SEE FS 553.80(2)(B) WITH RESPECT TO REPEAT | | | COMMENTS FOR CODE COMPLIANCE. | | | THIS IS ONLY ANOTICE GIVEN AT THIS TIME. | | | | | | ** PLEASE SEE NEC 2002 FOR CODE. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-07-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-26 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-26 |
Time |
11:51 |
Sent To |
Z |
|
| Notes |
| 2006-07-26 00:00:00 | *******UNSAT ************ | | | | | | 1) NOTE: PLEASE SEE MISSING RECEPT FOR | | | WHAT APPEARS TO BE MORE THAN 2 FT OF | | | WALL IN MAIN HOUSE. | | | | | | 2) NOTE: PLEASE COMPLETE PANEL SCHEDULES | | | TO INDICATE ALL SPECIFYOED AREAS AND | | | RMS. IE; LIV RM TLS, DINING RECEPTS , | | | BEDRM #1 RECEPTS ETC. | | | 408.4,240.4,310.16 | | | | | | 3) NOTE: PLEASE SEE PANEL FOR MAIN HOUSE | | | IS NOT ON PLANS., 110.26,240.24 ETC | | | PLEASE ALSO SHOW SERVICE AND LOCATION OF | | | SERVICE. PLEASE SEE NOTES FOR GUEST | | | HOUSE ALSO AS MAINS DO NOT APPEAR TO BE | | | GROUPED ETC. | | | PLEASE SEE 230.70,230.72,225.31-225.39 | | | PLEASE SEE MISSING DISCONNECTING MEANS | | | AT GUEST HOUSE. RISER SHOWS A DISCONNECT | | | HOWEVER IT IS NOT SHOWN ON PLANS WHERE | | | THIS ITS. | | | | | | 4) NOTE: PLEASE SEE MISSING GROUNDING | | | ELECTRODE SYSTEM AT GUEST HOUSE PER | | | 250.32, 250.50 | | | | | | 5) NOTE: PLEASE CORRELATE PLANS AS GUEST | | | HOUSE SHOWS 60A PANEL, AND RISER SHOWS | | | 100A ALONG WITH PANEL SCHEDULE. | | | PLEASE SEE LOAD SHOWN EXCEEDS THE RATING | | | OF THE 60A PANEL. | | | 2404.310.16 | | | 106.1.2 FBC | | | | | | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | | | | 7) NOTE: PLEASE VERIFY THE 60A OCP SHOWN | | | FO THE 7.5KW HEAT IN GUEST HOUSE. | | | | | | 8) NOTE: PLEASE SEE DINING RM SHALL BE | | | ON ONE OR MORE OF THE SMALL APPLIANCE | | | CIRCUITS. PLEASE SEE IF DINING IS ON | | | THEIR OWN, PLEASE SEE 210.52B1,210.11C1 | | | AND 220.16 AS THE THESE SHALL BE FIGURED | | | AS 1500 VA. | | | | | | 9) NOTE: PLEASE SEE NFPA-72 11.8.3 FOR | | | SD'S LOCATED WITHIN 20' OF COOKING | | | EQUIPMENT. | | | | | | 10) NOTE: PLEASE CLARIFY IF THEIR ARE | | | GONG TO BE LAUNDRY FACILITIES IN GUEST | | | HOUSE.? | | | | | | ** PLEASE SEE ANY POSSIBLE ZONING | | | COMMENTS WHICH MAY AFFECT PLANS. | | | | | | ** BEFORE AND WHEN RESUBMITTING PLANS, | | | PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS FROM SETS AND ONLY | | | INSERT NEW REVISED SHEETS INTO TWO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | SUBMIT ONE COPY OF THE OLD/VOIDED SHEETS | | | FOR REFERENCE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-03-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-23 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-23 |
Time |
10:22 |
Sent To |
M |
|
| Notes |
| 2007-03-23 10:23:02 | TO "M" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-01-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-29 |
Time |
08:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-29 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2007-01-29 14:32:23 | TO "DPALMER" DESK/RESUB--EXPEDITED PERMIT-- |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-01-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-24 |
Time |
10:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-24 |
Time |
10:57 |
Sent To |
Z |
|
| Notes |
