Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-10-24 Cont ID  
Sent By shill Date 2007-10-24 Time 11:38 Rev Time 0.00
Received By shill Date 2007-10-24 Time 11:38 Sent To  
Notes
2007-10-24 12:11:22****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 **NEW PLANS DRAWN BY NEW DESIGNER**
  
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY PRIOR TO PERMIT ISSUANCE.
 THE PLANS MUST BE STAMPED AND THE
 RECEIPT ATTACHED TO THE APPLICATION.
 561-233-5025
  
 3.)THE DESCRIPTION FOR 6X6 10/10 WWM HAS CHANGED TO
 6X6 W1.4XW1.4, SEE FBC R 506.2.4 EXCEPTION 2.THIS NOW
 REFERS TO CROSS SECTIONAL AREA RATHER THAN GAUGE;
 PLEASE REVISE FOUNDATION PLAN SHEET 4.
  
 4.)FOR THE SCREEN LANAI, EITHER PROVIDE ALL
 SPECIFICATIONS FOR THE SCREEN ENCLOSURE OR A SEPARATE
 PERMIT WILL BE REQUIRED.
  
 5.)THE TYPICAL STAIR DETAIL REFERS TO FBC1007.5.THE
 CORRECT CODE REFERENCES WILL BE FOUND IN FBC
 RESIDENTIAL.CHECK ALL CODE REFERENCES.
  
 6.)SHEET 2, WIND INFO, ITEM 6, INTERNAL PRESSURE
 COEFFICIENT IS "CH".WHAT IS THIS?
  
 7.)ROOF TRUSS PLANS WILL BE REQUIRED, REVIEWED BY
 ENGINEER OF RECORD, PRIOR TO INSTALLATION
 (INFORMATIONAL), FBC R 802.1.6.1.
  
 8.)SHOW GUARDRAIL AND STAIR RAIL HEIGHT, FBC R 311.5,
 312.STAIR RAIL HEIGHT IS SPECIFIED AS 32" OR 34", BUT
 DRAWN THE SAME HEIGHT AS THE GUARDRAIL, WHICH HAS A 34"
 MINIMUM HEIGHT REQUIREMENT.
  
 9.)SPECIFY DESIGN CRITERIA FOR THE GUARDRAIL AT THE
 BALCONY, FBC312.
  
 10.)DOOR 2, GARAGE TO HOUSE, SHEET 3, IS REQUIRED TO
 MEET THE REQUIREMENTS OF FBC R13-603.1ABC.1 (INSULATED
 OR SOLID CORE) AND R309.1 (FIRE RATING REQUIREMENTS).
  
 11.)SHOW SEPARATION BETWEEN GARAGE AND DWELLING AS
 REQUIRED BY FBC R 309.2.
  
 12.)SHEATHING FASTENING ON SHEET 5 IS IN CONFLICT
 WITH FBC TABLE 2304.9.1; 4" REQUIRED AT EDGE STRIP (NOT
 FOR GABLES ONLY).
  
 13.)SHEET 5 INCLUDES A FRAMING DETAIL FOR OPENINGS.
 AS THIS IS CBS CONSTRUCTION, WHERE IS THIS DETAIL
 APPLICABLE?PLEASE USE DETAIL REFERENCE MARKERS ON THE
 FLOOR PLAN.
  
 14.)PLEASE NOTE THAT NO ATTIC STORAGE WILL BE
 ALLOWED, SHEET 7 OR REVISE BOTTOM CHORD LIVE LOAD,
 FBC3.
  
 15.)SHEET 7, TRUSS ANCHOR SCHEDULE IS ILLEGIBLE.
  
 16.)SHEET 2, STAIR SECTTION, IS THE NOSING INCLUDED
 IN THE 10" TREAD, OR IS THIS A 10" TREAD AND AN
 ADDITIONAL 1" NOSING?FBC R 311.
  
 17.)SHEET 2, NOTE A, REVISE CODE REFERENCE AS FBC1007
 TO APPLICABLE RESIDENTIAL CODE SECTION.
  
 18.)PROVIDE A SOILS INVESTIGATION REPORT, TWO
 ORIGINALS.
  
 19.)PROVIDE COOLING LOAD CALCS FBC 13-607.1.ABC.1.
  
 20.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 21.)THE VALUE OF THIS PROJECT HAS BEEN ADJUSTED BASED
 SQUARE FOOT AREA USING THE ICC BUILDING VALUATION
 TABLES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-02-27 Cont ID  
Sent By shill Date 2007-02-27 Time 08:20 Rev Time 0.00
Received By shill Date 2007-02-27 Time 08:02 Sent To  
Notes
2007-02-27 08:23:34****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 PLAN CHECK #05041961
  
 COMMENTS FROM THE PREVIOUS REVIEWS;
 NUMBERING TO REMAIN THE SAME FOR
 CONSISTENCY.NOTE THAT CODE REFERENCE
 NUMBERS HAVE CHANGED AS THE FIRST REVIEW
 WAS DONE ON FBC2001, SECOND AND THIRD REVIEWS ON
 FBC2004.
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY PRIOR TO PERMIT ISSUANCE.
 THE PLANS MUST BE STAMPED AND THE
 RECEIPT ATTACHED TO THE APPLICATION.
 561-233-5025
  
 3.-5.)ADDRESSED.
  
 6.)ENERGY CALCS REQUIRED, FBC11-101.2.
 SIGN THE OWNER/AGENT LINE OF THE ENERGY
 CALC, FBC11-103.1.2.
  
 7.-57.)ADDRESSED.
  
 58.)PRODUCT APPROVALS REQUIRED FOR COMPONENTS AND
 CLADDING.PRODUCT APPROVALS ARE TO BE APPROVED BY
 DESIGNER OF RECORD, FBC*106.3.3.
  
 NEW COMMENT
  
 59.)A4.0 SPECIFIES 16INCH BEAM, A6.0 SPECIFIES 20INCH
 CONCRETE BEAM.SUBMIT CALCULATIONS, FBC*106.1.2.
  
 60.)INFORMATIONAL ONLY; THE BLOCK WALL WILL REQUIRE A
 SEPARATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-06 Cont ID  
Sent By shill Date 2006-11-06 Time 13:42 Rev Time 0.00
Received By shill Date 2006-11-06 Time 13:42 Sent To  
Notes
2006-11-06 13:56:43****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 PLAN CHECK #05041961
  
 COMMENTS FROM THE PREVIOUS REVIEWS;
 NUMBERING TO REMAIN THE SAME FOR
 CONSISTENCY.NOTE THAT CODE REFERENCE
 NUMBERS HAVE CHANGED AS THE FIRST REVIEW
 WAS DONE ON FBC2001, SECOND AND THIRD REVIEWS ON
 FBC2004.
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY PRIOR TO PERMIT ISSUANCE.
 THE PLANS MUST BE STAMPED AND THE
 RECEIPT ATTACHED TO THE APPLICATION.
 561-233-5025
  
 3.-5.)ADDRESSED.
  
 6.)ENERGY CALCS REQUIRED, FBC11-101.2.
 SIGN THE OWNER/AGENT LINE OF THE ENERGY
 CALC, FBC11-103.1.2.
  
 7.)A9.0 IS NOT LEGIBLE.
 IT ALSO CONTAINS MANY INCORRECT CODE REFERENCES; FOR
 INSTANCE, BOCA (GOVERNING CODE IS FBC2004) AND
 ACI530.1-95 (USE CURRENT REFERENCES).CHECK ALL
 SPECIFICATIONS.
  
 8.-41.)ADDRESSED.
  
 42.)SHOW POSITIVE DRAINAGE FBC R401.3, FBC*109.3.10.
 THE TYPICAL WALL SECTION ON A8.0 SHOWS A SLOPE AWAY
 FROM THE BUILDING, BUT AT 5' AWAY FROM THE PROPERTY
 LINE DOESN'T THIS CAUSE THE WATER TO DUMP ONTO THE
 ADJACENT PARCEL?PLEASE ADDRESS DRAINAGE ON THE SITE
 PLAN.
  
 43-55.)ADDRESSED.
  
 NEW COMMENT:
  
 56.)DESIGN CRITERIA FOR TRUSSES IS NOT CLEAR.A9.0
 STATES 20PSF LIVE, 10PSF DEAD BOTTOM CHORD; A7.0 NOTE
 STATES "20PSF DEAD LOAD 10PSF".
  
 57.)A9.0 STILL SPECIFIES SHEATHING NAILING OF 6" ON
 EDGES, 8"IN THE FIELD.FLOOR SHEATHING NAILING IS IN
 CONFLICT WITH OTHERS SPECIFICATIONS ON THE PLAN.THE
 SHEET IS DIFFICULT TO READ.MAKE THIS SHEET LEGIBLE IF
 IT IS REQUIRED FOR CODE COMPLIANCE, AND CHECK THAT ALL
 NOTES ARE CODE COMPLIANT, CURRENT, REFERRING TO CURRENT
 GOVERNING CODE, AND SPECIFICATIONS ARE CONSISTENT WITH
 OTHER SPECIFICATIONS ON THE PLAN.
  
 58.)PRODUCT APPROVALS REQUIRED FOR COMPONENTS AND
 CLADDING.PRODUCT APPROVALS ARE TO BE APPROVED BY
 DESIGNER OF RECORD, FBC*106.3.3.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-08 Cont ID  
Sent By shill Date 2006-08-08 Time 17:04 Rev Time 0.00
Received By shill Date 2006-08-08 Time 12:27 Sent To  
Notes
2006-08-08 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 PLAN CHECK #05041961
  
 COMMENTS FROM THE PREVIOUS REVIEWS;
 NUMBERING TO REMAIN THE SAME FOR
 CONSISTENCY.NOTE THAT CODE REFERENCE
 NUMBERS HAVE CHANGED AS THE FIRST REVIEW
 WAS DONE ON FBC2001, SECOND REVIEW ON
 FBC2004.
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED, FS713.13.
  
 2.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY PRIOR TO PERMIT ISSUANCE.
 THE PLANS MUST BE STAMPED AND THE
 RECEIPT ATTACHED TO THE APPLICATION.
 561-233-5025
  
 3.-5.)ADDRESSED.
  
 6.)ENERGY CALCS REQUIRED, FBC11-101.2.
 SIGN THE OWNER/AGENT LINE OF THE ENERGY
 CALC, FBC11-103.1.2.
  
 THE FRAME WALLS AND THE FLOOR CEILING
 ASSEMBLY ARE NOT SHOWN.THERE ARE
 INTERIOR ADJACENT WALLS AND EXTERIOR
 FRAME WALLS.THE BLOCK WALL ON THE
 ENERGY CALC SHOWS 0 INSULATION;
 INSULATION REQUIRED BETWEEN CONDITIONED
 AND UNCONDITIONED SPACE, AND IN CONFLICT
 WITH THE PLAN.
  
 7.)A7.0, PROJECT DATA, IS NOT LEGIBLE.
 DESIGN PRESSURES ARE NOT LEGIBLE.
 FBC1606.1.7 IS NOT THE CORRECT CODE
 REFERENCE; PLEASE REMOVE.
  
 8.-19.)ADDRESSED.
  
 20.)WHAT IS THE CONSTRUCTION OF THE
 CABANA WALLS?IT DOES NOT APPEAR TO BE
 BLOCK.PROVIDE A DETAIL."STUCCO ON
 INSULATED WALLS" IS NOT A SUFFICIENT
 DETAIL.
  
 21.)SEE FBC R302.1,302.2, BAY WINDOW
 MUST BE OVER 3' FROM THE PROPERTY LINE.
 NOTE THAT THE ARCHITECT'S SITE PLAN
 SHOWS THE BAY WINDOW 3' FROM THE
 PROPERTY LINE.NO OPENINGS ALLOWED 3'
 FROM THE PROPERTY LINE.THIS IS IN
 CONFLICT WITH THE SURVEY WHICH SHOWS
 3.5' FROM THE PROPERTY LINE.3.5' IS
 ACCEPTABLE.
  
 22-26.)ADDRESSED.
  
 27.)REGARDING THE WALL BETWEEN THE
 GARAGE AND LAUNDRY AREA, FROM PREVIOUS
 CORRECTION LIST: THE FRAME WALL SHOWS
 "SOUND INSULATION", MUST HAVE R VALUE
 SPECIFIED FBC13-602.
  
 28.-41.)ADDRESSED.
  
 42.)SHOW POSITIVE DRAINAGE FBC R401.3,
 FBC*109.3.10.
  
 43-46.)ADDRESSED.
  
 46.)THE GARAGE BEAM DETAIL SHOWS EMPTY
 SPACE ABOVE THE BEAM.HOW WILL THIS BE
 STRUCTURALLY CONTINUOUS?
  
 47.)PROVIDE A DETAIL FOR THE EXTERIOR
 FRAME WALL.
  
 NOT ADDRESSED.
  
 NEW COMMENTS, 3RD REVIEW:
  
 48.)A7.0 REFERS TO ASCE7-98, CORRECT
 REFERENCE IS ASCE7-02, FBC35.
  
 49-53.) ADDRESSED.
  
 NEW COMMENT:
  
 54.)R403.1.4, EXTERIOR FOOTINGS TO BE
 12" BELOW GRADE.
  
 55.)TWO COPIES OF ALL DOCUMENTS
 REQUIRED.
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-09-20 Cont ID  
Sent By dpalmer Date 2007-09-20 Time 10:29 Rev Time 0.00
Received By dpalmer Date 2007-09-20 Time 09:04 Sent To M
Notes
2007-09-20 10:30:08 
 ** DENIED 4TH TIME **
  
 THIS IS THE FIRST REVIEW UNDER NEW PLANS FROM A NEW
 DESIGN PROFESSIONAL(S).
  
 ** PLEASE SEE THERE ARE NEW NOTES BASED ON THE PLANS
 BEING SUBMITTED FOR THE FIRST TIME. THESE PLANS WERE
 NOT PREVIOUSLY SUBMITTED FOR REVIEW.
  
 1) NOTE: PLEASE KNOW THIS PROJECT WAS APPLIED FOR
 PERMIT UNDER THE PREVIOUS ADOPTED CODE CYCLE IN THE
 FLORIDA STATUTES 553.73.
 PLEASE SEE THIS IS UNDER THE 2002 NFPA-70 AS THIS WAS
 APPLIED FOR PERMIT BEFORE DECCEMBER 8TH, 2006. PLEASE
 ADJUST PLANS.
  
 2) NOTE: PLEASE SEE THE ELECTRICAL PLANS FOR LAYOUT OF
 DWELLING DOES NOT CONTAIN ANY DESIGN PROFESSIONAL FOR
 TAKING RESPONSIBILITY OF PLANS.
 PLEASE SEE THE SHEET WHICH CONTAINS THE ELECTRICAL
 PANEL SCHEDULE AND RISER CONTAINS AN ENGINEER SIGNED,
 DATED AND SEALED ALONG WITH TITLE BLOCKS.
 ** PLEASE KNOW A DESIGN PROFESSIONAL MUST TAKE
 RESPONSIBILITY OF SAID PLANS. FS 471, 481, 489, ETC FBC
 ADMIN SECTION, 106.1.2, 106.3.1, 110.1.2 ETC.
  
 3) NOTE: PLEASE SHOW DISCONNECTS FOR THE CONDENSING
 UNITS PER 440.11, 110.26.
  
