Plan Review Details - Permit 06070994
Plan Review Stops For Permit 06070994
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-09-20 Cont ID  
Sent By jwitmer Date 2007-09-20 Time 16:11 Rev Time 0.55
Received By jwitmer Date 2007-09-20 Time 16:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-06-28 Cont ID  
Sent By jwitmer Date 2007-06-28 Time 13:55 Rev Time 1.11
Received By jwitmer Date 2007-06-28 Time 13:55 Sent To FIRE
Notes
2007-06-28 14:09:09PERMIT: 06070994
 ADD: 300 EXECUTIVE CENTER DR.
 CONT: CLINLOR ELECTRIC
 TEL: (386)774-1020
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) NOC EXPIRED WILL NEED TO RE-RECORD NOC. FL S S
 713.13NOTICE OF COMMENCEMENT, TO BE FILED WITH THE
 CLERK OF THE COURT.NOTE: 713.13(2) IF THE WORK
 DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)PLANS INDICATE THEY WERE CREATED BY AN ENGINEER R.
 GRELLE. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
  
 4) TITLEBLOCK;IN ADDITION TO SIGNING, SEALING AND
 ATING EACH PAGE OF THE PLANS, THE ENGINEER IN
 RESPONSIBLE CHARGE MUST LEGIBLY INDICATE IN A TITLE
 BLOCK THEIR NAME, ADDRESS AND LICENSE NUMBER ON EACH
 PLAN SHEET. 61G15-23.002 F.A.C.
  
 5) LINC SERVICES:471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY SHEET BEARING
 THE NAME OF AN ENGINEER PRACTICING UNDER A FICTITIOUS
 NAME, A CORPORATION, OR A PARTNERSHIP, OFFERING
 ENGINEERING SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER. ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-12-26 Cont ID  
Sent By jwitmer Date 2006-12-26 Time 11:48 Rev Time 0.77
Received By jwitmer Date 2006-12-26 Time 11:48 Sent To PC
Notes
2006-12-26 11:49:50PERMIT: 06070994
 ADD: 300 EXECUTIVE CENTER DR.
 CONT: CLINLOR ELECTRIC
 TEL: (386)774-1020
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) COMPLIED.
  
 3) COMPLIED.
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8)3RD REQUEST FOR THE TYPE OF FASTENER TO BE
 USED TO FASTEN THE GENERATOR FRAME TO THE
 EXISTING CONCRETE DECK. GENERATOR SLAB &
 ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 1609.1.3 ANCHORAGE AGAINST OVERTURNING, UPLIFT AND
 SLIDING
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-08 Cont ID  
Sent By jwitmer Date 2006-11-08 Time 12:13 Rev Time 1.66
Received By jwitmer Date 2006-11-08 Time 12:13 Sent To  
Notes
2006-11-08 12:14:48BUILDING PLAN REVIEW
 PERMIT: 06070994
 ADD: 300 EXECUTIVE CENTER DR.
 CONT: CLINLOR ELECTRIC
 TEL: (386)774-1020
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) COMPLIED.
  
 3)THE NEW VALUE OF THIS PERMIT NEEDS TO
 BE PAID PLUS FORTHE THIRD REVIEW 10% ASSESSMENT
 BEFORE THE THIRD REVIEW CAN TAKE PLACE.MARSHALL & SWIFT
 IF VALUE IS NOT
 CORRECTED.
  
 4) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
 THE NOC HAS NOT BEEN RECORDED AT THE COUNTY CLERKS
 OFFICE.
  
 5) THE SITE PLAN DOESN'T INDICATE TO WHOM IT WAS DRAWN
 BY?
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 1609.1.3 ANCHORAGE AGAINST OVERTURNING, UPLIFT AND
 SLIDING
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-09 Cont ID  
Sent By jwitmer Date 2006-08-09 Time 08:25 Rev Time 2.22
Received By jwitmer Date 2006-08-09 Time 08:25 Sent To  
Notes
2006-08-09 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06070994
 ADD: 300 EXECUTIVE CENTER DR.
 CONT: CLINLOR ELECTRIC
 TEL: (386)774-1020
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) PLEASE PROVIDE DOCUMENTS FOR SIZE OF
 GENERATOR AND ALSO FOR THE SIZE OF FUEL
 TANK TO ACCOMPANY THE GENERATOR.
  