| 2007-01-24 10:58:42 | TO 5TH FL ZONING IN-BOX--EXPEDITED PERMIT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-10-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-23 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-23 |
Time |
15:32 |
Sent To |
E |
|
| Notes |
| 2006-10-23 15:32:30 | TO "DPALMER"DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-10-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-10-14 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-10-14 |
Time |
16:48 |
Sent To |
B |
|
| Notes |
| 2006-10-14 16:48:22 | TO "ALANGE" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-09-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-29 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-29 |
Time |
16:56 |
Sent To |
Z |
|
| Notes |
| 2006-09-29 00:00:00 | TO "Z" BOX/RESUB--EXPEDITED PERMIT-- |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-08-08 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-08-08 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-07-25 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2006-07-25 00:00:00 | TO "SFR" "Z"--EXPEDITED PERMIT |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2007-03-28 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-03-28 |
Time |
11:53 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-03-28 |
Time |
11:53 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2007-01-31 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-01-31 |
Time |
15:44 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2007-01-31 |
Time |
15:44 |
Sent To |
P |
|
| Notes |
| 2007-01-31 16:12:22 | *** DENIED *** | | | | | | 1) AS NOTED IN LAST REVIEW 10-24-07 NOTE #2, MECHANICAL | | | PLANS FOR MAIN HOUSE AND COTTAGE, NEED JOB ADDRESS ON | | | THEM. | | | | | | 2) AS NOTED IN LAST REVIEW 10-24-07 NOTE #3, THE A/C | | | SYSTEM FOR THE MAIN HOUSE IS OVER-SIZED, THE MAIN HOUSE | | | MANUAL J CALCULATIONS ARE CALLING FOR 19,783 SENSIBLE | | | BTU'S, THE MECHANICAL PLANS ARE CALLING FOR 33,322 | | | SENSIBLE BTU'S, THE PLANS CAN ONLY CALL FOR 20% MORE | | | THAN THE MANUAL J CAL'S, PER 2004 FBC 13-607.1.ABC.1.1, | | | PLEASE CORRECT. | | | | | | 3) AS NOTED IN LAST REVIEW 10-24-07 NOTE #4. SEE MAIN | | | HOUSE MECH. PLAN, 12"RETURN AIR TRANSFER DUCT TO | | | MASTER SUITE IS TO SMALL. BALANCED RETURN AIR MAY BE | | | ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE | | | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS | | | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR | | | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO | | | ACHIEVE PROPER RETURN AIR BALANCE. | | | (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET | | | THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR | | | EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY | | | ROOMS, | | | EXECPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL | | | BE INCLUDED. PER 2004 FBC/R M1602.4. | | | | | | 4) PLEASE SHOW ON MECHANICAL PLANS WERE THE CLOTHES | | | DRYER VENT WILL TERMINATE (VENT MAY NOT DISCHARGE NEAR | | | A/C CONDENSER UNIT). | | | | | | 5) SEE MECHANICAL PLANS TO MAIN HOUSE, WHITE-OUT MAY | | | NOT BE USED ON PLANS, AND DO NOT SUBMIT CHANGES IN PEN. | | | PLEASE MAKE COPY'S AFTER CHANGES HAVE BEEN MADE AND | | | SUBMIT COPY'S. | | | | | | 6) SEE ATTACHED NOTICE FS 553.80(2)(B) REGARDING FOUR | | | TIMES THE FEE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-10-24 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-10-24 |
