| 2006-08-16 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | BUILDING |
| | FBC RFLORIDA BUILDING CODE 2004 |
| | RESIDENTIAL |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713.13.A NEW |
| | NOC WILL BE REQUIRED FOR THE NEW |
| | CONTRACTOR. |
| | |
| | 2.)THE CONTRACTOR HAS CARPENTRY |
| | CONTRACTOR AND A WINDOW AND DOOR |
| | CONTRACTOR LICENSES.THE SCOPE OF WORK |
| | FOR THIS PROJECT EXCEEDS THE SCOPE OF |
| | THESE LICENSES (DRYWALL, PAINT, MASONRY, |
| | CONCRETE, ETC.).SEE ATTACHED FOR WORK |
| | ALLOWED UNDER THESE LICENSES. |
| | |
| | 3.)WHEN APPLYING FOR PERMITS, ONLY |
| | REFER TO ONE LICENSE NUMBER.IF THE |
| | SCOPE OF WORK INCLUDES BOTH LICENSES, |
| | TWO PERMIT APPLICATIONS SHOULD BE |
| | COMPLETED WITH TWO DIFFERENT PERMIT |
| | NUMBERS GENERATED. |
| | |
| | 4.)A WINDOW AND DOOR PERMIT HAS BEEN |
| | ISSUED FOR THIS ADDRESS.THE PLANS SHOW |
| | THE WINDOWS AND DOORS AS EXISTING.NOTE |
| | THAT AS THE CONTRACTOR DID NOT ADVISE |
| | THAT THERE WAS TO BE A CHANGE OF |
| | OCCUPANCY, THE CONTRACTOR IS PROCEEDING |
| | AT HIS OR HER OWN RISK AS THAT PLAN WAS |
| | NOT REVIEWED FOR ACCESSIBILITY, TABLE |
| | 602, AND EGRESS REQUIREMENTS. |
| | |
| | 5.)THE PLANS STATE THAT THIS IS A |
| | REMODEL MODIFICATION OF AN EXISTING |
| | RESIDENCE TO DR. SCHWARZ PSYCHIATRY |
| | FUNCTION.THIS IS A CHANGE OF |
| | OCCUPANCY, FROM R3 TO BUSINESS.REMOVE |
| | ALL REFERENCES TO RESIDENCES AND |
| | RESIDENTIAL CODE FROM THE PLAN AS THEY |
| | DO NOT APPLY TO THIS JOB.CHANGE OF |
| | OCCUPANCY IS TO COMPLY WITH ALL |
| | REQUIREMENTS OF FLORIDA BUILDING CODE |
| | 2004 EXISTING BUILDING CODE, CHAPTERS 5 |
| | THROUGH 8 AND FLORIDA BUILDING CODE |
| | 2004, BUILDING, 11-4.1.6. |
| | |
| | 6.)MANY OF THE NOTES ON THE SITE PLAN |
| | DO NOT APPLY TO THIS JOB.REMOVE FROM |
| | THE PLAN. |
| | |
| | 7.)PROVIDE A CODE SUMMARY OF THE |
| | EXISTING BUILDING; BUILDING HEIGHT, |
| | CONSTRUCTION TYPE INCLUDING A OR B FBC |
| | 6, FIRE SPRINKLER INFORMATION, GOVERNING |
| | CODE INCLUDING FBC EB, OCCUPANCY FBC3. |
| | |
| | |
| | 8.)PROVIDE AREA CALCULATIONS FOR THE |
| | STORAGE AREAS.SEE FBC302.1.1, 302.2, |
| | AND TABLE 302.1.1. |
| | |
| | 9.)PROVIDE AREA CALCULATIONS; |
| | EXISTING, PROPOSED NEW, NEW TOTAL.IT |
| | APPEARS THAT YOU ARE CONVERTING |
| | UNINHABITABLE SPACE TO BECOME HABITABLE; |
| | THE AREA CALCULATIONS SHOULD REFLECT |
| | THIS.THIS IS USED FOR ASSESSMENT OF |
| | IMPACT FEES BY PALM BEACH COUNTY. |
| | FAILURE TO PROPERLY ADDRESS THIS WILL |
| | RESULT IN DELAYS.IF YOU DO NOT |
| | UNDERSTAND WHAT IS REQUIRED, PLEASE |
| | CONTACT ME. |
| | |
| | 10.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, CHANGE OF USE.233-5025 |
| | FOR MORE INFORMATION. |
| | |
| | 11.)SHOW COMPLIANCE WITH FBC TABLE |
| | 503. |
| | |
| | 12.)PROVIDE A COPY OF THE SURVEY OF |
| | THIS PROPERTY SO THAT FBC TABLE 601 |
