Plan Review Details - Permit 06071187
Plan Review Stops For Permit 06071187
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-26 Cont ID  
Sent By adarroug Date 2006-08-26 Time 16:08 Rev Time 0.00
Received By adarroug Date 2006-08-26 Time 16:08 Sent To M
Notes
2006-08-26 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-21 Cont ID  
Sent By adarroug Date 2006-08-21 Time 11:35 Rev Time 0.00
Received By adarroug Date 2006-08-21 Time 11:35 Sent To M
Notes
2006-08-21 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-26 Cont ID  
Sent By tgordon Date 2006-07-26 Time 11:59 Rev Time 0.00
Received By tgordon Date 2006-07-22 Time 11:22 Sent To  
Notes
2006-07-22 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-09-01 Cont ID  
Sent By tgordon Date 2006-09-01 Time 09:27 Rev Time 0.45
Received By tgordon Date 2006-09-01 Time 11:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-08-22 Cont ID  
Sent By tgordon Date 2006-08-22 Time 08:40 Rev Time 0.45
Received By tgordon Date 2006-08-22 Time 08:40 Sent To  
Notes
2006-08-22 00:00:00*** DENIED ***
 1) MECHANICAL PLANS HAVE TO MUCH
 ELECTRICAL PLAN DETAIL ON THEM AND THE
 DUCT LAY-OUT IS FADED AND DIFFICULT TO
 READ, PLEASE SUBMIT A MECHANICAL PLAN
 NOT A ELECTRICAL PLAN. AS NOTED IN LAST
 REVIEW 7-26-06. CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY. PER 2004
 FBC 106.1.1 .
  
 2) AS NOTED IN LAST REVIEW 7-26-06. A/C
 DUCT LAY-OUT ON FIRST FLOOR IS NOT
 DESIGNED PROPERLY. WHAT TYPE OF DUCTS
 ARE BEING USED? ROUND METAL, IF SO SHOW
 ALL TRANSITIONS AND SIZE CHANGES.
 RECTANGULAR, IF SO SHOW DUCT DIMENSIONS
 12"X ?" . OR FLEX DUCTS, IF SO SHOW ALL
 MIXING BOXES.
  
 3) NEED TO SHOW THE CFM'S AT ALL SUPPLY
 AIR GRILLS.
  
 4) ONE 12" SUPPLY AIR DUCT LEAVING AHU
 #1 IS NOT ENOUGH, PLEASE CORRECT OR
 SUBMIT A MANUAL D CALCULATIONS FOR
 RESIDENTIAL DUCT DESIGN, PER 2004 FBC/R
 M1601.1 AND FBC 13-610.1.ABC.1 .
  
 5) AND AGAIN, CONSTRUCTION DOCUMENTS
 (PLANS) SHALL BE OF SUFFICIENT CLARITY.
 PER 2004 FBC 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-26 Cont ID  
Sent By tgordon Date 2006-07-26 Time 11:15 Rev Time 0.35
Received By tgordon Date 2006-07-26 Time 11:15 Sent To  
Notes
2006-07-26 00:00:00*** DENIED ***
 1) MECHANICAL PLAN DUCT LAY-OUT AND
 EQUIPMENT LISTING IS FADED AND DIFFICULT
 TO READ. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY. PER 2004 FBC
 106.1.1 .
  
 2) PLANS SHOW TWO DIFFERENT A/C
 EQUIPMENT LISTINGS, PLEASE CORRECT. ALSO
 HAVE EQUIPMENT LISTING SHOW HEATER
 SIZE(KW), TOTAL COOLING BTU'S, AND
 SENSIBLE BTU'S.
  
 3) SUPPLY AIR DUCT AND GRILL TO SECOND
 FLOOR BATHROOM NEEDS TO BE SIZED.
  
 4) SECOND FLOOR BATHROOM AND MASTER
 BATHROOM WATER CLOSET NEED EXHAUST FANS,
 PER 2004 FBC/R M1506 .
  
 5) RETURN AIR DUCT IN MASTER BEDROOM
 NEEDS TO BE 12", PER 2004 FBC/R M1602.4
  
 6) A/C DUCT LAY-OUT ON FIRST FLOOR IS
 NOT DESIGNED PROPERLY PLEASE CORRECT.
 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY. PER 2004 FBC 106.1.1
 .
  
 7) PROVIED RETURN AIR FOR FIRST FLOOR
 AIR HANDLER.
  
 8) MANUAL J CAALCULATIONS ARE ONLY
 CALLING FOR ONE A/C SYSTEM, PLANS ARE
 CALLING FOR TWO A/C SYSTEMS, THE TWO
 MUST COINCIDE, PLEASE CORRECT.
  
 9) ENERGY CALCULATIONS NEED TO BE ON
 FORM 600A-04 (2004) PER FBC 13-600.3.A .
  
 10) ENERGY CALCULATIONS NEED TO BE
 SIGNED BY OWNER/AGENT, PER 2004 FBC
 13-600.3.ABC.2
  
 11) MECHANICAL PLANS HAVE AN ENGINEER'S
 NAME IN THE TITLE BLOCK, THEREFORE
 REQUIRE HIS SEAL AND SIGNATURE, PER FAC
 61G15-23.002 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.