Time |
13:34 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-10-24 |
Time |
13:34 |
Sent To |
P |
|
| Notes |
| 2006-10-24 13:41:13 | *** DENIED *** | | | 1) MECHANICAL PLANS NEED THE NAME AND SIGNATURE OF THE | | | DESIGN PERSON ON THEM, FOR MAIN HOUSE AND COTTAGE. ALL | | | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING | | | DATA SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE | | | FOR THE DESIGN. PER FBC 104.2.1 . | | | | | | 2) SEE MECHANICAL PLANS FOR MAIN HOUSE AND COTTAGE, | | | NEED JOB ADDRESS ON THEM. | | | | | | 3) THE MAIN HOUSE MANUAL J CALCULATIONS ARE CALLING FOR | | | 14,200 TOTAL SENSIBLE BTU'S, THE MECH. PLANS ARE | | | CALLING FOR 33,322 TOTAL SENSIBLE BTU'S, THE PLANS CAN | | | ONLY CALL FOR 20% MORE THAN THE MANUAL J CAL'S, PRE | | | 2004 FBC 13-607.1.ABC.1.1, PLEASE CORRECT. | | | | | | 4) SEE MAIN HOUSE MECH. PLAN, 10"RETURN AIR TRANSFER | | | DUCT TO MASTER SUITE IS TO SMALL, PLEASE CORRECT, SEE | | | NOTE #5. | | | | | | 5)BALANCED RETURN AIR. | | | THIS MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. | | | (B)TRANSFER GRILLES SHALL USE 50 | | | SQUARE INCHES (OF GRILLE AREA) TO 100 | | | CFM (OF SUPPLY AIR) FOR SIZING | | | THROUGH-THE-WALL TRANSFER GRILLES AND | | | USING AN UNRESTRICTED 1-INCH | | | UNDERCUTTING OF DOORS TO ACHIEVE PROPER | | | RETURN AIR BALANCE | | | (C)HABITABLE ROOMS ONLY SHALL BE | | | REQUIRED TO MEET THESE REQUIREMENTS FOR | | | PROPER BALANCED RETURN AIR EXCLUDING | | | BATHROOMS, CLOSETS, STORAGE ROOMS AND | | | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY | | | AIR INTO THE MASTER SUITE SHALL BE | | | INCLUDED. PER 2004 FBC/R M1602.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-08-07 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-08-07 |
Time |
11:38 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2006-08-07 |
Time |
11:38 |
Sent To |
B |
|
| Notes |
| 2006-08-07 00:00:00 | *** DENIED *** | | | 1) MECHANICAL PLANS HAVE TO MUCH FLOOR | | | PLAN DETAIL ON THEM AND ARE DIFFICULT TO | | | READ. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY. PER 2004 FBC 106.1.1 | | | . | | | | | | 2) THE MECHANICAL PLANS NEED TO BE | | | SEALED BY THE ENGINEER AS HIS NAME AND | | | INFORMATION IS IN THE TITLE BLOCK, PER | | | FAC 61G15-23.002 (LOOK UP PLAGIARISM). | | | | | | 3) ONE COPY OF THE ENERGY CALCULATIONS | | | WERE SIGNED IN PENCIL BY THE PREPARER, | | | DOCUMENTS MUST BE SIGNED IN PEN. AND | | | SUBMIT TWO COPYS OF THE E-CAL'S FOR THE | | | GUEST HOUSE. | | | | | | 4) ENERGY CALCULATIONS NEED TO BE SIGNED | | | BY OWNER/AGENT ALSO, PER 2004 FBC | | | 13-600.3.ABC.2 . | | | | | | 5) SHOW A EQUIPMENT LISTING WITH ALL | | | PERTINENT INFORMATION ON THE MECHANICAL | | | PLANS. | | | | | | 6) SHOW CFM'S AT EACH SUPPLY AIR GRILL. | | | | | | 7) SHOW LOCATION OF CLOTHES DRYER VENT TERMINATION, ON | | | MECHANICAL PLANS. | | | | | | 8) ALL RETURN AIR TRANSFER DUCTS ARE TO | | | SMALL, SEE NOTE #9. | | | | | | 9) BALANCED RETURN AIR. | | | THIS MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. | | | (B)TRANSFER GRILLES SHALL USE 50 | | | SQUARE INCHES (OF GRILLE AREA) TO 100 | | | CFM (OF SUPPLY AIR) FOR SIZING | | | THROUGH-THE-WALL TRANSFER GRILLES AND | | | USING AN UNRESTRICTED 1-INCH | | | UNDERCUTTING OF DOORS TO ACHIEVE PROPER | | | RETURN AIR BALANCE | | | (C)HABITABLE ROOMS ONLY SHALL BE | | | REQUIRED TO MEET THESE REQUIREMENTS FOR | | | PROPER BALANCED RETURN AIR EXCLUDING | | | BATHROOMS, CLOSETS, STORAGE ROOMS AND | | | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY | | | AIR INTO THE MASTER SUITE SHALL BE | | | INCLUDED. PER 2004 FBC/R M1602.