Plan Review Details - Permit 06071240
Plan Review Stops For Permit 06071240
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-04 Cont ID  
Sent By amorse Date 2006-08-04 Time 13:51 Rev Time 0.00
Received By amorse Date 2006-08-04 Time 13:51 Sent To  
Notes
2006-08-04 00:00:00 
  
 DENIED
  
 1) PROVIDE PROOF OF OWNERSHIP, PROPERTY
 CONTROL NUMBER, AND ADDRESS
  
 2) PROVIDE LETTER FROM CONDO/HOA
 ASSOCIATION THAT WORK TO BE PERFORMED IS
 PERMITTED
  
 3) SUBMIT 2 COPIES OF ENERGY CALC'S PER
 13-101.2.2 FBC. BE SURE THAT THEY ARE
 SIGNED AND DATED BY PREPARER AND
 OWNER/AGENT PRIOR TO SUBMITTAL
  
 4) THE PERSONS RESPONSIBLE UNER 481.229
 F.S. FOR THE DRAWINGS SHALL LEGIBLY
 PRINT THEIR NAME AND SIGN AND DATE
  
 5) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 ******NOTE ONLY ONE COPY OF EACH PRODUCT
 APPROVAL WAS SUBMITTED FOR HORIZONTAL
 ROLLER AND FIXED WINDOW. SUBMIT 2 COPIES
 OF PRODUCT APPROVALS FOR MULLION.****
  
 6) DRAWING DOES NOT SHOW FIXED WINDOW
 PLEASE CLARIFY.
  
 7) PROVIDE SIZE OF NEW WINDOW TO BE
 INSTALLED AND ALL OTHER EXTERIOR WINDOWS
 PLEASE KNOW THAT IF THE AGREGATE AREA OF
 THE NEW GLAZING IS MORE THAN 25% OF THE
 TOTAL GLAZED AREA OF THE DWELLING UNIT
 IMPACT PROTECTION IS REQUIRED AND
 PRODUCT APPROVALS FOR THE SHUTTERS WILL
 ALSO BE REQUIRED
  
 8) PROVIDE ENGINEERED BUCK ATTACHMENT
  
 9) PROVIDE INFORMATION/DETAILS ON ROOF
 OVER SCREENED PATIO/NEW DINING ROOM
  
 10) DRAWINGS CANNOT HAVE HAND WRITTEN
 INFORMATION PLEASE MAKE CORRECTIONS
  
 11) PROVIDE INFORMATION THAT
 WINDOWS/BUCKS WILL BE ATTACHED TO FILLED
 BLOCK CELL
  
 12) VERIFY SCOPE OF WORK, APPLICATION
 STATES NEW HOT WATER HEATER BUT ENERGY
 CALC'S STATE EXISTING, PLEASE CLARIFY
  
 13) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-06 Cont ID  
Sent By dpalmer Date 2006-08-06 Time 08:26 Rev Time 0.00
Received By dpalmer Date 2006-08-06 Time 08:26 Sent To  
Notes
2006-08-06 00:00:00***** UNSAT *******
  
 1) NOTE: PLEASE SUBMIT AND SHOW NEW
 ELECTRICAL FOR NEW HABITABLE ROOMS PER
 210.52
  
 2) NOTE: PLEASE SEE PLANS MENTIONS A NEW
 BEDRM, THEN SCRATCHED OUT AND MENTIONS
 OFFICE. PLEASE KNOW IF THIS IS AN
 ADAPTABLE SLEEPING ROOM A SD MAY BE
 REQUIRED. IN EITHER CASE PLEASE SEE 2004
 R313. PLEASE VERIFY ALL LOCATIONS FOR
 SD'S BEING BROUGHT UP TO THE CURRNT CODE
 OR SHOW EXISTING WHICH MEETS CURRENT
 CODE.
 NFPA-72 11.5.1.1, 11.8.3
  
 ** PLEASE SEE THAT ALL SD'S ARE REQUIRED
 TO BE WIRED IN LINE ETC.
  
 3) NOTE: PLEASE SHOW MIN EGRESS LT
 CONTROL AND FIXTIRE(S) REQUIRED.
 210.70, LS101 7.8
  
 4)NOTE: PLEASE SPECIFY THE NEW DEDICATED
 DINING 20A CIRCUIT(S). PLEASE SEE
 210.52B1,210.11C1,220.16
  
 5) NOTE: PLEASE INCLUDE A PANEL SCHEDULE
 FOR NEW CIRCUITS BEING ADDED.
 408.4, FBC 106.1.2
  
 6) NOTE : PLEASE SEE PLANS SHALL BE
 SPECIFIC IN DESIGN FOR THE CURRENT CODE
 ADOPTED BY THE STATE OF FLORIDA.
 PLEASE SEE WE ARE UNDER 2004 FBC, 2002
 NFPA-70 , 2002 NFPA-72, THESE ARE
 REQUIRED FOR ELECTRICAL AT A MIN.
 MAY NOT STATE THE "LATEST" AS THOSE
 CODES WHICH ARE OUT ARE NOT YET ADOPTED.
  
 7) NOTE: PLEASE SEE THAT WHEN PLANS ARE
 NOT REQUIRED TO BE DONE BY AN ARCHITECT
 OR ENGINEER , THE PERSON RESPONSIBLE FOR
 PLANS AND DESIGN SHALL CLEARLY STATE
 DRAWN BY: PRINTED NAME AND SIGNATURE.
 FBC106.1.2
  
 8) NOTE: PLEASE SEE NOC INFORMATION AS
 REQUIRED ON A NOTICE OF COMMENCMENT
 WHICH IS ALSO REQUIRED TO BE RECORDED
 AND SUBMITTED BEFORE PICKING UP PERMIT.
 PLEASE SEE FS 713.13 FOR ALL INFORMATION
 REQUIRED AND PLEASE BE SURE THIS IS
 NOTARIZED AS REQUIRED. PLEASE SEE FS
 117.05 FOR REQUIREMENTS FOR THE NOTARY.
  
 ** PLEASE KNOW, PLANS SHALL BE SPECIFIC
 IN DESIGN AND MAY NOT STATE ALL PER CODE
 IN LEIU OF DEATAILS REQUIRED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-08-16 Cont ID  
Sent By mwennerg Date 2006-08-16 Time 15:30 Rev Time 0.00
Received By mwennerg Date 2006-08-16 Time 15:30 Sent To  
Notes
2006-08-16 00:00:00***DENIED***
  
 1) PLEASE SHOW THE LOCATION OF ALL
 REQUIRED SMOKE DETECTORS, NEW OR
 EXISTING.
  
 2) PLEASE CLARIFY THE USE OF THE ROOM
 THAT IS NOW IDENTIFIED AS A DEN.
  
 3) NEW SMOKE DETECTORS SHALL BE
 INSTALLED A MINIMUM OF (3)' FROM AC
 DIFFUSERS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-16 Cont ID  
Sent By mwennerg Date 2006-08-16 Time 15:34 Rev Time 0.00
Received By mwennerg Date 2006-07-22 Time 13:41 Sent To  
Notes
2006-08-03 00:00:00TO "BOB"#11
2006-07-22 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-04 Cont ID  
Sent By tgordon Date 2006-08-04 Time 16:06 Rev Time 0.20
Received By tgordon Date 2006-08-04 Time 16:06 Sent To  
Notes
2006-08-04 00:00:00*** DENIED ***
 1) SHOW SIZE OF NEW SUPPLY AIR GRILL IN
 OFFICE, AND CFM'S.
  
 2) PROVIDE RETURN AIR TO OFFICE, SEE
 NOTE #6.
  
 3) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT ALSO, PER 2004 FBC
 13-600.3.ABC.2
  
 4) SHOW SEER OREER ON ENERGY
 CALCULATIONS, AND PROVIDE TWO COPY'S OF
 THE ENERGY CALCULATIONS.
  
 5) SHOW A/C EQUIPMENT LISTING ON PLANS
 FOR NEW A/C SYSTEM.
  
 6) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-08-12 Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jleech Date 2006-08-12 Time 11:49 Sent To  
Notes
2006-08-12 00:00:00DENIED;
 SHOW PLUMBING WORK THAT WILL BE DONE ON
 PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695