Plan Review Details - Permit 06071062
Plan Review Stops For Permit 06071062
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-12-01 Cont ID  
Sent By alange Date 2006-12-01 Time 13:58 Rev Time 0.00
Received By alange Date 2006-12-01 Time 13:58 Sent To  
Notes
2006-12-01 14:10:57DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025
 FOR MORE INFORMATION.
  
 3.SELECT ASSEMBLY ON BITUMEN ROOF
 PRODUCT APPROVAL.NOTE:FLAT ROOF PRODUCT APPROVALS
 NOT SUBMITED.SUBMIT FLAT ROOF PRODUCT APPROVAL,
 SELECT THE ASSEMBLY USED AND SUBMIT THE FOLLOWING STATE
 PRODUCT APPROVAL INFORMATION.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 4.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION SO AS TO NOT CREATE
 A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE AWAY FROM FOUNDATION
 WALLS SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-31 Cont ID  
Sent By alange Date 2006-07-31 Time 11:00 Rev Time 0.00
Received By alange Date 2006-07-31 Time 10:59 Sent To  
Notes
2006-07-31 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025
 FOR MORE INFORMATION.
  
 3.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUE HAS BEEN REVISED TO
 $34,243.00.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 4.SQUARE FOOTAGE NOT ON APPLICATION.
  
 5.SELECT ASSEMBLY ON BITUMEN ROOF
 PRODUCT APPROVAL.
  
 4.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION SO AS TO NOT CREATE
 A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE AWAY FROM FOUNDATION
 WALLS SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-11-30 Cont ID  
Sent By dpalmer Date 2006-11-30 Time 08:00 Rev Time 0.00
Received By dpalmer Date 2006-11-30 Time 07:55 Sent To M
Notes
2006-11-30 08:00:54*** UNSAT ***
  
 *** PLEASE SEE NOTES FROM PREVIOUS REVIEWS WHICH STILL
 NEED TO BE ADDRESSED.
  
 1) NOTE:NO, PLEASE SEE PLANS ARE STILL SHOWING A NEW
 ELECTRICAL RISER, YET PANEL SCHEDULE SHOWS AS EXISTING?
 PLEASE SUBMIT A NEW RISER AS PREVIOUSLY NOTED OR IF
 INDEED THIS IS AN EXISTING SERVICE PLEASE INDICATE
 THIS. THE ELECTRICAL AS SHOWN FOR NEW BACK PORCH WHICH
 IS REPLACING THE EXISTING BACK PORCH IS OK.
  
 PLEASE PROVIDE A COMPLETE ELECTRICAL RISER DIAGRAM FOR
 NEW PROPOSED 200A SERVICE UPGRADE.
 PLEASE SUBMIT AIC RATINGS, SEC'S, GROUNDING, CONDUITS
 ETC.
 PLEASE SHOW LOCATIONS OF PANEL(S) ON EXISTING/ NEW
 HOUSE OR ADDITION.
 PLEASE CLARIFY PANEL SCHEDULE WHICH MENTIONS "AS-BUILT"
 , SHOW LOCATIONS OF ALL EQUIPMENT.
 110.26,240.24,215.5,250.50,110.9,310.16,
 240.4 ETC
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-27 Cont ID  
Sent By dpalmer Date 2006-07-27 Time 20:55 Rev Time 0.00
Received By dpalmer Date 2006-07-27 Time 20:39 Sent To M
Notes
2006-07-27 00:00:00****UNSAT ****
  
 1) NOTE: PLEASE PROVIDE A COMPLETE
 ELECTRICAL RISER DIAGRAM FOR NEW
 PROPOSED 200A SERVICE UPGRADE.
 PLEASE SUBMIT AIC RATINGS, SEC'S,
 GROUNDING, CONDUITS ETC.
 PLEASE SHOW LOCATIONS OF PANEL(S) ON
 EXISTING/ NEW HOUSE OR ADDITION.
 PLEASE CLARIFY PANEL SCHEDULE WHICH
 MENTIONS "AS-BUILT" , SHOW LOCATIONS OF
 ALL EQUIPMENT.
 110.26,240.24,215.5,250.50,110.9,310.16,
 240.4 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-29 Cont ID  
Sent By mmiller Date 2006-11-29 Time 17:16 Rev Time 0.00
Received By mmiller Date 2006-11-29 Time 17:16 Sent To E
Notes
2006-11-29 17:16:44SENT TO DEWEY PALMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-17 Cont ID  
Sent By adarroug Date 2006-11-17 Time 16:15 Rev Time 0.00
Received By adarroug Date 2006-11-17 Time 16:15 Sent To Z
Notes
2006-11-17 16:16:44TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-27 Cont ID  
Sent By adarroug Date 2006-07-27 Time 16:49 Rev Time 0.00
Received By adarroug Date 2006-07-27 Time 16:49 Sent To E
Notes
2006-07-27 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-31 Cont ID  
Sent By alange Date 2006-07-31 Time 11:08 Rev Time 0.00
Received By alange Date 2006-07-21 Time 16:44 Sent To  
Notes
2006-07-21 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-11-30 Cont ID  
Sent By tgordon Date 2006-11-30 Time 08:15 Rev Time 0.20
Received By tgordon Date 2006-11-30 Time 08:15 Sent To B
Notes
2006-11-30 08:18:03*** DENIED ***
 1) IF NO MECHANICAL (A/C) WORK IS TO BE DONE THAN YOU
 MUST HAVE MECHANICAL PERMIT #06071065 VOIDED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-28 Cont ID  
Sent By tgordon Date 2006-07-28 Time 08:40 Rev Time 0.20
Received By tgordon Date 2006-07-28 Time 08:40 Sent To P
Notes
2006-07-28 00:00:00*** DENIED ***
 1) SHOW ON PLANS MINI-SPLIT A/C
 CONDENSER UNIT LOCATION.
  
 2) SHOW ON PLANS A/C EQUIPMENT LISTING
 FOR A/C MINI-SPLIT SYSTEM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-07-28 Cont ID  
Sent By mperson Date 2006-07-28 Time 16:27 Rev Time 0.22
Received By mperson Date 2006-07-28 Time 16:27 Sent To B
Notes
2006-07-28 00:00:00NOTE: NO PLUMBING WORK SHOWN ON PLANS

Review Stop Z ZONING
Rev No 2 Status F Date 2006-11-26 Cont ID  
Sent By mmclean Date 2006-11-25 Time 22:11 Rev Time 0.00
Received By mmclean Date 2006-11-25 Time 22:11 Sent To I
Notes
2006-11-26 22:13:28DENIED, 2ND REQUEST.
 1. PLEASE PROVIDE 2 COPIES OF SURVEYS SHOWING THE
 PROPOSED REAR PORCH THAT IS ATTACHED TO EXISTING
 STRUCTURE
 2. THE PROPOSED GAME ROOM IS NOW CHANGED TO A REAR
 PORCH, WHICH REQUIRES TWO COPIES OF SURVEYS TO BE
 SUBMITTED SHOWING THE PROPOSED WORK WITH SETBACKS.
 3. THE ROOF PROJECTION CANNOT BE NO MORE THAN 3FT INTO
 SETBACKS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-23 Cont ID  
Sent By mmclean Date 2006-07-23 Time 15:57 Rev Time 0.00
Received By mmclean Date 2006-07-23 Time 15:57 Sent To I
Notes
2006-07-23 00:00:00DENIED,
 1. MUST PROVIDE TWO COPY OF CURRENT
 SURVEY SHOWING THE PROPOSED GAME ROOM
 ATTACHED TO EXISTING STRUCTURE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720