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2007-03-29 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-03-29 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-03-29 |
Time |
07:49 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2007-02-12 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-02-12 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-02-12 |
Time |
08:14 |
Sent To |
B |
|
| Notes |
| 2007-02-12 08:22:23 | DENIED; | | | 1. WATER HEATER REQUIRED TO HAVE THERMAL EXPANSION | | | PROTECTION, SECTION 607.3. SHOW ON PLANS. | | | 2. ADD NOTE TO PLANS THAT A REDUCED PRESSURE PRINCIPAL | | | BACKFLOW PREVENTOR IS REQUIRED AT THE WATER METER. | | | 3. AN AUTOMATIC CLOTHES WASHER HOOKUP IS REQUIRED IN | | | THE GUEST HOUSE. SEE TABLE 403.1 (7 R3) UNDER OTHER. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-10-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-10-26 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-10-26 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2006-10-26 12:12:41 | DENIED; | | | COMMENTS FROM FIRST REVIEW; | | | 1. NO THERE IS NO RISER DIAGRAM ON NEW SET OF PLANS. | | | 2.SEPORATE WATER SERVICES AND METERS; PLEASE ADD A NOTE | | | TO PLANS; | | | SEPARATE WATER SERVICES AND METERS. | | | 3.WATER HEATERS UNKNOWN ONLY GUEST HOUSE FLOOR PLAN | | | SHOWN ON PLANS. | | | 4. OK. | | | NEW COMMENTS; | | | PLANS ARE NOT COMPLETE. NO SANITARY RISER DIAGRAM. NO | | | FLOOR PLAN FOR MAIN HOUSE. | | | UNABLE TO DO A PLUMBING PLAN REVIEW. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-07-26 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-07-26 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-07-26 |
Time |
14:28 |
Sent To |
Z |
|
| Notes |
| 2006-07-26 00:00:00 | DENIED; | | | 1.PLEASE INCLUDE GUEST HOUSE ON THE | | | PLUMBING SANITARY RISER DIAGRAM. | | | 2.IS WATER SERVICE TO BOTH BUILDINGS | | | FROM THE SAME METER IF SO A BACKFLOW | | | PREVENTER IS REQUIRED TO BE INSTALLED AT | | | THE WATER METER BY THE UTILITY | | | DEPARTMENT. | | | 3.IS WATER HEATER IN MAIN HOUSE THE HOT | | | WATER SUPPLY FOR THE BACK HOUSE? IF SO | | | PLEASE SHOW ON THE PLANS THE DISTANCE | | | FROM THE W/H TO THE LAST FIXTURE. IF | | | 100' A METHOD OF MAINTAINING THE | | | TEMPERATURE IN ACCORDANC WITH CHAPTER 13 | | | OF THE FBC-2004 BUILDING CODE MUST BE | | | INSTALLED. | | | 4.IF A BACKFLOW IS REQUIRED THEN A MEANS | | | OF THERMAL EXPANSION SHELL BE REQUIRED. | | | SEE SECTION 607.3. SHOW ON DRAWINGS. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
N |
Date |
2007-01-29 |
|
|
Cont ID |
|
| Sent By |
astelly |
Date |
2007-01-29 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
astelly |
Date |
2007-01-29 |
Time |
13:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2006-10-23 |
|
|
Cont ID |
|
| Sent By |
astelly |
Date |
