| 2006-07-25 00:00:00 | ******DENIED****** |
| | REFERENCE: FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | THE FOLLOWING IS REQUIRED FOR GAS PLAN |
| | REVIEW: |
| | |
| | 1. PER FBC-2004 CHAPTER 1, SECTIONS |
| | 109.3 REQUIRED PERMITS AND SECTION 109.6 |
| | APPROVAL REQUIRED: THIS PERMIT CANNOT BE |
| | ISSUED UNTIL THE EXPIRED GAS PERMIT |
| | #03110020 HAS BEEN TAKEN CARE OF. PLEASE |
| | SEE ATTACHED PERMIT INFORMATION FOR |
| | REFERENCE. |
| | 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | 3. TYPE OF GAS, (LP OR NATURAL) |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). (NOTE: PERMIT INFORMATION |
| | INDICATES EXISTING GAS TO A GRILL ON |
| | EXPIRED PERMIT #03110020, TOTAL BTU LOAD |
| | NEEDS TO BE INDICATED ON ISOMETRIC.) |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). ( NOTE: |
| | THIS INCLUDES EXISTING GAS TO GRILL) |
| | 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | (NOTE: NEED MANUFACTURE CUT SHEETS ON |
| | 2LB REGULATORS) |
| | 7. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. PLEASE SEE CORRECTED ISOMETRIC GAS |
| | RISER DIAGRAM IN RED INK FOR REFERENCE |
| | FOR RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |