| Plan Review Stops For Permit 06071062 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-12-01 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-12-01 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-12-01 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2006-12-01 14:10:57 | DENIED | | | | | | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF | | | THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT SET OF | | | PLANS MUST BE STAMPED BY THAT OFFICE, | | | AND A COPY OF THE PAID RECEIPT ATTACHED | | | TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025 | | | FOR MORE INFORMATION. | | | | | | 3.SELECT ASSEMBLY ON BITUMEN ROOF | | | PRODUCT APPROVAL.NOTE:FLAT ROOF PRODUCT APPROVALS | | | NOT SUBMITED.SUBMIT FLAT ROOF PRODUCT APPROVAL, | | | SELECT THE ASSEMBLY USED AND SUBMIT THE FOLLOWING STATE | | | PRODUCT APPROVAL INFORMATION. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | | | | 4.R401.3 DRAINAGE. | | | SURFACE DRAINAGE SHALL BE DIVERTED TO A | | | STORM SEWER CONVEYANCE OR OTHER APPROVED | | | POINT OF COLLECTION SO AS TO NOT CREATE | | | A HAZARD. LOTS SHALL BE GRADED SO AS TO | | | DRAIN SURFACE WATER AWAY FROM FOUNDATION | | | WALLS. THE GRADE AWAY FROM FOUNDATION | | | WALLS SHALL FALL A MINIMUM OF 6 INCHES | | | WITHIN THE FIRST 10 FEET. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. SUBMIT ONE COPY OF | | | OLD PAGES FOR REFERENCE . A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET | | | OR SPECIFICATION PAGE WHERE THE CHANGES | | | CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | CONSTRUCTION SERVICES DEPARTMENT | | | BUILDING PLANS EXAMINER | | | 561-805-6672 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-07-31 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-07-31 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-07-31 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2006-07-31 00:00:00 | DENIED | | | | | | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF | | | THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT SET OF | | | PLANS MUST BE STAMPED BY THAT OFFICE, | | | AND A COPY OF THE PAID RECEIPT ATTACHED | | | TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025 | | | FOR MORE INFORMATION. | | | | | | 3.BASED ON ICC BUILDING VALUATION DATA | | | THE PERMIT VALUE HAS BEEN REVISED TO | | | $34,243.00.ADDITIONAL PERMIT FEES ARE | | | DUE. | | | | | | 4.SQUARE FOOTAGE NOT ON APPLICATION. | | | | | | 5.SELECT ASSEMBLY ON BITUMEN ROOF | | | PRODUCT APPROVAL. | | | | | | 4.R401.3 DRAINAGE. | | | SURFACE DRAINAGE SHALL BE DIVERTED TO A | | | STORM SEWER CONVEYANCE OR OTHER APPROVED | | | POINT OF COLLECTION SO AS TO NOT CREATE | | | A HAZARD. LOTS SHALL BE GRADED SO AS TO | | | DRAIN SURFACE WATER AWAY FROM FOUNDATION | | | WALLS. THE GRADE AWAY FROM FOUNDATION | | | WALLS SHALL FALL A MINIMUM OF 6 INCHES | | | WITHIN THE FIRST 10 FEET. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. SUBMIT ONE COPY OF | | | OLD PAGES FOR REFERENCE . A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET | | | OR SPECIFICATION PAGE WHERE THE CHANGES | | | CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | CONSTRUCTION SERVICES DEPARTMENT | | | BUILDING PLANS EXAMINER | | | 561-805-6672 | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-11-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-11-30 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-11-30 |
Time |
07:55 |
Sent To |
M |
|
| Notes |
| 2006-11-30 08:00:54 | *** UNSAT *** | | | | | | *** PLEASE SEE NOTES FROM PREVIOUS REVIEWS WHICH STILL | | | NEED TO BE ADDRESSED. | | | | | | 1) NOTE:NO, PLEASE SEE PLANS ARE STILL SHOWING A NEW | | | ELECTRICAL RISER, YET PANEL SCHEDULE SHOWS AS EXISTING? | | | PLEASE SUBMIT A NEW RISER AS PREVIOUSLY NOTED OR IF | | | INDEED THIS IS AN EXISTING SERVICE PLEASE INDICATE | | | THIS. THE ELECTRICAL AS SHOWN FOR NEW BACK PORCH WHICH | | | IS REPLACING THE EXISTING BACK PORCH IS OK. | | | | | | PLEASE PROVIDE A COMPLETE ELECTRICAL RISER DIAGRAM FOR | | | NEW PROPOSED 200A SERVICE UPGRADE. | | | PLEASE SUBMIT AIC RATINGS, SEC'S, GROUNDING, CONDUITS | | | ETC. | | | PLEASE SHOW LOCATIONS OF PANEL(S) ON EXISTING/ NEW | | | HOUSE OR ADDITION. | | | PLEASE CLARIFY PANEL SCHEDULE WHICH MENTIONS "AS-BUILT" | | | , SHOW LOCATIONS OF ALL EQUIPMENT. | | | 110.26,240.24,215.5,250.50,110.9,310.16, | | | 240.4 ETC | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-07-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-27 |