2006-10-23 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
astelly |
Date |
2006-10-23 |
Time |
08:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2006-08-04 |
|
|
Cont ID |
|
| Sent By |
astelly |
Date |
2006-08-04 |
Time |
14:54 |
Rev Time |
0.00 |
| Received By |
astelly |
Date |
2006-08-04 |
Time |
14:54 |
Sent To |
M |
|
| Notes |
| 2006-08-04 00:00:00 | THE FOLLOWING RECOMMENDATIONS ARE | | | STRONGLY ADVISED FOR THE IMPROVEMENT OF | | | THE ARCHITECTURE AND THE INTERIOR | | | ENVIRONMENT. | | | | | | MAIN HOUSE | | | ALL ELEVATIONS: | | | 1.MAINTAIN THE SAME WINDOW PROPORTIONS | | | (3'X5') IN ALL ROOMS EXCEPT KITCHEN AND | | | BATHS. | | | 2.MAINTAIN CONSISTENCY WITH WINDOW | | | CASINGS AND SILLS WITH ALL ELEVATIONS. | | | | | | FRONT ELEVATION: | | | 1.FLATTEN OR REMOVE ARCHES AT PORCH IN | | | ORDER TO FULLY REVEAL WINDOWS. | | | 2. PROVIDE A BASE AND CAPITAL FOR THE | | | COLUMNS. | | | | | | INTERIOR LIVING ENVIRONMENTS: | | | 1. ADD WINDOW TO LEFT ELEVATION AT | | | BEDROOM #1 TO PROVIDE CROSS VENTILLATION | | | AND IMPROVE THE AESTHETICS OF THELEFT | | | FACADE. MOVE COVERED PORCH TO THE REAR | | | OF THE MASTER BEDROOM AND CHANGE THE | | | DOOR IN BEDROOM #1 TO A WINDOW. OR, | | | EXTEND THE COVERED PORCH TO THE FULL | | | LENGTH OF THE REAR FACADE AND MAINTAIN | | | THE DOOR IN BEDROOM #1. | | | 2. CENTER THE WINDOW IN THE WALL | | | FOR BEDROOM #2. | | | 3. ADD WINDOW IN MASTER BEDROOM AT RIGHT | | | ELEVATION TO PROVIDE CROSS VENTILLATION | | | ANDIMPROVE THE AESTHETICS OF THE RIGHT | | | FACADE. | | | 4. CONSIDER REDUCING ROOF PITCH TO 3:12 | | | TO IMPROVE THE MASSING OF THE HOUSE. | | | | | | GUEST HOUSE | | | 1. CENTER WINDOW IN BEDROOM #1 TO | | | IMPROVE FRONT ELEVATION. | | | 2. ADD AN ADDITIONAL WINDOW IN THE | | | LIVING ROOM AT THE FRONT ELEVATION TO | | | IMPROVE FRONT FACADE. | | | 3. ADD ADDITIONAL WINDOW IN LIVING ROOM | | | AT LEFT ELEVATION TO IMPROVE LEFT | | | FACADE. | | | 4. ADD WINDOWS TO REAR ELEVATION. A | | | BLANK FACADE IS UNACCEPTABLE. | | | 5. CHANGE WINDOW IN BEDROOM #1 TO A | | | SINGLE UNIT IN FAVOR OF ADDING WINDOWS | | | AT FRONT AND LEFT ELEVATIONS. | | | 6. MAINTAIN WINDOW PROPORTIONS THROUGHT | | | THE HOUSE WHENEVER IT'S POSSIBLE. | | | | | | INTERIOR ENVIRONMENT: | | | 1. THE DINETTE SPACE IS COMPROMISED BY | | | HAVING 3 OPENNINGS AND 3 CIRCULATION | | | PATHS CROSS THE AREA. | | | | | | PLEASE SCHEDULE A MEETING WITH AMY | | | STELLY IN THE URBAN DESIGN DIVISION TO | | | DISCUSS THE ARCHITECTURE. 822-1440 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-07-27 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-07-27 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-07-27 |
Time |
14:47 |
Sent To |
M |
|
| Notes |
| 2006-07-27 00:00:00 | DENIED, | | | 1. THE PROPOSED WALKWAY & DRIVEWAY WILL | | | EXCEED THE LANDSCAPE REQUIREMENTS. | | | PLEASE PROVIDE THE DIMENSION OF THE | | | PROPOSED WALKWAY.CAN HAVE A TOTAL OF | | | 12.5SQ FT OF CONCRETE WITHIN THE FRONT | | | SETBACK (THIS WILL INCLUDE DRIVEWAY & | | | WALKWAY). | | | | | | NOTE:MUST MAINTAIN 1000SQ FT OR 75% OF | | | LANDSCAPE, WHICHEVER IS LESS WITHIN THE | | | FIRST 25FT FRONT SETBACK. | | | | | | 2. MUST PROVIDE ADDITIONAL PARKING FOR | | | THE PROPOSED GUEST HOUSE. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720+ |
|
|