Plan Review Details - Permit 06071219
Plan Review Stops For Permit 06071219
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-08-18 Cont ID  
Sent By amorse Date 2007-08-18 Time 09:15 Rev Time 0.00
Received By amorse Date 2007-08-18 Time 09:15 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-10-23 Cont ID  
Sent By amorse Date 2006-10-23 Time 07:35 Rev Time 0.00
Received By amorse Date 2006-10-23 Time 07:35 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-15 Cont ID  
Sent By amorse Date 2006-09-15 Time 13:30 Rev Time 0.00
Received By amorse Date 2006-09-15 Time 13:30 Sent To  
Notes
2006-09-15 00:00:00 
  
  
 DENIED
  
 1) DUE TO OWNER REVISION ON A1.0 NOTE #1
 WALL TILE WAS REMOVED FROM SCOPE OF WORK
 PLEASE PROVIDE INFORMATION THAT SHOWS
 THE REQUIRED SMOOTH, HARD, NON ABSORBENT
 SURFACE WITHIN 2 FEET OF URINALS AND
 WATER CLOSETS UP TO A HEIGHT OF 4 FEET.
 PER 1210 FBC
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-07 Cont ID  
Sent By amorse Date 2006-08-07 Time 08:50 Rev Time 0.00
Received By amorse Date 2006-08-07 Time 08:50 Sent To  
Notes
2006-08-07 00:00:00 
  
 DENIED
  
 1) PROVIDE BLDG CONSTRUCTION TYPE AND
 OCCUPANCY ON DRAWINGS
  
 2) ITEM 22 ON D1.0 IS NOT USED ON THE
 DEMOLITION PLAN AS IT WAS ON THE WEST
 TOWER. PLEASE CLARIFY ARE NEW DOORS TO
 BE INSTALLED IN THIS LOCATION AS
 REQUIRED BY 707.14.1 FBC
  
 3) CORRECT THE FOLLOWING ON A5.O
  
 A) PROVIDE NOTE THAT ALL WOOD FURRING TO
 BE FIRE RETARDANT OR REFFER TO NOTE #33
 IN GENERAL NOTES
  
 4) TITLE BLOCK ADDRESS SHALL GIVE
 LOCATION OF WORK (12TH FLOOR LOBBY)
  
 5) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-07-31 Cont ID  
Sent By dpalmer Date 2007-07-31 Time 15:02 Rev Time 0.00
Received By dpalmer Date 2007-07-31 Time 14:47 Sent To PC
Notes
2007-07-31 15:07:39OK, STAMPED REV.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-23 Cont ID  
Sent By dpalmer Date 2006-10-23 Time 07:13 Rev Time 0.00
Received By dpalmer Date 2006-10-23 Time 07:13 Sent To  
Notes
2006-10-23 07:13:37OK,,STAMPED THREE SETS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-14 Cont ID  
Sent By dpalmer Date 2006-09-14 Time 16:37 Rev Time 0.00
Received By dpalmer Date 2006-09-14 Time 15:49 Sent To  
Notes
2006-09-14 00:00:00***UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE COMMENTS BELOW ARE TAKEN
 DIRECLTY FROM PREVIOUS REVIEW.
 PLEASE SEE PLANS ARE ALSO ALRADY COMING
 BACK DUE TO COMMENTS FROM OTHER TRADES.
  
 1) NOTE: OK.
  