 3) VALUE IS LOW WILL ASSESS VALUE FROM
 MARSHALL & SWIFT IF VALUE IS NOT
 CORRECTED.
  
 4) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 5) PLANS INDICATE THEY ARE THE PROPERTY
 (DRAWN BY) DONNELLY ENGINEERING,
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 6) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G) FLOOD ZONE
  
 7) SITE PLAN ILLEGIBLE.
 106.1.2 ADDITIONAL DATA. THE
 BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS,
 STRESS DIAGRAMS, AND OTHER
 DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THIER OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
  
 8) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-06-18 Cont ID  
Sent By dpalmer Date 2007-06-18 Time 08:34 Rev Time 0.00
Received By dpalmer Date 2007-06-18 Time 08:12 Sent To  
Notes
2007-06-18 08:35:05TWO PACKAGES ATTACHED TOGETHER AND STAMPED ELECTRICAL
 ONLY.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-12-19 Cont ID  
Sent By dpalmer Date 2006-12-19 Time 11:58 Rev Time 0.00
Received By dpalmer Date 2006-12-19 Time 09:29 Sent To  
Notes
2006-12-19 11:58:54**** UNSAT ****
  
 1) NOTE: PLEASE SEE NO OCP IS BEING SHOWN ON RISER FROM
 GENERATOR TO ATS AND EXISTING EQUIPMENT.
 PLEASE SEE 445.13 FOR SIZING OF THE CONDUCTORS.
  
 2) NOTE: PLEASE SEE LETTER IS PACKAGE FROM THE
 ELECTRICAL CONTRACTOR MENTIONS CONSIDERATION FOR NEC
 250.20A IS BEING TAKEN WHICH IS A SECTION FOR
 SEPARATELY DERIVED SYSTEMS. PLEASE SEE IF THIS GOING TO
 BE A SD SYSTEM, THEN THE RISER WOULD NEED TO SHOW THE
 GROUNDING AT THE GENERATOR ACCORDING TO 250.50.
 PLEASE ALSO INDICATE OF THE EXISTING ATS IS A 4-POLE
 UNIT.
 PLEASE INDICATE THE VOLTAGE ON THE PLANS/RISER AS WELL
 AS THE SPECS SHEETS SUBMITTED.
  
 ** A CALL WAS PLACED TO THE ELECTRICAL CONTRACTOR ON
 12/19/07 AT 10:23AM.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-22 Cont ID  
Sent By dpalmer Date 2006-10-22 Time 14:22 Rev Time 0.00
Received By dpalmer Date 2006-10-22 Time 13:55 Sent To  
Notes
2006-10-22 14:22:21** UNSAT **
  
 1) NOTE: PLEASE SEE VALUE HAS BEEN ADJUSTED AND FEES
 WILL BE OWED BEFORE PERMIT CAN BE ISSUED. THE
 ADDITIONAL FEE FO $444.00 IS BASED ON NEW VALUE OF
 $45K.
  
 2) NOTE: PLEASE SEE THE ELECTRICAL RISER DIAGRAM
 PREVIOUSLY SUBMITTED IS NO LONGER IN PLANS OR
 SUBMITTED??
 EVEN IF EXISTING, PLEASE SHOW SO THAT THE CONDUCTORS
 ETC EVEN IF EXISTING CAN BE VERIFIED.
  
 3) NOTE: PLEASE SEE BOTH SETS OF SUBMITTIALS OF
 MANUFACTURE SPECS/CUT SHEETS NEED TO BE COMPLETE TO
 CONTAIN THE SAME IN BOTH SETS. PLEASE SEE ONE PACKAGE
 IS MISSING SHEETS WHICH ARE IN OTHER PACKAGE.
 FBC 106.1.2, ADMIN SECT.
 90.7, 110.3
  
 4) NOTE: PLEASE SEE THAT ANY ELECTRICAL PLANS/PLANS ETC
 WHEN NOT DONE BY AN ARCHITECT OR ENGINEER SHALL BEAR
 THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLANS, DEISGN ETC.
 PLEASE SEE THIS WAS STATED IN PERVIOUS REVIEW. PLEASE
 SEE FBC 106.1.2 ADMIN SECT.
 PLEASE SEE NOTE ABOVE WITH RESPECT TO RISER NOT BEING
 SUBMITTED FOR THIS REVIEW. (EVEN IF EXISTING). CODE
 COMPLIANCE FOR EXISTING NEEDS TO BE VERIFIED AS
 CONNECTION OF NEW EQUIPMENT MAY NOT GO BACK TO AN
 EXISTING CODE VIOLATION (IF ONE EXISTS).
  
 5) NOTE: PLEASE SEE THE NOTICE OF COMMENCEMENT
 SUBMITTED WAS NOT RECORDED WITH THE PALM BEACH COUNTY
 COURTHOUSE. PLEASE KNOW, THIS NOC MUST BE RECORDED AND
 SUBMITTED PER FS713.13.
  
  
 ** PLEASE KNOW AS THIS IS AN IMPORTANT PROJECT AND TIME
 IS A SENSITIVE NATURE ONCE READING OF THESE COMMENTS
 PLEASE CALL TO GO OVER SOME OPTIONS. BEFORE OTHER
 REVIEWS ARE DONE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-02 Cont ID  
Sent By dpalmer Date 2006-08-02 Time 17:25 Rev Time 0.00
Received By dpalmer Date 2006-08-02 Time 17:25 Sent To  
Notes
2006-08-02 00:00:00********* UNSAT **********
  
 1) NOTE: PLEASE SEE THAT THE VALUE FOR
 COMPLETE SCOPE OF WORK SHALL INCLUDE ALL
 LABOUR AND MATERIALS EVEN IF ANY
 MATERIALS/EQUIPMENT IS OWNER SUPPLIED.
 PLEASE KNOW A VALUE MAY BE ADJUSTED
 BASED ON THE MARSHALL'S/SWIFT GUIDE
 ADOPTED INTO THE FBC.
 FBC 108.3
  
 2) NOTE: PLEASEONLY SUPPLY PLANS
 /DRAWINGS FOR SCOPE OF WORK BEING
 PERFORMED. PLEASE SEE RISER SUBMITTED
 INCLUDES NEW SERVICE EQUIPMENT ALSO.
 PLEASE VERIFY THIS.
 106.1.2 FBC
  
 3) NOTE: PLEASE ALSO SEE PLANS SUBMITTED
 ALSO CONTAIN TITLE BLOCKS FOR AN
 ENGINEERING FIRM. IF SO, PLEASE BE SURE
 PLANS ARE SIGNED, DATED AND SEALED BY
 SAID FIRM.
 PLEASE SEE FS 471.025
 ** PLEASE KNOW, DEPENDING ON ACTUAL
 SCOPE PF WORK PLANS MAY NOT BE REQUIRED
 TO BE DONE BY AN ENGINEER.
 PLEASE KNOWIN EITHER CASE PLANS SHALL
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON REPSONSIBLE FOR PLANS AND
 DESIGN.
 FBC 106.1.2
  
 4) NOTE: PLEASE SUBMIT ALL MANUFACTURE'S
 SPEC/CUT SHEETS FOR NEW GEN. IF OUTSIDE
 PLEASE ALSO INCLUDE THE WP ENCLOSURE
 DETAIL/SPECS.
 PLEASE SEE SPECS SUBMIITED INDICATE A
 125/113 KW UNIT, YET PLANS INDICATE A
 275KW UNIT.
 90.8,110.3
 FBC 106.1.2
  
 ** PLEASE SEE POSSIBLE COMMENTS AS PLANS
 INDICATE A 7000 GALLON TANK.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-09-25 Cont ID  
Sent By mawillia Date 2007-09-25 Time 14:09 Rev Time 0.00
Received By mawillia Date 2007-09-25 Time 13:52 Sent To  
Notes
2007-09-25 14:03:01*****APPROVED*****
  
  
 GENERATOR ENCLOSURE PLAN AND DETAIL SHEET (1 OF 1)
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-06-28 Cont ID  
Sent By mawillia Date 2007-06-28 Time 16:36 Rev Time 0.00
Received By mawillia Date 2007-06-28 Time 16:29 Sent To  
Notes
2007-06-28 16:33:02*****APPROVED*****
  
  
  
 TO BE STAMPED AND SIGNED WHEN ALL PLAN REVIEWS HAVE
 BEEN SATISFIED

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-12-22 Cont ID  
Sent By mawillia Date 2006-12-22 Time 15:36 Rev Time 0.00
Received By mawillia Date 2006-12-22 Time 15:36 Sent To  
Notes
2006-12-22 15:38:22*****APPROVED*****
  
  
  
 TO BE STAMPED AND SIGNED WHEN ALL PLAN REVIEWS HAVE
 BEEN SATISFIED

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-11-01 Cont ID  
Sent By mwennerg Date 2006-11-01 Time 13:46 Rev Time 0.00
Received By mwennerg Date 2006-11-01 Time 13:46 Sent To  
Notes
2006-11-01 13:50:32***DENIED***
  
 PLEASE SEE ELECTRICAL REVIEW COMMENT #3. WHEN
 SUBMITTING PLANS, PLEASE PROVIDE COMPLETE SETS OF PLANS
 AND ASSOCIATED SHEETS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722 OR 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-08-09 Cont ID  
Sent By mwennerg Date 2006-08-09 Time 13:45 Rev Time 0.00
Received By mwennerg Date 2006-08-09 Time 13:45 Sent To  
Notes
2006-08-09 00:00:00***DENIED***
  
 1) PLEASE PROVIDE MANUFACTURER
 SPECIFICATION SUBMITAL FOR GENERATOR.
  
 2) PLEASE NOTE THAT THE 2002 EDITION OF
 NFPA 110, "STANDARD FOR EMERGENCY AND
 STANDBY POWER SYSTEMS" SHALL BE
 REFERENCED.
  
 3) PLEASE VERIFY DISTANCES FROM
 GENERATOR TO BUILDING OPENINGS AND MEANS
 OF EGRESS.
  
 4) FUEL TANK WILL REQUIRE APPROVAL BY
 DERM.
  
 5) NO SMOKING SIGNS ARE REQUIRED IF NOT
 ALREADY PRESENT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status N Date 2006-08-21 Cont ID  
Sent By pkrauss Date 2006-08-21 Time 10:08 Rev Time 0.00
Received By pkrauss Date 2006-08-21 Time 10:08 Sent To  
Notes
2006-08-21 00:00:00ADDITIONAL PERMIT REQUIRED FOR THE FUEL
 OIL.
  
 PLEASE SUBMIT PLANS FOR APPROVAL TO
 DEPARTMENT OF ENVIRONMENTAL PROTECTION
 AT THE FOLLOWING ADDRESS:
  
 3323 BELVEDERE RD
 BLDG # 502
 WEST PALM BEACH, FL
 PHONE:(561)233-2400, ASK FOR
 CHIP GREEN
  
 PLEASE SUBMIT PLANS AFTER THE APPROVAL
 FROM DERM.
  
 INDICATE DISTANCES/CLEARANCES FROM
 PROPERTY LINES, BUILDING, FRESH AIR
 INTAKES, WINDOW, DOORS, ETC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719
 OR E-MAIL [email protected].
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-08-10 Cont ID  
Sent By kstevens Date 2006-08-10 Time 07:30 Rev Time 0.00
Received By kstevens Date 2006-08-10 Time 07:30 Sent To  
Notes
2006-08-10 00:00:00GENERATOR INDICATED AS DIESEL GENERATOR.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-15 Cont ID  
Sent By adarroug Date 2007-08-15 Time 14:25 Rev Time 0.00
Received By adarroug Date 2007-08-15 Time 14:25 Sent To  
Notes
2007-08-15 14:25:48TO "COMM" BD#58