 4) NOTE: PLEASE SEE THE A/C SYSTEMS WHICH ARE SHOWN ON
 PLANS DO NOT CORRELATE WITH THE LOAD CALCULATIONS, OVER
 CURRENT PROTECTION AND LOCATIONS.
 PLEASE SEE THE MISSING AIR HANDLER UNIT FOR 2ND FLOOR
 W/ DISCONNECT. 440.11, 110.26
 PLEASE SEE THE LOADS SHOWN ON CALCULATIONS EXCEED THAT
 OF THE RATING OF THE BRANCH CIRCUITS FEEDING EACH OF
 THESE SYSTEMS. PLEASE SEE 220.19, 240.4, 310.16,
 424.3B
 PLEASE SEE THE OVER CURRENT PROTECTION IS TO MEET THE
 MINIMUM FOR HEAT LOADS PER 424.3B (125% WHICH IS FOR
 OVER CURRENT PROTECTION).
 PLEASE ADJUST THE OCP, CONDUCTOR SIZES, LOCATIONS AND
 LOADS AS NEEDED.
  
 5) NOTE: PLEASE SEE THE LOAD, OVER CURRENT PROTECTION
 AND SIZE OF FEEDERS TO PANEL *B* DO NOT MEET THE
 REQUIREMENTS FOR THE LOADS.
 PLEASE ADJUST.
 240.4, 310.16, 408.4
  
 6) NOTE: PLEASE SHOW THE LOCATION OF PANEL *B*. 110.26,
 408.7, 240.24D
  
 7) NOTE: PLEASE CORRELATE CIRCUITING ON PLANS. PLEASE
 SEE THERE ARE SEVERAL CIRCUITS ON PANEL SCHEDULE(S)
 WHICH ARE NOT THE SAME AS ON PLANS.
 PLEASE SEE FOR EXAMPLE:
 B-7 ON PLANS IS FOR REFRIGERATOR, YET THE PANEL
 SCHEDULE SHOWS THIS AS THE DISHWASHER.
 B-9 NOT ON PANEL SCHEDULE YET SHOWN AS DISHWASHER ON
 PLANS.
 PLEASE SEE THERE ARE SOME OTHERS PLEASE BE SURE TO
 VERIFY ALL.
  
 8) NOTE: PLEASE SEE MISSING DISPOSAL ON PLANS. PLEASE
 BE SURE TO SEE 210.4B FOR REQUIRED 2-POLE BREAKER IF
 THE DISHWASHER AND DISPOSAL IS ON THE SAME YOKE.
 408.4.
 FBC 106.3.5.4
  
 9) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.16 FOR
 REQUIRED CIRCUITING FOR DINING ROOM/AREA RECEPTACLE
 CIRCUITS. PLEASE SEE THE AREAS AS SPECIFIED IN 210.52B1
 ARE TO BE ON ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS. PLEASE ALSO SEE THAT THE LOAD SHALL BE
 FIGURED ON EACH OF THOSE CIRCUITS AT A MINIMUM OF
 1500VA FOR EACH. THIS INCLUDES ANY ABOVE THE MINIMUM
 FOR THE KITCHEN SMALL APPLIANCE CIRCUITS.
 PLEASE SEE AS NOTED IN SECTIONS, THESE MUST BE 20AMP
 AND #12 AWG.
 PLEASE ADJUST PLANS FOR THESE. (EXAMPLE CIRCUIT #33).
  
 10) NOTE: PLEASE SEE THERE ARE SEVERAL BATHROOM
 CIRCUITS WHICH DO NOT MEET 210.52D, 210.11C3. PLEASE
 SEE ONE CIRCUIT WHICH IS #22 MENTIONS THIS IS ALSO TO
 FEED HALL, WHICH IS NOT PERMITTED.
 PLEASE SEE THESE ARE SHOWN WITH THE REQUIRED #12
 HOWEVER NOT THE REQUIRED 20AMP BREAKER.
 PLEASE ADJUST ALL ON PLANS/PANEL SCHEDULES AS NEEDED.
 (19,22,37,38,39 ETC)
  
 11) NOTE: PLEASE SEE 210.12 FOR SMOKE ALARM CIRCUIT
 WHICH IS NOT SHOWN AS ARC FAULT PROTECTED AS REQUIRED.
 ALL OUTLETS ARE TO BE AFCI. PLEASE ADJUST AND LIST ON
 PANEL SCHEDULE.
  
 12) NOTE: PLEASE INDICATE THE AIC RATING FOR
 MAINS/PANELS/BREAKERS PER 110.9.
 FBC 106.1.2, 106.1.3, 106.3.5.4
  
 13) NOTE: PLEASE CLARIFY *UTILITY ROOM* CIRCUITS WHICH
 ARE SHOWN AS #12, 15AMP, AND GFI?
 THESE CIRCUITS 17 AND 23 ARE FEEDING OTHER AREAS ALSO.
  
 14) NOTE: PLEASE SEE WATER HEATER IS BEING SHOWN ON
 CIRCUITS 5/9 ON PLAN WHICH IS NOT POSSIBLE FOR
 220/240V. PLEASE SEE THE PANEL SCHEDULE AS THIS CALLS
 FOR 5/7.
 PLEASE ALSO SEE THE SYMBOL SHOWN FOR CONNECTION OF THE
 WATER HEATER LENDS THIS AS BEING PLUG IN CONNECTION.
 PLEASE SEE 422.30, 422.31 AS THIS UNIT IS REQUIRED TO
 BE HARDWIRED AND MAY NOT PLUG-IN.
 A DISCONNECT IS NOT REQUIRED WHEN THE PANEL IS WITHIN
 SIGHT, HOWEVER MAY BE INSTALLED.
  
 15) NOTE: PLEASE VERIFY IF THE CONDUIT FROM THE METER
 TO THE PANEL INSIDE IS UNDERGROUND/SLAB OR NOT. PLEASE
 SEE 230.70,230.71, AS A MAIN DISCONNECT WITH OVER
 CURRENT PROTECTION WOULD BE REQUIRED OUTSIDE IF MORE
 THAN 8FT OF UNPROTECTED CONDUCTORS ARE INSIDE THE
 DWELLING.
  
 16) NOTE: PLEASE KNOW FOR INFORMATIONAL PURPOSE ONLY:
 THE LOW VOLTAGE AS SHOWN ON PLANS WILL BE REQUIRED TO
 BE UNDER A SEPARATE PERMIT.
 PLEASE KNOW THESE PLANS MAY BE USED FOR REFERENCING AND
 A *TURN AROUND* PERMIT WILL BE ISSUED.
 ** THIS IS ONLY NOTED FOR INFORMATION TO THE OWNER.
  
 17) NOTE:
  
  
 *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-20 09:04:36NEW PLANS SUBMITTED ON 9/13/07

Review Stop E ELECTRICAL
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2007-09-20 Time   Rev Time 0.00
Received By dpalmer Date 2007-08-21 Time 13:38 Sent To  
Notes
2007-08-21 13:39:298/21/07 PLANS ARE ON HOLD, OWED FEES FOR PREVIOUS
 REVIEWS. PLANS SUBMITTED ARE THAT DONE BY THE
 ARCHITECT. PLANS SUBMITTED AND PREVIOUSLY RETAINED
 PLANS MAY BE TURNED OVER TO THE STATE BOARD OF
 ARCHITECTS AND STATE'S LEGAL COUNSEL TO THE BOARD. DV
 PALMER.
  