 2) NOTE: NO.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE THE CURRENT
 CODES ARE REFLECTED.
 2002 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-05 Cont ID  
Sent By dpalmer Date 2006-08-05 Time 12:25 Rev Time 0.00
Received By dpalmer Date 2006-08-05 Time 12:25 Sent To  
Notes
2006-08-05 00:00:00***UNSAT ***
  
 1) NOTE: PLEASE HAVE ENGINEER OF RECORD
 SIGN PLANS WITH SIGNATURE AS RECONIZED
 AND ON FILE WITH THE OFFICE.
 FS 471.025
  
 2) NOTE: PLEASE BE SURE THE CURRENT
 CODES ARE REFLECTED.
 2002 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-09-19 Cont ID  
Sent By mawillia Date 2006-09-19 Time 13:57 Rev Time 0.00
Received By mawillia Date 2006-09-19 Time 13:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-08-11 Cont ID  
Sent By mwennerg Date 2006-08-11 Time 10:16 Rev Time 0.00
Received By mwennerg Date 2006-08-11 Time 10:15 Sent To  
Notes
2006-08-11 00:00:00***APPROVED***
  
 1) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 2) PLEASE PROVIDE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS IN TERMS OF CLASS A,B,ORC AND
 INDICATE ON PLANS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-07 Cont ID  
Sent By ssherman Date 2007-08-07 Time 17:49 Rev Time 0.00
Received By ssherman Date 2007-08-07 Time 17:49 Sent To B
Notes
2007-08-07 17:50:04TO ADRIANS DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-18 Cont ID  
Sent By adarroug Date 2007-07-18 Time 13:33 Rev Time 0.00
Received By adarroug Date 2007-07-18 Time 13:33 Sent To  
Notes
2007-07-26 14:25:25TO "BOB"#11
2007-07-18 13:34:03WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-12 Cont ID  
Sent By adarroug Date 2006-10-12 Time 10:29 Rev Time 0.00
Received By adarroug Date 2006-10-12 Time 10:29 Sent To  
Notes
2006-10-20 14:51:38TO 'AMORSE "DESK/RESUB--NEEDS BLDG AND ELEC.OTHER
 BLDG PERMIT FOR SAME PROJECT ON "BOB"
2006-10-12 10:29:44WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-09 Cont ID  
Sent By adarroug Date 2006-09-09 Time 19:34 Rev Time 0.00
Received By adarroug Date 2006-09-09 Time 19:34 Sent To  
Notes
2006-09-13 00:00:00TO "BOB"#4
2006-09-09 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-14 Cont ID  
Sent By adarroug Date 2006-08-14 Time 15:38 Rev Time 0.00
Received By adarroug Date 2006-07-22 Time 12:01 Sent To  
Notes
2006-08-02 00:00:00TO "BOB"#5
2006-07-22 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-07-27 Cont ID  
Sent By tgordon Date 2007-07-27 Time 08:07 Rev Time 0.20
Received By tgordon Date 2007-07-27 Time 08:07 Sent To  
Notes
2007-07-27 08:08:20MECH. REVISION TO PAGE M2.1.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-09-15 Cont ID  
Sent By tgordon Date 2006-09-15 Time 10:30 Rev Time 0.20
Received By tgordon Date 2006-09-15 Time 10:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-08-09 Cont ID  
Sent By tgordon Date 2006-08-09 Time 10:28 Rev Time 0.20
Received By tgordon Date 2006-08-09 Time 10:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-10-03 Cont ID  
Sent By jleech Date 2006-10-03 Time 07:40 Rev Time 0.00
Received By jleech Date 2006-10-03 Time 07:40 Sent To  
Notes
2006-10-03 00:00:00PROVISO;
 DEMO PERMIT REQUIRED FOR PLUMBING.
 FIXTURE CHANGE OUT ONLY.

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-08-14 Cont ID  
Sent By pschmitz Date 2006-08-14 Time 15:31 Rev Time 0.00
Received By pschmitz Date 2006-08-14 Time 15:31 Sent To  
Notes
2006-08-14 00:00:00 
 PROVISO:
 EXACT CHANGE OUT
 PLUMBING DEMOLITION PERMIT REQUIRED

Review Stop Z ZONING
Rev No 1 Status N Date 2007-07-30 Cont ID  
Sent By choops Date 2007-07-30 Time 17:42 Rev Time 0.00
Received By choops Date 2007-07-30 Time 17:41 Sent To  
Notes
2007-07-30 17:42:08*VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.