Time |
20:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-27 |
Time |
20:39 |
Sent To |
M |
|
| Notes |
| 2006-07-27 00:00:00 | ****UNSAT **** | | | | | | 1) NOTE: PLEASE PROVIDE A COMPLETE | | | ELECTRICAL RISER DIAGRAM FOR NEW | | | PROPOSED 200A SERVICE UPGRADE. | | | PLEASE SUBMIT AIC RATINGS, SEC'S, | | | GROUNDING, CONDUITS ETC. | | | PLEASE SHOW LOCATIONS OF PANEL(S) ON | | | EXISTING/ NEW HOUSE OR ADDITION. | | | PLEASE CLARIFY PANEL SCHEDULE WHICH | | | MENTIONS "AS-BUILT" , SHOW LOCATIONS OF | | | ALL EQUIPMENT. | | | 110.26,240.24,215.5,250.50,110.9,310.16, | | | 240.4 ETC | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-11-29 |
|
|
Cont ID |
|
| Sent By |
mmiller |
Date |
2006-11-29 |
Time |
17:16 |
Rev Time |
0.00 |
| Received By |
mmiller |
Date |
2006-11-29 |
Time |
17:16 |
Sent To |
E |
|
| Notes |
| 2006-11-29 17:16:44 | SENT TO DEWEY PALMER'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-11-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-11-17 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-11-17 |
Time |
16:15 |
Sent To |
Z |
|
| Notes |
| 2006-11-17 16:16:44 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-07-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-07-27 |
Time |
16:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-07-27 |
Time |
16:49 |
Sent To |
E |
|
| Notes |
| 2006-07-27 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-07-31 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-07-31 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-07-21 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2006-07-21 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-11-30 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-11-30 |
Time |
08:15 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2006-11-30 |
Time |
08:15 |
Sent To |
B |
|
| Notes |
| 2006-11-30 08:18:03 | *** DENIED *** | | | 1) IF NO MECHANICAL (A/C) WORK IS TO BE DONE THAN YOU | | | MUST HAVE MECHANICAL PERMIT #06071065 VOIDED. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-07-28 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-07-28 |
Time |
08:40 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2006-07-28 |
Time |
08:40 |
Sent To |
P |
|
| Notes |
| 2006-07-28 00:00:00 | *** DENIED *** | | | 1) SHOW ON PLANS MINI-SPLIT A/C | | | CONDENSER UNIT LOCATION. | | | | | | 2) SHOW ON PLANS A/C EQUIPMENT LISTING | | | FOR A/C MINI-SPLIT SYSTEM. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2006-07-28 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2006-07-28 |
Time |
16:27 |
Rev Time |
0.22 |
| Received By |
mperson |
Date |
2006-07-28 |
Time |
16:27 |
Sent To |
B |
|
| Notes |
| 2006-07-28 00:00:00 | NOTE: NO PLUMBING WORK SHOWN ON PLANS |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2006-11-26 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-11-25 |
Time |
22:11 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-11-25 |
Time |
22:11 |
Sent To |
I |
|
| Notes |
| 2006-11-26 22:13:28 | DENIED, 2ND REQUEST. | | | 1. PLEASE PROVIDE 2 COPIES OF SURVEYS SHOWING THE | | | PROPOSED REAR PORCH THAT IS ATTACHED TO EXISTING | | | STRUCTURE | | | 2. THE PROPOSED GAME ROOM IS NOW CHANGED TO A REAR | | | PORCH, WHICH REQUIRES TWO COPIES OF SURVEYS TO BE | | | SUBMITTED SHOWING THE PROPOSED WORK WITH SETBACKS. | | | 3. THE ROOF PROJECTION CANNOT BE NO MORE THAN 3FT INTO | | | SETBACKS. | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-07-23 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-07-23 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-07-23 |
Time |
15:57 |
Sent To |
I |
|
| Notes |
| 2006-07-23 00:00:00 | DENIED, | | | 1. MUST PROVIDE TWO COPY OF CURRENT | | | SURVEY SHOWING THE PROPOSED GAME ROOM | | | ATTACHED TO EXISTING STRUCTURE. | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|