  
 THIS IS BEING TURNED OVER TO TEH BUILDING OFFICIAL AND
 NO FURTHER REVIEWS WILL BE DONE AT THIS TIME. DV
 PALMER.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-01-21 Cont ID  
Sent By dpalmer Date 2007-01-21 Time 09:47 Rev Time 0.00
Received By dpalmer Date 2007-01-19 Time 20:50 Sent To M
Notes
2007-01-21 09:50:02**** UNSAT ****
 3RD REVIEW UNDER PERMIT # 06071334
 6TH REVIEW FOR THIS SINGLE FAMILY HOUSE.(PREVIOUS#
 WAS 05041961
  
 ** PLEASE SEE COMMENTS FROM PREVIOUS REVIEW STILL NEED
 TO BE ADDRESSED.
  
  
 1) NOTE: PLEASE SEE THE NEC 2002. 220, 220.31, 220.16,
 220.14, 220.17, 210.52B1, 210.11C1, 210.11C2,ETCFOR
 LOAD CALCULATIONS, MINIMUM CIRCUITS, AND LOADS FOR EACH
 OF THOSE MINIMUM CIRCUITS.
 PLEASE SEE THE PREVIOUS COMMENTS FROM ALL OF THE
 PREVIOUS REVIEWS STATED THAT THE LOADS SHOWN ON THE
 PANEL SCHEDULE DID NOT CORRELATE WITH THE LOADS IN THE
 LOAD CALCULATIONS.
 PLEASE SEE AMPERAGES SHOWN ON THE PANEL SCHEDULE DO NOT
 CORRELATE WITH THE KVA/WATTAGE LOAD ON THE LOAD
 CALCULATIONS.
 PLEASE SEE LOADS OF 6AMPS IS BEING SHOWN FOR
 WASHER/LAUNDRY CIRCUIT, HOWEVER THIS DOES NOT CORRELATE
 WITH THE KVA ON CALCULATIONS
 PLEASE SEE THE DISHWASHER/DISPOSAL IS STILL BEING SHOWN
 ON THE SAME CIRCUIT AND IS SHOWN ON WITH THE DINING
 ROOM CIRCUIT. THE LOADS ON THE DISHWASHER AND DISPOSAL
 ARE MOST LIKELY DEDICATED CIRCUITS. THIS OFFICE HAS
 NEVER SEEN A DISHWASHER ON WITH THE DISPOSAL AND ALL
 THE OTHER RECEPTACLES AS SHOWN. PLEASE SEE THE DISPOSAL
 IS STILL ONLY BEING SHOWN HARDWIRED. IF THIS IS FED
 FROM THE SAME RECEPTACLE OUTLET AS THE DISHWASHER
 (SPLIT OUTLET) PLEASE SEE 210.4B
 PLEASE SEE MICROWAVE.
 PLEASE SEE MISSING SMALL APPLIANCE CIRCUIT DESIGNATIONS
 ON PANEL SCHEDULE. ONE CIRCUIT SEEMS TO BE SHOWN AS 2ND
 FLR GFI, INSTEAD OF SM APPL. PLEASE SEE THE OTHER
 CIRCUIT SHOWN IN THE KITCHEN IS SHOWN FEEDING THE
 REFRIGERATOR ONLY. PLANS SHOW ONE CIRCUIT FEEDING ALL
 COUNTER SPACE RECEPTS IN THE KITCHEN.
 PLEASE SEE THE LOAD FOR THE POOL PANEL IS BEING SHOWN
 AS 30AMPS, YET THE LOAD CALCULATIONS ONLY INDICATE
 2.2KW??
 PLEASE SEE GARAGE DOOR OPENER WHICH IS STILL BEING
 SHOWN ON WITH ALL OTHER RECEPTS IN THE GARAGE. PLEASE
 SEE MOTOR LOADS AS STATED ABOVE 220.14, 430.148.
 PLEASE SEE AS STATED IN THE PREVIOUS REVIEWS; PLEASE
 CORRELATE ALL OF THE LOADS ON PANEL SCHEDULE WITH THE
 LOADS BEING SHOWN IN THE LOAD CALCULATIONS.
 THE ABOVE ITEMS ARE NOT ALL POSSIBLE ITEMS AS THE NOTES
 MENTIONS; CODE COMPLIANCE FOR ALL SHALL BE MET.
 THE COMMENT RESPONSE FROM THE ARCHITECT MENTIONS ALL OF
 THESE WOULD BE ADDRESSED.
  
 2) NOTE: PLEASE SEE MISSING RECEPTACLE IN GUEST ROOM,
 THIS WAS ON PREVIOUS PLANS, HOWEVER IS NOW REMOVED. IF
 PLANS WERE OK WITH LOAD CALCULATIONS, THIS WOULD HAVE
 BEEN REDLINED. 210.52 2FT OF WALL SPACE.
  
 3) NOTE: PLEASE SEE THE AHU'S IN THE FIRST FLOOR CLOSET
 AND 2ND FLOOR ATTIC ARE STILL BEING SHOWN WITH 220V
 RECEPTACLES? THIS WAS GONE OVER ON THE MEETING WITH THE
 ARCHITECT AND THE DESIGNER. THE RECEPTACLE WAS GOING TO
 BE REMOVED, HOWEVER STILL SHOWN ON PLANS. PLEASE SEE
 THIS WOULD HAVE BEEN REDLINED, HOWEVER SEE NOTE #1.
 THE AHU'S ARE TO BE HARDWIRED TO DISCONNECTS, THESE ARE
 NOT TO BE CORD AND PLUG CONNECTED. THE SIGNED AND
 SEALED COMMENT RESPONSE FROM THE ARCHITECT MENTIONS
 WOULD BE ADDRESSED AND CORRECTED.
 4220.30, 422.30, 440.11.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEWS REQUESTED ALL
 CIRCUITING ON PLANS TO CORRELATE WITH PANEL SCHEDULE.
 PLEASE SEE DRYER IS STILL BEING SHOWN WITH A RECEPTACLE
 WHICH FEEDS THE GUEST ROOM?
 (CIRCUIT #20).
 408.4, 310.16, 240.4,
 FBC 106.1.2, 106.3.5.4 ADMIN SECTION.
  
 5) NOTE: PLEASE SEE RISER SHOWS POOL SUB PANEL BEING
 30AMP, YET THIS IS BEING FED FROM A 40AMP BREAKER ON
 THE MAIN PANEL. PLEASE CORRELATE THE LOADS (AS NOTED
 ABOVE IN NOTE #1), PLEASE CORRELATE THE SIZE OF THE
 PANEL AND ANY OTHER ASPECTS TO THIS.
 RESPONSE MENTIONS THIS WOULD BE CORRECTED AS THIS
 COMMENT WAS IN PREVIOUS REVIEWS;, HOWEVER PLEASE SEE
 THIS IS STILL IN NEED OF COORDINATION.
 310.16, 240.4, 220, ETC.
  
 6) NOTE: PLEASE SEE AS GIVEN NOTICE IN THE PREVIOUS
 REVIEWS, A 4X FEE HAS NOW BEEN ASSESSED TO THE DESIGN
 PROFESSIONAL FOR REPEAT CODE COMPLIANCE COMMENTS PER
 553.80(2)(B).
 PLEASE SEE THE FEE OF $2820.00 HAS NOW BEEN ASSESSED TO
 THE DESIGN PROFESSIONAL AND IS NOT THE RESPONSIBILITY
 OF THE CONTRACTOR OR THE OWNER OF PROPERTY.
 ONE COPY OF THE ELECTRICAL PLANS IS BEING RETAINED AND
 WILL BE PLACED WITH THE OTHER PREVIOUS FIVE SETS OF
 PLANS PREVIOUSLY RETAINED IN FILE. THESE PLANS WILL BE
 FORWARDED TO THE STATE BOARD OF ARCHITECT'S LEGAL
 COUNSEL ONCE ALL REVIEWS ARE COMPLETED.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-19 20:51:072007-01-19 20:51:07
 IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-27 Cont ID  
Sent By dpalmer Date 2006-10-27 Time 13:07 Rev Time 0.00
Received By dpalmer Date 2006-10-27 Time 10:46 Sent To M
Notes
2006-10-27 13:07:24********** UNSAT 2ND REVIEW UNDER 06071334
 ***************
 5TH REVIEW FOR PROJECT**
  