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-21 Cont ID  
Sent By shill Date 2007-05-21 Time 15:27 Rev Time 0.00
Received By shill Date 2007-05-21 Time 15:27 Sent To  
Notes
2007-06-12 11:19:33TO "COMM" BD#13
2007-05-21 15:28:11WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-01 Cont ID  
Sent By adarroug Date 2006-12-01 Time 13:32 Rev Time 0.00
Received By adarroug Date 2006-12-01 Time 13:32 Sent To  
Notes
2006-12-18 14:16:15TO "COMM" BD#4
2006-12-01 13:33:11WAITING FOR "COMM"BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-11 Cont ID  
Sent By adarroug Date 2006-10-11 Time 13:40 Rev Time 0.00
Received By adarroug Date 2006-10-11 Time 13:40 Sent To  
Notes
2006-10-20 15:53:17TO "COMM" BD#18--EXPEDITED PERMIT--
2006-10-11 13:40:30WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-21 Cont ID  
Sent By pkrauss Date 2006-08-21 Time 10:21 Rev Time 0.00
Received By pkrauss Date 2006-07-19 Time 16:21 Sent To  
Notes
2006-08-01 00:00:00TO COMM. BOARD # 16
2006-07-19 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-08-21 Cont ID  
Sent By pkrauss Date 2006-08-21 Time 10:03 Rev Time 0.00
Received By pkrauss Date 2006-08-21 Time 09:59 Sent To  
Notes
2006-08-21 00:00:00PERMIT APPLICATION INDICATES FUEL OIL
 PERMIT APPLICATION TO BE SUBMITTED
 SEPARATELY.NO MECHANICAL PLANS
 SUBMITTED FOR REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].
  

Review Stop Z ZONING
Rev No 5 Status P Date 2007-09-26 Cont ID  
Sent By bpowell Date 2007-09-26 Time 15:49 Rev Time 0.00
Received By bpowell Date 2007-09-26 Time 15:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2007-08-23 Cont ID  
Sent By bpowell Date 2007-08-23 Time 16:55 Rev Time 0.00
Received By bpowell Date 2007-08-23 Time 16:55 Sent To  
Notes
2007-08-23 17:01:291. PLANS SHALL SHOW THAT THE WALL OF THE ENCLOSURE WILL
 BE LANDSCAPED WITH SHRUBS AND HEDGES PLANTED AT
 TWO-FOOT INTERVALS, PER SECTION 94-444(B) OF THE CITY'S
 ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 2. A CHAINLINK GATE IS ALLOWED HOWEVER, IT MUST BE
 SCREENED WITH SLATS.
  
 FOR QUESTIONS OR COMMENTS CONTACT: BOBBY POWELL, JR.,
 (561) 822-1435, [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 2007-06-01 Cont ID  
Sent By bpowell Date 2007-06-01 Time 13:43 Rev Time 0.00
Received By bpowell Date 2007-06-01 Time 13:43 Sent To  
Notes
2007-06-01 13:47:12PLEASE PROVIDE DETAILS INDICATING THE SIZE AND TYPE OF
 SCREENING THAT WILL BE USED FOR THE GENERATOR.PER
 SEC. 94-444 (B), SCREENING SHALL BE CONSTRUCTED OF
 BRICK, DECORATIVE CONCRETE, OTHER DECORATIVE MASONARY,
 OR COMPARABLE WOOD OR STEEL.WALLS SHALL BE LANDSCAPED
 WITH SHRUBS AND HEDGES PLANTED AT TWO-FOOT INTERVALS.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-10-24 Cont ID  
Sent By mmclean Date 2006-10-24 Time 17:10 Rev Time 0.00
Received By mmclean Date 2006-10-24 Time 17:10 Sent To  
Notes
2006-10-24 17:12:44NOTE: THE PROPOSED GENERATOR MUST BE SCREENED WITH
 LANDSCAPE HEDGES (SCREENED FROM PUBLIC VIEW).

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-10 Cont ID  
Sent By mmclean Date 2006-08-10 Time 09:06 Rev Time 0.00
Received By mmclean Date 2006-08-10 Time 09:06 Sent To  
Notes
2006-08-10 00:00:00DENIED,
 1. PLEASE SUBMIT TWO COPY OF CURRENT SURVEY/SITEPLAN
 SHOWING THE LOCATION OF
 THE EXISTING AND NEW GENERATOR OF THE
 COMPLETE PROPERTY.
 2. CANNOT USE SITE LIGHTING PLAN AND IT
 DOES NOT IDENTIFY THE COMPLETE PROPERTY
 AND NOT LEDGERABLE TO READ.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720