| 2007-01-05 18:33:40 | ** UNSAT ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE PLANS SHALL BEAR THE CORRECT |
| | ADDRESS ON TITLE BLOCKS. |
| | PLEASE SEE THE PERMIT APPLICATION AND THE ADDRESS IN |
| | OUR SYSTEM APPLIED TO IS 205 N. DIXIE. |
| | FAC 61G1-16.004, 61G15-23.002 |
| | |
| | 2) NOTE: PLEASE SEE PLANS SHALL REFERENCE ALL CODES |
| | WHICH ARE CURRENTLY RELEVANT TO THE DESIGN OF SAID |
| | PLANS AND WHICH SHALL ALSO BE STATED ON PLANS. PLEASE |
| | BE SURE TO SEE ALL OF THESE NEW SECTIONS WHICH ARE |
| | RELEVANT TO THE DESIGNS FOR THE SCOPE OF WORK BEING |
| | SHOWN AND PROPOSED. |
| | PLEASE ALSO SEE THAT THE FOLLOWING SHALL BE STATED ON |
| | THE PLANS AT A MINIMUM. |
| | 2004 FBC W/2006 REVISIONS. |
| | 2002 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | 2003 NFPA-75 |
| | |
| | ** SIDE NOTE, AS OF 12/8/06 THE STATE OF FLORIDA HAS |
| | ADOPTED THE 2005 NFPA-70 (NEC) AND THE 2006 REVISIONS |
| | TO THE 2004 FBC. THIS IS GIVEN FOR INFORMATION ONLY. |
| | ALL PERMIT APPLICATIONS ON 12/8/06 OR LATER SHALL BE |
| | UNDER THE NEW CODES. |
| | |
| | 3) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF |
| | WORK SHALL INCLUDE ALL LABOR AND MATERIALS. PLEASE ALSO |
| | SEE BUILDING REVIEW COMMENTS AS BASED ON THE SCOPE OF |
| | WORK SHOWN THE APPLIED VALUE IS LOW. PLEASE SEE THE |
| | VALUE HAS NOT CHANGED, HOWEVER THE SCOPE OF WORK HAS |
| | SUBSTANTIALLY INCREASED EVEN WITHOUT THE EQUIPMENT |
| | BEING INSTALLED. |
| | FBC 108.3 |
| | |
| | 4) NOTE: PLEASE SHOW AND INDICATE THE ACTUAL ATTACHMENT |
| | FOR THE GROUNDING OF THE TRANSFORMER PER 250.30, |
| | 250.20. QUOTING GROUNDING "PER NEC 250" IS NOT |
| | PERMITTED. PLEASE SUBMIT DETAIL IN LIEU OF QUOTING THE |
| | CODE(S). |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 5) NOTE: PLEASE SEE PANEL ON PLANS MENTIONS "EXISTING |
| | IT PANEL" YET THIS IS NOT POSSIBLE AS THIS PANEL WAS |
| | NOT LOCATED IN THE OLD COMPUTER ROOM. PLEASE CLARIFY |
| | THIS ON PLANS. |
| | FBC 106.1.2. |
| | |
| | 6) NOTE: PLEASE SEE 450.3 FOR THE MAXIMUM OVER CURRENT |
| | PROTECTION PERMITTED ON THE TRANSFORMER AS SHOWN. (125% |
| | MAX). |
| | |
| | |
| | 7) NOTE: PLEASE PROVIDE CALCULATIONS ON NEUTRAL |
| | CONDUCTORS FOR ALL NON-LINEAR CIRCUITS. PLEASE SEE ALL |
| | CIRCUITS WHICH CONTAIN THESE LOADS SHALL MEET THE |
| | SIZING REQUIREMENTS TO HANDLE AND ALLEVIATE THE OVER |
| | LOADING OF THE NEUTRAL ON A 3-PHASE 4-WIRE SYSTEM WITH |
| | PREDOMINATELY OR ACTUALLY IN MANY CASES ALL NON-LINEAR |
| | LOADS. PLEASE SEE THIS CAN BE DONE BY USING MANY |
| | METHODS, K-RATED TRANSFORMERS, FULL NEUTRAL LOAD |
| | CALCULATION ON EACH CIRCUIT AND FEEDERS BASED ON ALL |
| | NON-LINEAR LOADS OR THE SIZING OF THE NEUTRAL(S) AT |
| | 200%. |
| | PLEASE SEE THE RISK OF FIRE, LIFE SAFETY AND CAUSE TO |
| | PROPERTY DAMAGE CAN BE SUBSTANTIAL AND IT IS THE |
| | CONCERN OF THE OFFICE BASED ON OUR INFORMATION KNOWN |
| | AND PLEASE SEE STUDIES IN WHITE PAPERS FROM NUMEROUS |
| | MANUFACTURES OF ELECTRONIC/COMPUTER EQUIPMENT WHICH |
| | INDICATE AS MUCH AS 1.7 TIMES THE RATED LOAD OF THE |
| | CONDUCTOR OR CIRCUIT AND FEEDERS. |
| | PLEASE SEE THE FOLLOWING CODES: THIS OFFICE IS AWARE OF |
| | WHAT A FPN MEANS, HOWEVER SEE SOME SECTIONS GIVEN WHICH |
| | DO NOT CONTAIN FPN.PLEASE SEE 210.4A (FPN), 220.22 |
| | (FPN(2), 310.10, 310.15B4(C), 400.5, 520.44, 408.16, |
| | AND FBC 104.6ADMINISTRATIVE SECTION AS ADOPTED BY THE |
| | CITY OF WEST PALM BEACH. |
| | PLEASE PROVIDE MORE INFORMATION ON WHAT STEPS WILL BE |
| | TAKEN TO ALLEVIATE THESES RISKS. |
| | |
| | 8) NOTE: PLEASE SEE PANEL "HA", THE AIC RATING AS SHOWN |
| | IS BEING SHOWN AT 35K WHICH IS OK; HOWEVER IS THIS FOR |
| | ALL BRANCH BREAKERS? |
| | 110.9, |
| | FBC 106.1.2 ADMIN SECTION |
| | |
| | 9) NOTE: PLEASE SHOW/ INDICATE ANY AND ALL SMOKE |
| | DETECTION DEVICES ON PLANS (SHOWN) AND NOTE FOR BEING |
| | CONNECTED. SEPARATE PERMIT PLANS. |
| | PLEASE SEE FBC 11-4.28.2, .3(4) FOR ANY HORN AND STROBE |
| | DEVICES. PLEASE BE SURE THESE STATE THE MINIMUM |
| | LEVELS. |
| | 75CD FOR STROBES. |
| | |
| | 10) NOTE: PLESE ADJUST THE PERMIT APPLICATION FOR SCOPE |
| | OF WORK. |
| | |
| | ** PLEASE KNOW, PLANS PERMIT APPLICATION, MANUFACTURE |
| | SPECS/CUT SHEETS WILL BE REQUIRED FOR THE FUTURE |
| | EQUIPMENT FOR THE ROOM. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |