Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-04-11 Cont ID  
Sent By mjacobs Date 2007-04-11 Time 11:18 Rev Time 0.00
Received By mjacobs Date 2007-04-11 Time 08:59 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-02-09 Cont ID  
Sent By mjacobs Date 2007-02-09 Time 18:33 Rev Time 0.00
Received By mjacobs Date 2007-02-09 Time 16:21 Sent To  
Notes
2007-02-09 17:40:32BUILDING PLAN REVIEW
 PERMIT:06071011
 ADD:2505METROCENTRE BLVD
 CONT:PATE CHERNIN & ASSO. INC.
 TEL: (561)792-2757
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD
 ACTION: DENIED
  
 1)OK
  
 2)OK
  
 3)OKHOWEVER, ELEVATION #6 ON SHEET A-4 DOES NOT
 SHOW THE DEPT OF THE SINK OR ANY PIPES BELOW THE SINK.
 SHOW HOW THE REQUIREMENTS OF FBC.11-4.24 WILL BE MET.
  
 4)THE LEGENDNEEDS TO BE MORE SPECIFIC WITH THE
 SYMBOLS FOR THE EXISTING AND NEW PARTITIONS. THE SYMBOL
 IS THE SAME FOR EACH WALL. WALL TYPES I AND 2 SHOULD BE
 DIFFERENT HOWEVER, ON THE DRAWINGS THE NUMBERS ARE THE
 SAME FOR BOTH TYPE OF WALLS. CLARIFY.
 HOW CAN DIFFERENT SYMBOLS REPRESENT THE SAME SIZE AND
 TYPE OF WALLS? SEE SHEET A-1.
  
 5) THE ELEVATION DETAIL #9 ON SHEET A-3 DOES NOT
 REFLECT THE FLOOR PLAN ON SHEET A-1. WHERE IS THE
 SECOND DOOR? ALSO SEE ELEVATION DETAIL #4 ON SHEET A-3.
 ALL DETAILS SHALL CORRESPON WITH THE FLOOR PLAN.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-03 Cont ID  
Sent By mjacobs Date 2007-01-03 Time 16:13 Rev Time 0.00
Received By mjacobs Date 2007-01-03 Time 11:06 Sent To  
Notes
2007-01-03 16:13:23BUILDING PLAN REVIEW
 PERMIT:06071011
 ADD:2505METROCENTRE BLVD
 CONT:PATE CHERNIN & ASSO. INC.
 TEL: (561)792-2757
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND.
 ACTION: DENIED
  
 1) 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 2) THE EXTERIOR AREA OF THE RECEPTION COUNTER SHALL
 MEET ONE OF THE REQUIREMENTS OF 11-7.2. WHERE A PORTION
 OF THE MAIN COUNTER SHALL BE A MINIMUM OF 36 INCHES IN
 LENGTH AND A MAXIMUM HEIGHT OF 36 INCHES.
  
 3)11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK (SEE FIGURE 11-32
 ).SHOW ON THE DRAWINGS HOW REQUIREMENTS OF
 SEC.11-4.24 WILL BE MET. SHEET A-1 ROOM #003.
  
 4)THE LEGENDNEEDS TO BE MORE SPECIFIC WITH THE
 SYMBOLS FOR THE EXISTING AND NEW PARTITIONS. THE SYMBOL
 IS THE SAME FOR EACH WALL. WALL TYPES I AND 2 SHOULD BE
 DIFFERENT HOWEVER, ON THE DRAWINGS THE NUMBERS ARE THE
 SAME FOR BOTH TYPE OF WALLS. CLARIFY.
  
 5) THE ELEVATION DETAIL #9 ON SHEET A-3 DOES NOT
 REFLECT THE FLOOR PLAN ON SHEET A-1. WHERE IS THE
 SECOND DOOR? ALSO SEE ELEVATION DETAIL #4 ON SHEET A-3.
 ALL DETAILS SHALL CORRESPON WITH THE FLOOR PLAN.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-04 Cont ID  
Sent By amorse Date 2006-08-04 Time 10:58 Rev Time 0.00
Received By amorse Date 2006-08-04 Time 10:58 Sent To  
Notes
2006-08-04 00:00:00 
  
 DENIED
  
 1) REMOVE ALL REFERENCES TO THE 2001
 FBC. DRAWINGS AND SPECIFICATIONS SHALL
 COMPLY WITH THE 2004 FBC WITH
 AMMENDMENTS. ALSO THE GENERAL CODE
 ANALYSIS ON A-2 USES 2001 SECTIONS AND
 TABLES PLEASE CORRECT
  
 2) SPECIFY SAFTY GLAZING FOR GLASS IN
 WALL BETWEEN RECEPTION AND CONFRENCE
 ROOM PER 2406.3 FBC
  
 3) DOOR SCHEDULE HAS DOOR #3 AS 2'-0"
 MAY BE A MISPRINT?
  