 1) NOTE:PLEASE SEE THAT THIS ISNOW THE
 5TH REVIEW FOR THIS PROJECT. PLANS
 ORIGINALLY CAME IN UNDER A "PLAN REVIEW"
 FOR THREE REVIEWS UNDER #05041961 AND
 NOW ARE BEING SUBMITTED FOR PERMIT.
 PLEASE SEE MANY OF THE FOLLOWING
 COMMENTS ARE FROM ALL PREVIOUS
 ELECTRICAL REVIEWS.
 ** PLEASE KNOW ONCE AGAIN PLANS ARE BEING RETAINED.
 PLEASE SEE OTHER
 POSSIBLE COMMENTS FROM OTHER TRADES.
 PLANS WILL BE REVIEWED BY THE SAME
 REVIEWERS AS PREVIOUSLY REVIEWED.
 PLEASE BE AWARE THAT ONE COMPLETE SET OF
 PLANS ARE BEING RETAINED AND WILL BE ALL
 SETS OF PLANS PREVIOUSLY RETAINED. ONCE
 ALL REVIEWS ARE COMPLETE PLANS WILL BE
 FORWARDED TO THE STATE BOARD OF
 ARCHITECT'S AND STATE'S LEGAL COUNSEL TO
 THE BOARD. THESE PLANS WILL NOW HAVE
 BEEN REVIEWED FOUR TIMES FOR A SINGLE
 FAMILY HOUSE WITH MOST OF THE SAME
 COMMENTS FOR ELECTRICAL NOT ADDRESSED.
 PLEASE SEE FS 553.80(2)(B).
 PLEASE KNOW, IF PLANS COME BACK WITH ANY OF THE SAME
 COMMENTS FOE CODE COMPLIANCE NOT ADDRESSED, A 4X FEE
 WILL BE ASSESSED.
 PLEASE SEE
 FS 481.221(4)
  
 2) NOTE: OK.
  
 3) NOTE:NO, SOME CIRCUITS SHOWN BLANK ON SCHEDULE FOR
 CONDUCTOR AND BREAKER SIZES FOR THIS?
 PLEASE ALSO SEE PREVIOUS NOTES WHICH MENTIONS THE BATH
 CIRCUIT WITH THE GFI RECEPT MAY NOT BE PART OF ANY
 OTHER DEVICES/OUTLETS OUTSIDE THE BATH ROOM.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 210.52D, 210.11C3
 FOR CIRCUITING OF BATH(S). PLEASE SEE
 MULTIPLE BATHS MAY NOT BE FED FROM THE
 SAME CIRCUIT WHEN FEEDING BATH LTS AND
 RECEPTS.
 PLEASE ALSO SEE THE REQUIRED DEDICATED
 BATH CIRCUIT(S) ARE ALSO SHOWN FEEDING
 OTHER AREAS? (HALL, CLOSETS ETC).
 PLEASE SEE PLANS SHOW THIS IS VIOLATION
 OF CODES ABOVE.
  
 4) NOTE: NO, SAME NOTE>
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE RISER AND
 PANEL SCHEDULE FOR FUTURE POOL PANEL.
 TWO SETS OF FEEDER SIZE ARE SHOWN??
 #8'S ? #6'S?
 215.5, FBC106.1.2
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE:NO, SAME NOTE >
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MIN DISCONNECT
 CLEARANCES PER 110.26 FOR A/C CU.
  
 8) NOTE:NO/OK, PLEASE SEE ACCESS SEEMS TO BE
 ADDRESSED, HOWEVER PLEASE SEE THAT THE UNITS ARE NOW
 BEING SHOWN AND NOTED HAVING RECEPTS FOR UNIT??? PLEASE
 SEE 440.11,110.26 AS DISCONNECTS ARE REQUIRED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MECHANICAL COMMENTS
 AS AHU SHOWN IN ATTIC IS MORE THAN 6'
 AWAY FROM WHAT IS SHOWN AS THE ATTIC
 ACCESS ON PLANS.
 PLEASE ALSO SEE MISSING LT AND RECPT.210.70,210.63
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE: NO, LOAD CALCULATIONS DO NOT MEET CODE.
 PLEASE SEE NEC 220.31 , 220.
 CAN NOT TAKE DE-RATINGS FOR SMALL APPLIANCE CIRCUITS.
 PLEASE SEE NOW WASHER/LAUNDRY CIRCUIT IS BEING SHOWN AS
 1200 VA. PLEASE SEE 220.16, 210.11C2 FOR MIN VA.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE NEC FOR LOAD CALCULATIONS. IT IS NOT
 CLEAR WHERE AND
 HOW THESE FIGURES ARE DERIVED AS THE
 DERATING SHOWN DO NOT APPEAR IN THE
 CODE. PLEASE SEE DIFFERENT PERCENTAGES
 ARE BEING SHOWN WHICH ARE NOT PERMITTED.
 PLEASE SEE 220.
 PLEASE ALSO SEE MANY LOADS (AMERAGES)
 SHOWN ON PANEL SCHEDULE DO NOT CORRELATE
 WITH THE KW RATINGS SHOWN ON LOAD
 CALCULATIONS.
 PLEASE SEE A/C#1, A/C #2, DRYER, RANGE
 ETC, HOW AND WHERE DO THESE AMPERAGE'S
 COME FROM. PLEASE SEE THE KW RATING IS
 DIVIDED BY THE VOLTAGE TO ARRIVE AT THE
 AMPERAGE AND THE FIGURES SHOWN JUST
 DON'T ADD UP.????
 PLEASE SEE OTHER LOADS WHERE LOADS ARE
 TAKEN AT 40%?? PLEASE INDICATE HOW AND
 WHERE IN THE NEC PERMITS THESE AT 40%??
 PLEASE SEE NEC 2002 ART 220.
 PLEASE ALSO CLARIFY HOW THE LOADS SHOWN
 OFGENERAL LIGHTING AND RECEPT LOADS
 ARE DERIVED. AN AMPERAGE LOAD IS SHOWN
 FOR EACH OF THESE??
  
 12) NOTE: OK.
  
 13) NOTE:NO, DISC SHOWN, HOWEVER DO NOT MEET 110.26.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW REQUIRED
 DISCONNECTS FOR CU'S 440.11 AND PLEASE
 SEE 110.26 FIR MIN CLEARANCE.
  
 14) NOTE: OK.
  
 15) NOTE:OK.
  
 *** NEW NOTE **
  
 16) NOTE: PLEASE SEE COPY OF FS 553.80(2)(B) ATTACHED.
  
 17) NOTE: PLEASE KNOW, IN NO CASE CAN WHITE OUT OR HAND
 WRITTEN CHANGES BE PLACED ON PLANS SIGNED , DATED AND
 SEALED BY A DESIGN PROFESSIONAL.
 FS 481/471
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-25 Cont ID  
Sent By dpalmer Date 2006-07-25 Time 08:28 Rev Time 0.00
Received By dpalmer Date 2006-07-25 Time 07:03 Sent To Z
Notes
2006-07-25 00:00:00********** UNSAT ***************
  
 1) NOTE:PLEASE SEE THEAT THIS IS THE
 4TH REVIEW FOR THIS PROJECT. PLANS
 ORIGINALLY CAME IN UNDER A "PLAN REVIEW"
 FOR THREE REVIEWS UNDER #05041961 AND
 NOW ARE BEING SUBMITTED FOR PERMIT.
 PLEASE SEE MANY OF THE FOLLOWING
 COMMENTS ARE FROM ALL PREVIOUS
 ELECTRICAL REVIEWS. PLEASE SEE OTHER
 POSSIBLE COMMENTS FROM OTHER TRADES.
 PLANS WILL BE REVIEWED BY THE SAME
 REVIEWERS AS PREVIOUSLY REVIEWED.
 *************************************
 PLEASE BE AWARE THAT ONE COMPLETE SET OF
 PLANS ARE BEING RETAINED AND WILL BE ALL
 SETS OF PLANS PREVIOUSLY RETAINED. ONCE
 ALL REVIEWS ARE COMPLETE PLANS WILL BE
 FORWARDED TO THE STATE BOARD OF
 ARCHITECT'S AND STATE'S LEGAL COUNSEL TO
 THE BOARD. THESE PLANS WILL NOW HAVE
 BEEN REVIEWED FOUR TIMES FOR A SINGLE
 FAMILY HOUSE WITH MOST OF THE SAME
 COMMENTS FOR ELECTRICAL NOT ADDRESSED.
 PLEASE SEE FS 553.80(2)(B).
 PLEASE SEE I AM ATTACHING ALL REVIEWS
 FOR ALL TRADES DONE UNDER 05041961 AND
 NEW COMMENTS UNDER 06071334.
 FS 481.221(4)
  
 2) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 THIS WAS REQUESTED ON ALL PREVIOUS
 REVIEWS.
  