| | COMPLIANCE CAN BE DETERMINED, |
| | FBC*106.3.4, FBC EB812.1, FBC704, |
| | FBC704.5. |
| | |
| | 13.)INFORMATIONAL ONLY; DUE TO THE |
| | LACK OF INFORMATION ON THE PLAN, A |
| | SECOND ROUND OF COMMENTS IS LIKELY. |
| | |
| | 14.)THE SITE PLAN IS NOT SIGNED AND |
| | SEALED.THIS IS REQUIRED AS THIS PAGE |
| | IS REQUIRED TO SHOW CODE COMPLIANCE. |
| | |
| | 15.)THE SITE PLAN HAS A NOTE, SUBJECT |
| | MEDICAL USE SHALL BE LIMITED USE PER |
| | TYPE 1 CATEGORY.WHAT DOES THIS MEAN? |
| | |
| | 16.)THE SITE PLAN DOES NOT PROVIDE A |
| | DESIGNATION FOR THE REAR BUILDING.IT |
| | APPEARS TO BE A GARAGE.CLEARLY |
| | INDICATE USE FOR THIS STRUCTURE, FBC11. |
| | |
| | 17.)THE REROOF PERMIT FOR THE HOUSE |
| | AND GARAGE ARE EXPIRED, PERMIT NUMBER |
| | 99081195.PLEASE ADDRESS. |
| | |
| | 18.)THE SITE PLAN DOES NOT SHOW THE |
| | EXIT RAMP SHOWN ON SHEET 2. |
| | |
| | 19.)GENERAL PROJECT NOTES DESIGN |
| | CRITERIA REFERS TO 3 SECOND GUESTS. |
| | PLEASE REVISE.IT APPEARS THAT YOU ARE |
| | STATING WIND DESIGN CRITERIA, SEE |
| | FBC1603.1.4 AND PROVIDE ALL INFORMATION. |
| | |
| | 20.)HAS RAUL LESCANO PE SIGNED THE |
| | PLANS?SEE FAC61G15-23.002.IT APPEARS |
| | THAT SOMEONE ELSE HAS SIGNED ON HIS |
| | BEHALF.THE ENGINEER IS TO SIGN, SEAL, |
| | AND DATE ALL DOCUMENTS. |
| | |
| | 21.)ARE THE ROOM DESIGNATIONS LABELED |
| | CORRECTLY?THE EXISTING SHOWS A WAITING |
| | ROOM, NOW A SITTING ROOM.THIS DOES NOT |
| | APPEAR APPROPRIATE FOR BUSINESS USE. |
| | THERE ARE TWO EXISTING SECOND FLOOR |
| | PLANS.NO KITCHEN IS SHOWN ANYWHERE ON |
| | THE PLAN, NO BATHTUB OR SHOWER IS SHOWN. |
| | IF THIS IS CURRENTLY A RESIDENCE, ISN?T |
| | THERE A KITCHEN AND BATH WHICH REQUIRES |
| | DEMOLITION?PLEASE LABEL ALL ROOMS |
| | CORRECTLY AS TO USE AND REVISE PLANS TO |
| | ADDRESS INCONSISTENCIES. |
| | |
| | 22.)WHAT WILL BE STORED IN THE STORAGE |
| | ROOM? |
| | |
| | 23.)PRODUCT APPROVALS ARE TO BE |
| | APPROVED BY DESIGNER OF RECORD, |
| | FBC*106.3.3. |
| | |
| | 24.)DECLARE AN OCCUPANCY, FBC 3. |
| | |
| | 25.)DECLARE OCCUPANT LOAD, FBC1004. |
| | |
| | 26.)DECLARE OCCUPANT LOAD FOR THE |
| | SECOND FLOOR.VERTICAL ACCESSIBILITY |
| | REQUIRED UNLESS EXCEPTED, FBC11-4.1.6. |
| | GENERAL PROJECT NOTES STATES THAT AN |
| | ELEVATOR WILL BE INSTALLED BUT NONE |
| | SHOWN ON THE PLAN. |
| | |
| | 27.)PARKING IS TO COMPLY WITH CITY OF |
| | WEST PALM BEACH STANDARD, SEE ATTACHED. |
| | PROVIDE A DETAIL ON THE PLAN. |
| | |
| | 28.)SHOW THE ACCESSIBLE ROUTE FROM THE |
| | PUBLIC WAY, FBC11-4.1.2(1).PROVIDE |
| | WIDTH, ELEVATION CHANGES. |
| | |
| | 29.)SHOW THE ACCESSIBLE ROUTE FROM THE |
| | ACCESSIBLE PARKING SPACE IN THE REAR TO |
| | THE OFFICE.THE ACCESSIBLE PARKING |
| | SPACE IS TO COMPLY WITH FBC11-4.6.2.NO |
| | ACCESS AISLE IS SHOWN FBC11-4.3, NO |
| | DETAIL FOR THE ACCESSIBLE PARKING |
| | PROVIDED. |
| | |
| | 30.)IT IS NOT CLEAR WHY THE RAMP GOES |