 4) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-04-05 Cont ID  
Sent By dpalmer Date 2007-04-05 Time 07:32 Rev Time 0.00
Received By dpalmer Date 2007-04-04 Time 16:44 Sent To  
Notes
2007-04-05 07:32:141) NOTE: PLEASE SEE ROOM/AREA WHICH SEEMS TO CONTAIN
 PARTITIONS WHICH WOULD REQUIRE AN AUTOMATED DEVICE PER
 13-415.1.ABC.1.1, .1.2.
 THESE WALLS ARE NOT CLEAR AND THIS IS TO BE VERIFIED IN
 FIELD.
  
 2) NOTE: PLEASE SEE ROOM ON PLANS WHERE PANEL IS
 LOCATED. THIS ROOM ON PREVIOUS PLANS CONTAINED A DESK,
 COMPUTER STATION ETC. NOW, WHAT APPEARED TO BE A SMALL
 OFFICE AREA NOW APPEARS TO BE A CLOSET. PLEASE KNOW THE
 ELECTRICAL PANEL MAY NOT BE IN A STORAGE CLOSET.
 110.26, 240.24, 408.7.
 PLEASE SEE PLANS HAVE BEEN REDLINED FOR THIS AS OVER
 CURRENT PROTECTION IS NOT TO BE LOCATED IN THE
 IMMEDIATE VICINITY OF EASILY IGNITABLE MATERIALS.
  
 ** PLEASE REVISE THE ABOVE ALONG WITH ANY OTHER
 REVISIONS BEFORE THE ROUGH ELECTRICAL INSPECTION.
  
 *IF THERE ARE ANY QUESTIONS ON THE ABOVE PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-02-07 Cont ID  
Sent By dpalmer Date 2007-02-07 Time 14:27 Rev Time 0.00
Received By dpalmer Date 2007-02-06 Time 15:22 Sent To  
Notes
2007-02-07 14:30:31*** UNSAT ****
  
  
 1) NOTE: PLEASE SEE NOT ALL AREAS APPEAR TO CONTAIN A
 DEVICE. PLEASE SEE ONE SET OF PLANS WHICH HAS THIS AREA
 REDLINED.
 PLEASE ALSO KNOW THAT THE STATE WAS CONTACTED AND
 PLEASE SEE THE DEFINITIONS AS STATED IN THE FBC AND
 EVEN IN CHAPTER 13. PLEASE SEE THE RESPONSE LETTER
 MENTIONS TO SEE *SEPARATE BUILDING* ETC, HOWEVER PLEASE
 SEE THE MINIMUM REQUIREMENTS FOR THE WALL. THE FIRE
 WALL DEFINITION IS PROVIDED IN CHAPTER 13.
 13-415.1.1, .1.2 AND .1.3
 13-415.2, 13-415.1.AB.1
  
 ** PLEASE KNOW THAT UPON CONSULTATION WITH ANN STANTON
 FROM THE STATE DEPARTMENT OF COMMUNITY AFFAIRS AND AS
 FOR ELECTRICAL CODE COMPLIANCE WITH THE LIGHTING
 PERFORMANCE AND ENERGY CALCULATIONS COME UP TO THE
 FIGURES AS SET FORTH THEN PLEASE CALL TO GO OVER HOW
 THIS CAN POSSIBLY BE SHOWN IN COMPLIANCE ON PLANS.
  
 2) NOTE: PLEASE SEE THE PLANS HAVE NOW COME BACK WITH A
 COMPLETELY NEW *SIGNATURE* FROM THE DESIGN
 PROFESSIONAL. PLEASE SEE THAT THE PLANS NOW APPEAR TO
 SHOW SOME KIND OF INITIALS INSTEAD WHICH DO NOT
 CORRELATE WITH THE ORIGINAL SIGNATURE OF RECORD IN ANY
 WAY.
 PLEASE SUPPLY AND SUBMIT A SIGNED, DATED, SEALED AND
 NOTARIZED LETTER ATTESTING TO THE LEGAL SIGNATURE OF
 THE DESIGNER OF RECORD.
 FS 481.221.
 PLEASE KNOW THAT IN NO CASE MAY ANY OTHER PERSON THAN
 THE LICENSE HOLDER SIGN PLANS.PLEASE KNOW THAT AT
 THIS TIME EACH SET OF PLANS ARE BEING RETAINED BY THIS
 OFFICE.
 PLEASE BE SURE THE NOTARIZED LETTER IS PROPERLY
 NOTARIZED PER FS 117.05
  
 *PLEASE ALSO SEE THAT THE SEAL IS REQUIRED TO BE CLEAR
 AND VISIBLE WITH ALL INFORMATION ON SAID SEAL. PLEASE
 SEE FS 481.221 AND FAC 61G1-16.003
 MANY OF THE SEALS ARE VERY FAINT AT THIS TIME AND NOT
 EASILY READABLE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-23 Cont ID  
Sent By dpalmer Date 2006-12-23 Time 15:27 Rev Time 0.00
Received By dpalmer Date 2006-12-23 Time 14:46 Sent To  
Notes
2006-12-23 15:29:28*UNSAT 2ND REVIEW *
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH
 STILL NEEDS TO BE ADDRESSED. PLEASE ALSO NEW NOTES
 BASED ON CHANGES AND/OR PLANS SUBMITTED.
  
 ** PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW IN THE SAME NUMERICAL ORDER WITH A NO
 OR OK. PLEASE SEE SOME MAY CONTAIN BOTH NO/OK, WHICH
 MEANS PART OF NOTE MAY HAVE BEEN ADDRESSED.
  
  
  
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE: NO, PLEASE SEE NOT ALL AREAS CONTAIN THE
 REQUIRED CONTROLS FOR THE OCCUPANCY SENSOR DEVICES AS
 REQUIRED. PLEASE SEE NO MAXIMUM OVER RIDE/OC SENSOR
 TIMES ARE INDICATED.
 PLEASE SEE ENERGY CALCULATIONS INDICATE METHOD "A".
 PLEASE SEE 13-415.1.AB.1, PLEASE CLARIFY HOW METHOD "A"
 CAN BE USED FOR BUILD OUT OF AN EXISTING SPACE. PLEASE
 SEE THESE ALSO INDICATE MANUAL CONTROL FOR LIGHTING
 WHERE AUTO SHUT OFF IS BEING INSTALLED.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR PERFORMANCE
 LEVELS TO BE SPECIFIED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13. 13-415.1.ABC.1.1,.1.2,.1.3
 ETC
  
 ** NEW NOTE (S) **
  
 1) NOTE: PLEASE STATE THE MINIMUM REQUIRED LEVELS FOR
 HORN AND STROBE DEVICES. PLEASE SEE FBC 11-4.28.1, .2,
 .3(4).
 THIS IS A NEW COMMENT.
  
 2) NOTE: PLEASE SEE THAT PLANS STATE THE FOLLOWING
 CODES AT A MINIMUM 2002 NFPA-70, 2002 NFPA-72
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-04 Cont ID  
Sent By dpalmer Date 2006-08-04 Time 17:35 Rev Time 0.00
Received By dpalmer Date 2006-08-04 Time 16:37 Sent To  
Notes
2006-08-04 00:00:00*** UNSAT **
  
 ** PLEASE KNOW, PLANS WEREONLY
 SUBMITTED FOR "PLANREVIEW" AND HAS NOT
 BEEN SUBMITTED FOR PERMIT.
  
 1) NOTE: PLEASE CLARIFY THE GFI RECEPT
 FOR CU'S.
 210.63,210.8
  
 2) NOTE: PLEASE CLARIFY THE MEANS OF
 DISCONNECT FOR THE AHU'S.
 440.11.
  
 3) NOTE: PLEASE SEE FBC CHAPTER CHAPTER
 13.
 13-415.1.ABC.1.1,.1.2,.1.3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date   Cont ID  
Sent By   Date 2007-04-10 Time   Rev Time 0.00
Received By mawillia Date 2007-04-10 Time 12:11 Sent To  
Notes
2007-04-10 12:43:57*****APPROVED*****
  
  
 PLAN SHEET A-7 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-02-12 Cont ID  
Sent By mawillia Date 2007-02-12 Time 11:27 Rev Time 0.00
Received By mawillia Date 2007-02-12 Time 11:21 Sent To  
Notes
2007-02-12 11:26:54****APPROVED*****
  
  
 PLANS TO BE STAMPED WHEN OTHER PLAN REVIEWS HAVE BEEN
 SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-26 Cont ID  
Sent By mwennerg Date 2006-12-26 Time 15:38 Rev Time 0.00
Received By mwennerg Date 2006-12-26 Time 15:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-08-08 Cont ID  
Sent By mwennerg Date 2006-08-08 Time 15:34 Rev Time 0.00
Received By mwennerg Date 2006-08-08 Time 15:34 Sent To  
Notes
2006-08-08 00:00:00***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 2) SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE SPRINKLER REMODEL IF
 APPLICABLE.
  