 3) NOTE: PLEASE SEE 210.52D, 210.11C3
 FOR CIRCUITING OF BATH(S). PLEASE SEE
 MULTIPLE BATHS MAY NOT BE FED FROM THE
 SAME CIRCUIT WHEN FEEDING BATH LTS AND
 RECEPTS.
 PLEASE ALSO SEE THE REQUIRED DEDICATED
 BATH CIRCUIT(S) ARE ALSO SHOWN FEEDING
 OTHER AREAS? (HALL, CLOSETS ETC).
 PLEASE SEE PLANS SHOW THIS IS VIOLATION
 OF CODES ABOVE.
  
 4) NOTE: PLEASE CORRELATE RISER AND
 PANEL SCHEDULE FOR FUTURE POOL PANEL.
 TWO SETS OF FEEDER SIZE ARE SHOWN??
 #8'S ? #6'S?
 215.5, FBC106.1.2
  
 5) NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN DISCONNECT
 TO PANEL "A". 250.24B, 250.110,250.122
  
 6) NOTE: PLEASE SEE MISSING REQUIRED
 FOOTER STEEL AS PART OF THE GROUNDING
 ELECTRODE SYSTEM. 250.50
  
 7) NOTE: PLEASE SEE MIN DISCONNECT
 CLEARANCES PER 110.26 FOR A/C CU.
  
 8) NOTE: PLEASE SEE MECHANICAL COMMENTS
 AS AHU SHOWN IN ATTIC IS MORE THAN 6'
 AWAY FROM WHAT IS SHOWN AS THE ATTIC
 ACCESS ON PLANS.
 PLEASE ALSO SEE MISSING LT AND RECPT.210.70,210.63
  
 9) NOTE: PLEASE THAT THE FOLLOWING
 MINIMUM CODES ARE REFERENCED ON THE
 PLANS.
 2002 NFPA-70 (NEC), 2002 NFPA-72 .
  
 10) NOTE: PLEASE SEE SD'S ARE STILL
 BEING SHOWN ON MULTIPLE CIRCUITS????
 PLEASE KNOW, SD'S ARE REQUIRED TO BE
 120V W/ BATTERY BACK AND WIRED "INLINE"
 WITH EACH OTHER. PLEASE EXPLAIN HOW THIS
 IS POSSIBLE AS SHOWN WITH SD'S BEING
 SHOWN ON AT LEAST FOUR DIFFERENT
 CIRCUITS??
 11.5.1.1, 11.8.3 NFPA-72
  
 11) NOTE: PLEASE SEE THE NEC FOR LOAD CALCULATIONS. IT
 IS NOT CLEAR WHERE AND
 HOW THESE FIGURES ARE DERIVED AS THE
 DERATING SHOWN DO NOT APPEAR IN THE
 CODE. PLEASE SEE DIFFERENT PERCENTAGES
 ARE BEING SHOWN WHICH ARE NOT PERMITTED.
 PLEASE SEE 220.
 PLEASE ALSO SEE MANY LOADS (AMERAGES)
 SHOWN ON PANEL SCHEDULE DO NOT CORRELATE
 WITH THE KW RATINGS SHOWN ON LOAD
 CALCULATIONS.
 PLEASE SEE A/C#1, A/C #2, DRYER, RANGE
 ETC, HOW AND WHERE DO THESE AMPERAGE'S
 COME FROM. PLEASE SEE THE KW RATING IS
 DIVIDED BY THE VOLTAGE TO ARRIVE AT THE
 AMPERAGE AND THE FIGURES SHOWN JUST
 DON'T ADD UP.????
 PLEASE SEE OTHER LOADS WHERE LOADS ARE
 TAKEN AT 40%?? PLEASE INDICATE HOW AND
 WHERE IN THE NEC PERMITS THESE AT 40%??
 PLEASE SEE NEC 2002 ART 220.
 PLEASE ALSO CLARIFY HOW THE LOADS SHOWN
 OFGENERAL LIGHTING AND RECEPT LOADS
 ARE DERIVED. AN AMPERAGE LOAD IS SHOWN
 FOR EACH OF THESE??
  
 12) NOTE: PLEASE SEE MISSING RECEPT PER
 210.52 IN UTILITY AREA.
  
 13) NOTE: PLEASE SHOW REQUIRED
 DISCONNECTS FOR CU'S 440.11 AND PLEASE
 SEE 110.26 FIR MIN CLEARANCE.
  
 14) NOTE: PLEASE SEE RECEPT SHOWN FOR
 WATER HEATER, HOWEVER THIS IS REQUIRED
 TO BE HARDWIRED W/ DISCONNECT.
 422.30,422.31.
  
 15) NOTE: PLEASE VERIFY THE OCP SHOWN
 FOR DRYER. THIS IS A 5KW UNIT AND SHOWS
 40A OCP?.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-09-14 Cont ID  
Sent By adarroug Date 2007-09-14 Time 08:24 Rev Time 0.00
Received By adarroug Date 2007-09-14 Time 08:24 Sent To Z
Notes
2007-09-14 08:24:50TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-08-17 Cont ID  
Sent By shill Date 2007-08-17 Time 16:16 Rev Time 0.00
Received By shill Date 2007-08-17 Time 16:16 Sent To Z
Notes
2007-08-17 16:16:55TO CHOOPS
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-01-19 Cont ID  
Sent By adarroug Date 2007-01-19 Time 08:34 Rev Time 0.00
Received By adarroug Date 2007-01-19 Time 08:34 Sent To E
Notes
2007-01-19 08:34:55TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-01-12 Cont ID  
Sent By eschneid Date 2007-01-18 Time 18:10 Rev Time 0.00
Received By adarroug Date 2007-01-12 Time 09:00 Sent To I
Notes
2007-01-12 09:01:03TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-20 Cont ID  
Sent By adarroug Date 2006-10-20 Time 09:58 Rev Time 0.00
Received By adarroug Date 2006-10-20 Time 09:57 Sent To E
Notes
2006-10-20 09:58:18TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-11 Cont ID  
Sent By adarroug Date 2006-10-11 Time 13:32 Rev Time 0.00
Received By adarroug Date 2006-10-11 Time 13:32 Sent To Z
Notes
2006-10-11 13:33:17TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-08 Cont ID  
Sent By shill Date 2006-08-08 Time 17:55 Rev Time 0.00
Received By shill Date 2006-07-24 Time 10:15 Sent To  
Notes
2006-07-24 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-09-20 Cont ID  
Sent By tgordon Date 2007-09-20 Time 11:48 Rev Time 0.35
Received By tgordon Date 2007-09-20 Time 11:48 Sent To P
Notes
2007-09-20 12:02:33PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** PLANS UNDER NEW DESGIN PROFESSIONAL **
  
 *** DENIED ***
 1) SUBMIT COOLING LOAD CALCULATIONS, SEE FBC
 13-607.1.ABC.1.
  
 2) MECHANICAL (A/C) PLANS HAVE NOT BEEN SUBMITTED FOR
 REVIEW. SUBMIT MECHANICAL (A/C) PLANS FOR REVIEW, SEE
 WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-01-22 Cont ID  
Sent By tgordon Date 2007-01-22 Time 09:36 Rev Time 0.30
Received By tgordon Date 2007-01-22 Time 09:36 Sent To P
Notes
2007-01-22 09:39:10*** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 10-30-06. PLEASE SUBMIT
 ENERGY CALCULATIONS PER FBC 13-101.2.1 .
  