| | TO A STORAGE ROOM; IS THIS A LOADING |
| | RAMP RATHER THAN A RAMP FOR |
| | ACCESSIBILITY, FBC1 1-4.8?ACCESSIBLE |
| | RAMPS ARE TO HAVE A LANDING AT THE TOP |
| | AND BOTTOM, FBC11-4.8.4. |
| | |
| | 31.)MEANS OF EGRESS CANNOT GO THROUGH |
| | A BATHROOM (A ROOM THAT CAN BE LOCKED) |
| | OR ASTORAGE ROOM, FBC1013.2.IT IS |
| | NOT CLEAR WHERE THE ACCESSIBLE ENTRANCE |
| | IS. |
| | |
| | 32.)PROVIDE A LIFE SAFETY PLAN FOR |
| | BOTH THE FIRST AND SECOND FLOOR.THE |
| | DIMENSIONS FOR ALL MEANS OF EGRESS WHICH |
| | ARE CURRENTLY SHOWN AS EXISTING IS |
| | REQUIRED; DOORWAYS, STAIRS, FBC CHAPTER |
| | 10.OVERALL DIMENSIONS ARE NOT SHOWN ON |
| | THE FLOOR PLAN. |
| | |
| | 33.)SHOW EXIT LIGHTS IN COMPLIANCE |
| | WITH FBC1006.3. |
| | |
| | 34.)PROVIDE A DETAIL AND A SECTION FOR |
| | THE EXISTING STAIRS SHOWING CONSTRUCTION |
| | AND ALL DIMENSIONS, INCLUDING HEAD |
| | CLEARANCE AND LANDING SIZE, FBC 1009, |
| | FBC11-4.9. |
| | |
| | 35.)PROVIDE A HANDRAIL AND GUARDRAIL |
| | (IF APPLICABLE) DETAIL FOR THE STAIRS, |
| | FBC1012, FBC1009, FBC11-4.9.4. |
| | |
| | 36.)THE ENTRY DOOR DOES NOT APPEAR TO |
| | COMPLY WITH FBC11-4.13.4, DOUBLE-LEAF |
| | DOORWAYS. |
| | |
| | 37.)SECOND FLOOR EXISTING BATH IS TO |
| | BE ACCESSIBLE.PROVIDE ALL DETAILS, ALL |
| | DIMENSIONS, FOR BOTH BATHROOMS, FIRST |
| | AND SECOND FLOOR, RELATED TO |
| | ACCESSIBILITY; TOILET, GRAB BARS, |
| | TURNING RADIUS, SINK, CLEAR FLOOR SPACE |
| | FOR FIXTURES. |
| | |
| | 38.)THE SECOND FLOOR BATH DOOR |
| | ENCROACHES INTO THE CLEAR FLOOR SPACE |
| | FOR THE SINK, FBC11-4.24.5. |
| | |
| | 39.)AN EXISTING A/C VENT IS SHOWN IN |
| | THE NEW BATH.IS THIS IN THE FLOOR? |
| | GRATING IS TO COMPLY WITH FBC11-4.5.4. |
| | |
| | 40.)DOORS ARE TO COMPLY WITH |
| | MANEUVERING CLEARANCE, FBC11-4.13.6, FBC |
| | FIGURE 11-25.THE FOLLOWING DOORS DO |
| | NOT APPEAR TO COMPLY WITH THE PULL SIDE |
| | MANEUVERING CLEARANCE REQUIREMENT; FIRST |
| | FLOOR STORAGE EXTERIOR NEW DOOR, NEW |
| | BATH EXTERIOR DOOR, SECOND FLOOR |
| | EXISTING SITTING ROOM, EXISTING LIBRARY |
| | CLOSET DOOR. |
| | |
| | 41.)HOW DOES THE LINTEL TIE INTO THE |
| | EXISTING?AS DRAWN, IT SITS ON TOP OF |
| | TWO NEW COLUMNS BUT IS NOT STRUCTURALLY |
| | CONNECTED. |
| | |
| | 42.)PROVIDE DESIGN LOAD INFORMATION |
| | FOR THE LINTEL, LINTEL SIZE AND REBAR |
| | INFORMATION. |
| | |
| | 43.)PROVIDE DESIGN LOAD INFORMATION |
| | FOR THE FIRST FLOOR, SECOND FLOOR, AND |
| | STAIRS.CERTIFY THAT THE EXISTING |
| | FLOORS AND STAIRS COMPLY WITH THE NEW |
| | DESIGN LOAD REQUIREMENTS. |
| | |
| | 44.)FBC*110.1.1, CERTIFICATE OF |
| | OCCUPANCY REQUIRED AS THIS IS A CHANGE |
| | FROM R3 TO B. |
| | |
| | 45.)INFORMATIONAL - CODE COMPLIANCE |
| | CANNOT BE SHOWN BY REFERRING TO CODE |
| | SECTIONS ONLY.DESIGNER IS TO PROVIDE |
| | DESIGN CRITERIA WITH DETAILS, NOT CODE |
| | REFERENCES. |