 3) IS THIS BUILDING PROTECTED BY A FIRE
 ALARM SYSTEM?
  
 4) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED. ACCESS SHALL BE NOT IN EXCESS
 OF 75' TRAVEL DISTANCE.
  
 5) NOTATIONS ARE MADE IN REGARDS TO DUCT
 SMOKE DETECTORS, BUT NONE ARE SHOWN ON
 DRAWINGS. PLEASE VERIFY.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-10-02 Cont ID  
Sent By adarroug Date 2007-10-02 Time 11:05 Rev Time 0.00
Received By adarroug Date 2007-10-02 Time 11:05 Sent To M
Notes
2007-10-02 11:06:06TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-06-18 Cont ID  
Sent By adarroug Date 2007-06-18 Time 10:26 Rev Time 0.00
Received By adarroug Date 2007-06-18 Time 10:26 Sent To M
Notes
2007-06-18 10:26:51TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-30 Cont ID  
Sent By spalmer Date 2007-03-30 Time 18:15 Rev Time 0.00
Received By spalmer Date 2007-03-30 Time 18:15 Sent To  
Notes
2007-03-30 18:15:20TO BOB # 4

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-06 Cont ID  
Sent By adarroug Date 2007-02-06 Time 11:29 Rev Time 0.00
Received By adarroug Date 2007-02-06 Time 11:29 Sent To  
Notes
2007-02-06 11:30:12TO "BOB"#5

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-22 Cont ID  
Sent By adarroug Date 2006-12-22 Time 11:17 Rev Time 0.00
Received By adarroug Date 2006-12-22 Time 11:17 Sent To  
Notes
2006-12-22 11:19:30TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-07 Cont ID  
Sent By adarroug Date 2006-12-07 Time 11:32 Rev Time 0.00
Received By adarroug Date 2006-12-07 Time 11:32 Sent To  
Notes
2006-12-07 11:32:18WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-08 Cont ID  
Sent By mwennerg Date 2006-08-08 Time 15:58 Rev Time 0.00
Received By mwennerg Date 2006-07-20 Time 18:01 Sent To  
Notes
2006-08-02 00:00:00TO "BOB"#4
2006-07-20 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-10-18 Cont ID  
Sent By tgordon Date 2007-10-18 Time 09:13 Rev Time 0.30
Received By tgordon Date 2007-10-18 Time 09:13 Sent To  
Notes
2007-10-18 09:13:55REVISION TO MECH. PLAN PAGE A-5.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-06-18 Cont ID  
Sent By tgordon Date 2007-06-18 Time 14:21 Rev Time 0.30
Received By tgordon Date 2007-06-18 Time 14:21 Sent To  
Notes
2007-06-18 14:22:21REVISION TO MECHANICAL PLANS PAGES A-5 AND A-6.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-04-05 Cont ID  
Sent By tgordon Date 2007-04-05 Time 10:44 Rev Time 0.25
Received By tgordon Date 2007-04-05 Time 10:44 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-02-08 Cont ID  
Sent By tgordon Date 2007-02-08 Time 12:07 Rev Time 0.20
Received By tgordon Date 2007-02-08 Time 12:07 Sent To  
Notes
2007-02-08 12:08:44*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTE #2, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-12-27 Cont ID  
Sent By tgordon Date 2006-12-26 Time 11:27 Rev Time 0.45
Received By tgordon Date 2006-12-26 Time 11:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-04 Cont ID  
Sent By tgordon Date 2006-08-04 Time 08:56 Rev Time 0.30
Received By tgordon Date 2006-08-04 Time 08:56 Sent To  
Notes
2006-08-04 00:00:00*** DENIED ***
 1) RETURN AIR TRANSFER DUCTS FROM D.C.
 OFFICE #007 TO WAR ROOM #005 NEEDS TO BE
 SIZED.
  
 2) ARE DOORS TO MECHANICAL ROOM
 LOUVERED? PLEASE SHOW ON PLANS (IF NOT
 PROVIDE RETURN AIR TO AHU).
  
 3) PROVIDE PRODUCT APPROVAL FOR A/C
 CONDENSER STAND.
  
 4) PLEASE SEE ENERGY CALCULATIONS FRONT
 PAGE, MAX TONNAGE 5.0, TWO A/C SYSTEMS
 ARE BEING INSTALLED A 5 TON AND A 4 TON
 WOULD MAKE MAX TONNAGE 9 TONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  