 2) AS REQUESTED IN LAST REVIEW 10-30-06. PLEASE SUBMIT
 MANUAL J CALCULATIONS, PER 2004 FBC 13-607.1.ABC.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-10-30 Cont ID  
Sent By tgordon Date 2006-10-30 Time 08:28 Rev Time 0.30
Received By tgordon Date 2006-10-30 Time 08:28 Sent To P
Notes
2006-10-30 08:36:33*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS PER FBC 13-101.2.1
 .
  
 2) PLEASE SUBMITMANUAL J CALCULATIONS, PER 2004 FBC
 13-607.1.ABC.1 .
  
 3) BOTH CALCULATIONS WERE SUBMITTED FOR LAST REVIEW,
 BUT HAVE NOT BEEN FOR THIS REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-27 Cont ID  
Sent By tgordon Date 2006-07-27 Time 16:26 Rev Time 0.30
Received By tgordon Date 2006-07-27 Time 16:26 Sent To B
Notes
2006-07-27 00:00:00*** DENIED ***
 1) RETURN AIR DUCTS TO FIRST FLOOR ROOMS
 OFFICE, STAIR HALL, GUEST ROOM, AND
 IN-LAW BEDROOM ARE NOT SIZED OR SIZED TO
 SMALL, SEE NOTE #6.
  
 2) PLEASE SHOW OR EXPLAIN HOW RETURN AIR
 DUCTS ARE TO TIE INTO THE OPEN RETURN IN
 THE A/C CLOSET ( LOUV. DOOR R/A AND
 DUCTED RETURN AIR).
  
 3) CONSTRUCTION DOCUMENTS (PLANS) SHALL
 BE OF SUFFICIENT CLARITY. PER 2004 FBC
 106.1.1 .
  
 4) ATTIC ACCESS NEEDS TO BE WITHIN 6
 FEET OF AHU #2, PER 2004 FBC/R
 M1305.1.3.2 .
  
 5) MECHANICAL PLANS ARE CALLING FOR UNIT
 #123,520 SENSIBLE BTU'S AND UNIT #2
 42,350 SENSIBLE BTU'S, MANUAL 'J'
 CALCULATIONS ARE CALLING FOR UNIT #1
 14,972 BTU'S AND UNIT #224,469
 SENSIBLE BTU'S, THE PLANS CAN ONLY CALL
 FOR 20% MORE THAN THE MANUAL
 'J'CALCULATIONS, PER 2004 FBC
 607.1.ABC.1.1, COOLING EQUIPMENT IS TO
 LARGE FOR HOUSE PLEASE CORRECT.
  
 6)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status F Date 2007-10-03 Cont ID  
Sent By jleech Date 2007-10-03 Time 07:33 Rev Time 0.00
Received By jleech Date 2007-10-03 Time 07:33 Sent To B
Notes
2007-10-03 07:47:21DENIED;
 NOT ENOUGH INFORMATION TO DO A PLUMBING PLAN REVIEW. A
 SANITARY RISER DIAGRAM IS REQUIRED SHOWING ALLSIZES OF
 WASTE AND VENT PIPES, PER FBC-2004 BUILDING CODE
 CHAPTER 1 ADMINISTRATION, SECTION 106.3.5(9).
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-02-06 Cont ID  
Sent By jleech Date 2007-02-06 Time 07:47 Rev Time 0.00
Received By jleech Date 2007-02-06 Time 07:06 Sent To B
Notes
2007-02-06 08:05:26DENIED;
 1. SANITARY RISER DIAGRAM NOT TO CODE.
 A) AUTOMATIC CLOTHES WASHER DRAIN IS REQUIRED
 TO BE 3" AND MUST BE VENTED WITH C.O. AT 48". NOTE 10
 AND11 SHOULD BE SHOW ON THE RISER DIAGRAM.
 B) FIRST FLOOR SINK VENT TIED INTO SECOND
 FLOOR WASTE STACK. NOT A VENT.
 C) WATER CLOSET NOT VENTED.
 D) TUB NOT VENTED.
 E) TUB NOT VENTED.
 F)SHOWER NOT VENTED.
 G) SECOND FLOOR KITCHEN SINK MUST DISCHARGE
 DOWN STREAM OF THE BATHROOM GROUP. SEC.909.1.
 H) SECOND FLOOR MASTER BATHROOM NOT DRAWN
 CORRECTLY.
 I)USE PROPER NAMES FOR FIXTURES. (
 BATHROOMS HAVE LAVATORIES NOT SINKS).
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-11-02 Cont ID  
Sent By jleech Date 2006-11-02 Time 12:50 Rev Time 0.00
Received By jleech Date 2006-11-02 Time 12:50 Sent To B
Notes
2006-11-02 12:57:25DENIED;
 1.RISER DIAGRAM DOES NOT MATCH FLAT DRAWING. TOO MANY
 CODE VIOLATIONS TO LIST.
 RISER DIAGRAM MARKED IN RED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-25 Cont ID  
Sent By jleech Date 2006-07-25 Time 12:22 Rev Time 0.00
Received By jleech Date 2006-07-25 Time 12:22 Sent To Z
Notes
2006-07-25 00:00:00DENIED;
 1.SANITARY RISER DIAGRAM IS NOT TO CODE;
 A)FIRST FLOOR REVENTS MUST EXTEND 6"
 ABOVE THE HIGHEST FIXTURE ON THE
 SECOND FLOOR BEFORE REVENTING INTO
 THE VENT STACK.
 B)TOILET ON FIRST FLOOR CANNOT BE
 INSTALLED DIRECTLY INTO THE BUILD-
 DRAIN, NOT VENTED PROPERY.
 C)WATER HEATER IS NOT PART OF THE
 SANITARY SYSTEM AND SHOULD NOT
 BE SHOWN ON THE RISER DIAGRAM.
 D)AUTOMATIC CLOTHES WASHER DRAIN,
 STAND PIPE AND VENT WITH CLEANOUT
 NOT DRAWN. DRAIN FOR THE W/M IS
 REQUIRED TO BE 3" AND A CLEANOUT TO
 BE AT 48" AFF. SEE SEC. 406.3 AND
 708..3.4.
 E)DISHWASHER MUST DICHARGE INDIRECTLY
 INTO THE DRAINAGE SYSTEM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 5 Status F Date 2007-09-19 Cont ID  
Sent By choops Date 2007-09-19 Time 09:55 Rev Time 0.00
Received By choops Date 2007-09-19 Time 09:55 Sent To E
Notes
2007-09-19 10:26:38***FAILED - RESUB #5?***
  
 REPEAT COMMENTS:
  
 1)THE PLANNING AND ZONING DEPARTMENT HAS NO RECORD
 THAT THE CITY OF WEST PALM BEACH APPROVED THIS
 SUBDIVISION.THE PROPERTY OWNER SHALL EITHER PROVIDE
 PROOF THAT THE LOT SPLIT WAS APPROVED BY THE PLANNING
 AND ZONING DEPARTMENT OR SHALL APPLY FOR A MINOR
 SUBDIVISION THROUGH THE PLANNING AND ZONING DEPARTMENT.
 THE LOT IS UNBUILDABLE UNTIL SUCH TIME THAT THE MINOR
 SUBDIVISION IS APPROVED.
  
 2)POOL TO BE UNDER SEPARATE PERMIT. PLANS (INCLUDING
 SURVEY) SHALL REFLECT SUCH.
  
 3)SURVEY SHOWS A 24' SETBACK TO FRONT COVERED ENTRY.
 REVISE...MUST BE A 25' SETBACK TO FRONT COVERED ENTRY.
  
 4)ELEVATION DIMENSIONS TO BE MEASURED FROM GRADE.
  
