Plan Review Details - Permit 06071166
Plan Review Stops For Permit 06071166
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mjacobs Date 2006-09-20 Time 07:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-08-05 Cont ID  
Sent By mjacobs Date 2006-08-05 Time 13:21 Rev Time 0.00
Received By mjacobs Date 2006-08-05 Time 09:37 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-09-17 Cont ID  
Sent By dpalmer Date 2006-09-17 Time 12:42 Rev Time 0.00
Received By dpalmer Date 2006-09-17 Time 12:42 Sent To PC
Notes
2006-09-17 00:00:00REDLINED PLANS,
  
 ALL OVERHEAD ELECTRICAL LINES, UTILITY
 OR OTHER WISE SHALL MEET THE MIN
 CLEARANCES AS REQUIRED PER 680.8

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-09-11 Cont ID  
Sent By dpalmer Date 2006-09-11 Time 18:12 Rev Time 0.00
Received By dpalmer Date 2006-09-11 Time 17:21 Sent To PC
Notes
2006-09-11 00:00:00**** UNSAT 3RD REVIEW ******
  
 1) NOTE: PLEASE SEE COMMENTS FROM TWO
 PREVIOUS REVIEWS.
 PLEASE SEE THE SPECS ON THE HEAT PUMP
 STILL DO NOT INDICATE WHICH ONE IS BEING
 USED/PROPOSED AND NONE OF THE UNITS ON
 THE SPECS SUBMITTED CORRELATE WITH THE
 LOAD CALCULATIONS SUBMITTED.??
 THE LOAD CALCULATIONS DONE BY THE
 ELECTRICAL CONTRACTOR ARE OK, HOWEVER
 THEY DO NOT CORRELATE.
  
 2) NOTE: PLEASE PREVIOUS REVIEW WHICH
 REQUESTED ALL "EXISTING/OLD/VOIDED"
 SHEETS TO BE COMPLETELY REMOVED FROM
 SETS, AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
 PLEASE SEE THE OLD LOAD CALCULATIONS ARE
 STILL IN SETS.
 THIS WAS NOT DONE.
 PLEASE ALSO SEE THAT TWO COPIES OF ALL
 PLANS/DRAWINGS ETC ARE REQUIRED AT A
 MINIMUM. PLEASE SEE ONLY ONE COPY OF THE
 REVISED PANEL SCHEDULE/LOAD CALCULATIONS
 WAS SUBMITTED. (UP TO 3 SETS MAY BE
 SUBMITTED).
 FBC 106.1.2, 106.1, ADMINSECT AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-20 Cont ID  
Sent By dpalmer Date 2006-08-20 Time 11:55 Rev Time 0.00
Received By dpalmer Date 2006-08-20 Time 11:53 Sent To PC
Notes
2006-08-20 00:00:00*** UNSAT 2ND REVIEW **
  
 1) NOTE: PLEASE SEE THE NOTES FROM
 PREVIOUS REVIEW AS THESE ARE THE SAME
 WHICH STILL NEED TO BE ADDRESSED.
 PLEASE SEE THAT THE EXACT SMAE PLANS
 SUBMITTED FOR THE PREVIOUS REVIEW WERE
 SUBMITTED BACK. NO CHANGES WERE MADE.
  
 2) NOTE: PLEASE CORRELATE HEAT PUMP ON
 CALCULATIONS WITH THE SPECS SUBMITTED.
  
 3) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE
 COMPLIANCE.
  
 ** ALL NOTES FROM FIRST REVIEW STILL
 STAND. SEE THESE ARE BEING ATTACHED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-28 Cont ID  
Sent By dpalmer Date 2006-07-28 Time 20:53 Rev Time 0.00
Received By dpalmer Date 2006-07-28 Time 20:45 Sent To P
Notes
2006-07-28 00:00:00****** UNSAT ******
  
 1) NOTE: PLEASE PROVIDE INFORMATION FOR
 POOL PUMP AND HEAT PUMP IF THE LOADS
 SHOWN ARE ALREADY FIGURED AT 125% FOR
 CONTINUOUS LOADS.
 215.3,230.42 ETC.
  
 2) NOTE: PLEASE SEE WIRING DIAGRAM SHOWS
 A NEW POOL PANEL, PLEASE LIST THE OCP
 FEEDING NEW PANEL ALONG WITH THE SIZE OF
 PANEL.
 PLEASE COMPLETEA POOL SUB PANEL
 SCHEDULE FOR NEW BRANCH CIRCUITS, OCP
 AND WIRES SIZES. THIS MAY BE DONE BY THE
 ELECTRICAL CONTRACTOR AND ATTACHED LIKE
 THE LOAD CALCULATIONS ARE.
 240.4,310.16,408.4
  
 3) NOTE: PLEASE SEE WIRING DIAGRAM FOR
 POOL HEATER DOES NOT INCLUDE ANY
 CONDUCTOR SIZES. PLEASE CORRELATE WITH
 THE ELECTRICAL PANEL SCHEDULE AND SHOW
 ON PLANS.
 106.1.2 FBC ADMIN SECT, 240.4,310.16
 ETC.
  
 4) NOTE: PLEASE BES URE THE ADDTIONAL
 SHEETS FOR LOAD CALCULATIONS AND PANEL
 SCHEDULE CONTAINS THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 PLANS/DESIGN/CALCS ETC.
 FBC 106.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-19 Cont ID  
Sent By adarroug Date 2006-09-19 Time 11:42 Rev Time 0.00
Received By adarroug Date 2006-09-19 Time 11:42 Sent To B
Notes
2006-09-19 00:00:00TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-05 Cont ID  
Sent By adarroug Date 2006-09-05 Time 10:04 Rev Time 0.00
Received By adarroug Date 2006-09-05 Time 10:04 Sent To E
Notes
2006-09-05 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-16 Cont ID  
Sent By adarroug Date 2006-08-16 Time 14:36 Rev Time 0.00
Received By adarroug Date 2006-08-16 Time 14:36 Sent To E
Notes
2006-08-16 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-08-05 Time   Rev Time 0.00
Received By adarroug Date 2006-07-28 Time 09:49 Sent To  
Notes
2006-07-28 00:00:00TO "E" BOX

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-08-02 Cont ID  
Sent By mperson Date 2006-08-02 Time 08:23 Rev Time 0.33
Received By mperson Date 2006-08-02 Time 08:23 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-09-20 Cont ID  
Sent By mmclean Date 2006-09-20 Time 10:33 Rev Time 0.00
Received By mmclean Date 2006-09-20 Time 10:33 Sent To B
Notes
2006-09-20 00:00:00POOL BARRIER.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-07-23 Cont ID  
Sent By mmclean Date 2006-07-23 Time 12:59 Rev Time 0.00
Received By mmclean Date 2006-07-23 Time 12:59 Sent To I
Notes
***NONE***