 5)PROPOSED A/C EQUIPMENT SHALL BE SHOWN ON SITE
 PLAN/SURVEY WITH SETBACK DIMENSIONS TO THE PROPERTY
 LINES. (MAY NOT ENCROACH MORE THAN 4' INTO ANY REQUIRED
 SETBACK.)
  
 NEW COMMENTS:
  
 1)SURVEY PROVIDED IS LABELED AS 423 WILDER, THE
 ADDRESS ON THE PERMIT APPLICATION IS 427 WILDER.
 CLARIFY.
  
 2)NEWLY SUBMITTED PLANS DO NOT SHOW COMPLIANCE WITH
 SECTION 94-442 OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS, REGARDING LANDSCAPING.A LANDSCAPE PLAN
 SHALL BE SUBMITTED SHOWING COMPLIANCE WITH SAID
 SECTION.
  
 3)NEWLY SUBMITTED PLANS DO NOT SHOW A
 DRIVEWAY/DIMENSIONS OF A DRIVEWAY/SQUARE FOOTAGE OF A
 DRIVEWAY.IF DRIVEWAY IS BEING PROPOSED, INCLUDE
 DIMENSIONS AND SQUARE FOOTAGE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 4 Status F Date 2007-08-17 Cont ID  
Sent By choops Date 2007-08-17 Time 16:47 Rev Time 0.00
Received By choops Date 2007-08-17 Time 16:47 Sent To E
Notes
2007-08-17 16:49:51***FAILED***
  
 REPEAT COMMENTS:
  
 1)THE PLANNING AND ZONING DEPARTMENT HAS NO RECORD
 THAT THE CITY OF WEST PALM BEACH APPROVED THIS
 SUBDIVISION.THE PROPERTY OWNER SHALL EITHER PROVIDE
 PROOF THAT THE LOT SPLIT WAS APPROVED BY THE PLANNING
 AND ZONING DEPARTMENT OR SHALL APPLY FOR A MINOR
 SUBDIVISION THROUGHT THE PLANNING AND ZONING
 DEPARTMENT.THE LOT IS UNBUILDABLE UNTIL SUCH TIME
 THAT THE MINOR SUBDIVISION IS APPROVED.
  
 2)FENCE/WALL/DECK/POOL TO BE UNDER SEPARATE PERMIT.
 PLANS SHALL REFLECT SAID STRUCTURES AS SUCH.
  
 3)SURVEY SHOWS A 24' SETBACK TO FRONT COVERED ENTRY.
 SITE PLAN SHOWS THE REQUIRED 25' SETBACK.CLARIFY.
  
 4)ELEVATION DIMENSIONS TO BE MEASURED FROM GRADE.
  
 NEW COMMENTS:
  
 1)PROPOSED A/C EQUIPMENT SHALL BE SHOWN ON SITE
 PLAN/SURVEY WITH SETBACK DIMENSIONS TO THE PROPERTY
 LINES. (MAY NOT ENCROACH MORE THAN 4' INTO ANY REQUIRED
 SETBACK.)
  
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, ZONING
 TECHNICIAN
 (561)805-6720

Review Stop Z ZONING
Rev No 3 Status F Date 2007-01-18 Cont ID  
Sent By eschneid Date 2007-01-18 Time 17:50 Rev Time 0.00
Received By eschneid Date 2007-01-18 Time 17:50 Sent To I
Notes
2007-01-18 18:09:44FAILED
  
 1) THE PROPERTY APPRAISER ISSUED THE NEW PCN IN 2002.
 THE PLANNING AND ZONING DEPARTMENT HAS NO RECORD THAT
 THE CITY OF WEST PALM BEACH APPROVED THE SUBDIVISION.
 THE PROPERTY OWNER SHALL EITHER PROVIDE PROOF THAT THE
 LOT SPLIT WAS APPROVED BY THE PLANNING AND ZONING
 DEPARTMENT OR HE SHALL APPLY FOR A MINOR SUBDIVISION
 THROUGH THE PLANNING AND ZONING DEPARTMENT.THIS LOT
 IS UNBUILDABLE UNTIL SUCH TIME THAT THE MINOR AMENDMENT
 IS APPROVED.
  
 2) NO SURVEY SUBMITTED WITH THE RESUBMITTED PLANS -
 FULL SIZE OR REDUCED AS STATED IN THE ARCHITECT'S
 RESPONSE.
  
 3) ELEVATIONS ARE STILL MISLABELED - THE EAST AND WEST
 ELEVATION ARE BACKWARDS AND NOW THE ADDITION OF NORTH
 AND SOUTH ARE ON THE WRONG SIDES OF THE BUILDING.
  
 CONTACT ERIC SCHNEIDER @ (822) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-10-17 Cont ID  
Sent By eschneid Date 2006-10-17 Time 11:18 Rev Time 0.00
Received By eschneid Date 2006-10-13 Time 14:03 Sent To  
Notes
2006-10-17 10:51:44FAILED
  
 1) PROVIDE EVIDENCE THAT THE CITY APPROVED THE
 SUBDIVISION TO CREATE THIS PARCEL, OR THAT THIS PARCEL
 HAS ALWAYS HAD A SEPERATE DEED AND PCN FROM 423 WILDER
 ST.
  
 2) NO SURVEY SUBMITTED WITH THE RESUBMITTED PLANS.
  
 3) PLEASE SHOW THE LOCATION AND SPECIES OF THE 7
 REQUIRD SHRUBS AND LIST THE SPECIES OF THE 3 EXISTING
 TREES (THEY SHALL BE SHADE OR FLOWERING TO MEET CODE
 REQUIREMENTS).
  
 4) BUILDING HEIGHT SHALL BE SHOWN ON THE PLANS MEETING
 CITY STANDARDS (MID-POINT FROM EVE TO RIDGE).
  
 5) ELEVATIONS ARE MISLABLED - LEFT AND RIGHT SIDES NOT
 CORRECT BASED ON THE PLAN - SHOULD USE EAST AND WEST
 ELEVATION.
  
 6) FRONT ROOF OVERHANG AND BALCONY RAIL CAP EXTEND
 FURTHER THAN 3 FEET INTO THE FRONT SETBACK.
  
 7) REAR BALCONY EXTENDS FURTHER THAN 3 FEET INTO THE
 REAR SETBACK.
  
 CONTACT ERIC SCHNEIDER @ (822) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-27 Cont ID  
Sent By mmclean Date 2006-07-27 Time 10:48 Rev Time 0.00
Received By mmclean Date 2006-07-27 Time 10:48 Sent To M
Notes
2006-07-27 00:00:00DENIED,
 1. THE SITEPLAN AND SURVEY DOES NOT
 MATCH (LAYOUT OF THE STRUCTURE).PLEASE
 PROVIDE TWO COPY OF THE PROPOSED WORK.
 2. THE DRIVEWAY OF THE PROPOSED WORK
 DOES NOT MATCH, NEED TO PROVIDE THE
 PROPOSED WORK OF THE PROPOSED DRIVEWAY
  
 NOTE:MUST MAINTAIN 1000SQ FT OR 75% OF
 LANDSCAPE, WHICHEVER IS LESS WITHIN THE
 FIRST 25FT FRONT SETBACK.
  
 3. THE SETBACK FOR THE PROPOSED COVERED
 PATIO MUST SIT BACK 25FT. THE ROOF CAN
 ONLY PROJECT 3FT INTO THE 25FT FRONT
 SETBACK.
 4. SEPERATE PERMIT MUST BE PULLED FOR
 THE POOL/DECK/WALL/GATE/FENCE (FENCE
 REQUIRES AN APPROVAL FROM THE CITY OF
 WEST PALM BEACH UTILITY DEPT).
 5. THE STRUCTURAL OVERHANG PROJECTION
 SHALL NOT EXTEND FARTHER THAN THREE FEET
 INTO ANY SETBACK.
  
 MICHELLE MCLEAN